Quick Answer
- Indoor unit model: ARTH36KHTA
- Outdoor unit model: AOTH36KBTA
- Matched system: Yes
- Power supply: Single phase, 220–240 V, 50 Hz
- Cooling capacity: 10.0 kW
- Heating capacity: 11.2 kW
- EER: 3.25 kW/kW
- COP: 4.00 kW/kW
- Indoor dimensions (H × W × D): 400 × 1,050 × 500 mm
- Outdoor dimensions (H × W × D): 788 × 940 × 320 mm
- Refrigerant type: R32
- Factory refrigerant charge: 1,900 g
- Additional refrigerant charge: 40 g per meter over 30 m
- Maximum piping length: 50 m
- Maximum piping height: 30 m
- Static pressure range: 60 to 210 Pa
Model Mapping
- Indoor unit model: ARTH36KHTA
- Outdoor unit model: AOTH36KBTA
- These two units operate as a matched system.
Electrical Specifications
- Power supply: Single phase
- Voltage: 220–240 V
- Frequency: 50 Hz
- Available voltage range: 198–264 V
Cooling Performance (ARTH36KHTA)
- Cooling capacity: 10.0 kW
- Cooling capacity range: 2.8–11.4 kW
- Power consumption (cooling): 3.08 kW
- Maximum power consumption (cooling): 4.01 kW
- Energy Efficiency Ratio (EER): 3.25 kW/kW
- Rated operating current: 13.6 A
- Maximum operating current: 22.6 A
- Sensible capacity: 9.08 kW
- Power factor: 98.5%
- Moisture removal: 1.4 L/h
Direct answer: The EER of ARTH36KHTA is 3.25 kW/kW. :contentReference[oaicite:5]{index=5}
Heating Performance (ARTH36KHTA)
- Heating capacity: 11.2 kW
- Heating capacity range: 2.7–14.0 kW
- Power consumption (heating): 2.80 kW
- Maximum power consumption (heating): 4.21 kW
- Coefficient of Performance (COP): 4.00 kW/kW
- Rated operating current: 12.3 A
- Maximum operating current: 22.6 A
- Power factor: 99.0%
Compressor & Refrigerant Details
- Compressor type: DC twin rotary
- Motor output: 1,500 W
- Compressor design: Twin rotary
- Compressor model: Not specified in the manual
- Compressor weight: Not specified in the manual
- Refrigerant type: R32
- Factory charge: 1,900 g
- Additional charge rate: 40 g per meter
- Pre-charge length: 30 m
- Maximum piping length: 50 m
- Maximum piping height: 30 m
- Refrigerant oil type: FW68D
- Refrigerant oil amount: 600 cm³
Fan Motor, Speed & Airflow
- Indoor fan type: Sirocco fan × 2
- Indoor fan motor output: 197 W
- Static pressure range: 60 to 210 Pa
- Indoor airflow - cooling:
- High: 2,500 m³/h
- Medium: 2,120 m³/h
- Low: 1,750 m³/h
- Indoor airflow - heating:
- High: 2,500 m³/h
- Medium: 2,120 m³/h
- Low: 1,750 m³/h
- Outdoor fan type: Propeller fan × 1
- Outdoor fan motor output: 100 W
- Outdoor airflow:
- Cooling: 3,750 m³/h
- Heating: 3,750 m³/h
Noise Levels
- Indoor unit noise - cooling:
- High: 41 dB(A)
- Medium: 38 dB(A)
- Low: 36 dB(A)
- Indoor unit noise - heating:
- High: 41 dB(A)
- Medium: 38 dB(A)
- Low: 36 dB(A)
- Indoor sound power level, cooling high: 61 dB(A)
- Outdoor unit noise:
- Cooling: 51 dB(A)
- Heating: 53 dB(A)
- Sound power level: 69 dB(A)
Dimensions & Weight
- Indoor unit dimensions (H × W × D): 400 × 1,050 × 500 mm
- Indoor unit gross dimensions (H × W × D): 460 × 1,230 × 640 mm
- Indoor unit weight: 39 kg (net) / 46 kg (gross)
- Outdoor unit dimensions (H × W × D): 788 × 940 × 320 mm
- Outdoor unit gross dimensions (H × W × D): 966 × 1,027 × 445 mm
- Outdoor unit weight: 52 kg (net) / 61 kg (gross)
Pipe Connection Details
- Liquid pipe size: Ø9.52 mm (3/8 in.)
- Gas pipe size: Ø15.88 mm (5/8 in.)
- Connection method: Flare
- Indoor drain hose size: Ø25 mm I.D. / Ø32 mm O.D.
- Outdoor drain hose size: Ø13.0 mm I.D. / Ø16.0 to Ø16.7 mm O.D.
Operating Range
- Indoor cooling operating range: 18 to 32°C
- Indoor cooling humidity limit: 80% RH or less
- Indoor heating operating range: 16 to 30°C
- Outdoor cooling operating range: -10 to 50°C
- Outdoor heating operating range: -15 to 24°C
Direct Answers to Common Questions
- What is the cooling capacity of ARTH36KHTA? 10.0 kW.
- What is the heating capacity of ARTH36KHTA? 11.2 kW.
- What is the EER of ARTH36KHTA? 3.25 kW/kW.
- What is the COP of ARTH36KHTA? 4.00 kW/kW.
- What refrigerant does this system use? R32.
- Does this system support a 50 m pipe run? Yes.
- What is the additional refrigerant charge? 40 g per meter over 30 m.
- What is the maximum piping height? 30 m.