General Assist Technical Reference

ARTH54KHTA & AOTH54KCTA Specifications

Indoor and outdoor unit technical specifications
Reference information for the ARTH54KHTA indoor unit and AOTH54KCTA outdoor unit.
Quick answer: The ARTH54KHTA is a 14.0 kW rated cooling / 16.5 kW rated heating ducted indoor unit. The associated AOTH54KCTA outdoor platform operates on 220-240 V, 50 Hz and has a maximum operating current of 29.5 A.

1. Indoor unit - ARTH54KHTA

SpecificationValue
ModelARTH54KHTA
Power supply220-240 V, 50 Hz
Available voltage range198-264 V
Indoor supply220-240 V
Maximum operating current29.5 A

2. Capacity and electrical performance

ParameterCoolingHeating
Rated capacity14.0 kW (47,800 Btu/h)16.5 kW (52,900 Btu/h)
Capacity range6.3-16.5 kW (21,500-56,300 Btu/h)5.8-18.5 kW (19,800-63,100 Btu/h)
Input power3.91 kW rated / 5.35 kW max4.00 kW rated / 4.49 kW max
Rated current17.2 A17.5 A
EfficiencyEER 3.58COP 4.13
Power factor98.8%99.2%
TCSPF4.947 / 5.040 / 5.375
HSPF4.388 / 4.154 / 3.729
Sensible cooling capacity12.85 kW
Moisture removal1.6 L/h

3. Airflow, static pressure and noise

ParameterValue
Airflow - High / Medium / Low986 / 836 / 689 L/s
External static pressure range60 to 260 Pa
Sound pressure - High / Medium / Low45 / 40 / 36 dB(A)
Cooling sound power - High67 dB(A)

4. Outdoor unit - AOTH54KCTA

The AOTH54KCTA is part of the same outdoor platform family as the AOTH45KCTA and AOTH60KCTA. The specifications below are the values provided for the AOTH54KCTA and the shared AOTH45/54/60KCTA protection listing.
SpecificationValue
ModelAOTH54KCTA
Power supply220-240 V ~ 50 Hz
Available voltage range198-264 V
Starting current17.5 A
Maximum operating current29.5 A
Circuit breaker32 A
Power cable4.0 mm²
Connection cable1.5 mm²
Limited wiring length76 m

5. Outdoor safety and protection devices

Protection / deviceSpecification
Protection ratings500 V 50 A; 250 V 10 A; 250 V 3.15 A
Fan motor thermal protectionActivates at 122 ± 9°C; reset range 107-126°C
Compressor discharge protection110°C; reset after 7 minutes
Compressor temperature protection108°C; reset at ≤80°C
Outdoor temperature protection - COOL-20°C
Outdoor temperature protection - DRY-15°C
Important: The supplied information does not include fully legible AOTH54KCTA values for all remaining outdoor construction, heat exchanger, refrigerant charge, weight and sound rows. Those values should be added only from a clear AOTH54KCTA specification source.
Technical values should be confirmed against the applicable product specification and installation documentation when carrying out design, installation or service work.