Purpose
Single reference article for specifications, dimensions, refrigerant system, wiring/PCB references, diagnostics, parts, accessories, and key service procedures for the following combinations:
Indoor: ARTG45LHTA / ARTG54LHTA
Outdoor: AOTG45LATL / AOTG54LATL
Index
Specifications
Dimensions
Refrigerant System
Electrical & Circuit References
Error Detection & Diagnostics
Outdoor Unit – Test Run
Outdoor Unit – Pump Down
Parts – Indoor Unit
Parts – Outdoor Unit
Accessories & Optional Parts
1) Specifications
Electrical Data (Cooling & Heating)
Power Source: 240 V, 50 Hz, Single phase
| Item | ARTG45LHTA + AOTG45LATL | ARTG54LHTA + AOTG54LATL |
|---|---|---|
| Cooling Capacity | 12.5 kW | 14.0 kW |
| Heating Capacity | 14.0 kW | 16.0 kW |
| Running Current (Cool) | 16.9 A | 19.5 A |
| Running Current (Heat) | 16.0 A | 18.6 A |
| Input Watts (Cool) | 4.03 kW | 4.66 kW |
| Input Watts (Heat) | 3.80 kW | 4.44 kW |
| E.E.R (Cool) | 3.10 kW/kW | 3.00 kW/kW |
| E.E.R (Heat) | 3.68 kW/kW | 3.60 kW/kW |
| Moisture Removal | 1.0 L/hr | 1.0 L/hr |
| Indoor Air Circulation | 3,250 m³/h | 3,550 m³/h |
| Outdoor Air Circulation (Cool) | 6,750 m³/h | 6,750 m³/h |
| Outdoor Air Circulation (Heat) | 6,200 m³/h | 6,850 m³/h |
| Maximum Current | 22.5 A | 23.5 A |
Noise Level
| Location | Mode | ARTG45LHTA | ARTG54LHTA |
|---|---|---|---|
| Indoor | High / Med / Low | 43 / 39 / 35 dB | 45 / 40 / 36 dB |
| Outdoor | Cool | 55 dB | 55 dB |
| Outdoor | Heat | 55 dB | 56 dB |
Fan Motor
Indoor unit discrimination: MFG-54AVN
ARTG45LHTA fan speeds (Fan1 / Fan2): High 1040/1000 rpm, Med 880/840 rpm, Low 740/700 rpm
ARTG54LHTA fan speeds (Fan1 / Fan2): High 1090/1050 rpm, Med 900/860 rpm, Low 780/740 rpm
Outdoor unit discrimination: MFE-45VVT
Cool: Upper 850 rpm, Lower 800 rpm
Heat:
AOTG45LATL: Upper 780 rpm, Lower 750 rpm
AOTG54LATL: Upper 850 rpm, Lower 830 rpm
Compressor & Refrigerant
Compressor type: Hermetic inverter, 6 poles, 3 phase, DC motor, twin rotary
Compressor discrimination: N-TF30HD1A
Weight (with oil): 15.4 kg
Refrigerant: R410A
Precharged refrigerant: 3,350 g
Additional charge: 40 g/m
Max pipe height: 30 m
Pipe length / full charge reference
20 m: 3,350 g
30 m: 3,750 g
40 m: 4,150 g
50 m: 4,550 g
2) Dimensions
Indoor Unit
H × W × D: 425 × 1,250 × 490 mm
Weight: Shipping 61 kg / Net 54 kg
Drain hose diameter: ID 23.4 mm / OD 25.4 mm
Outdoor Unit
H × W × D: 1,290 × 900 × 330 mm
Weight: Shipping 94 kg / Net 86 kg
3) Refrigerant System
Piping Sizes
Gas pipe: 15.88 mm (5/8")
Liquid pipe: 9.52 mm (3/8")
Key Components (Outdoor)
Compressor, accumulator, muffler(s)
3-way valve(s), 4-way valve
Pressure sensor, high pressure switch
Expansion valve, check valve(s), strainers
Thermistors (as referenced)
Compressor, discharge, heat exchanger (med/out), outdoor
Room, pipe
4) Electrical & Circuit References
This section is intended as a service wiring/PCB reference map for fault tracing and component location.
Circuit Diagram Coverage
Outdoor unit overall circuit reference
Indoor unit overall circuit reference
Indoor PCB circuit reference (control unit)
Outdoor PCB circuit reference (inverter assembly / power supply / transistor PCB)
Indicator PCB and LED/button layout references
Practical note: The detailed schematic symbol-by-symbol layouts are extensive. For deep PCB-level tracing (connector pinouts, component IDs, IC callouts), attach the source Word file to this article and reference it alongside the on-unit PCB markings.
ARTG45_54LHTA SM TC test
5) Error Detection & Diagnostics
A) Wired Remote Control – Error Code Display
If an error occurs, the wired controller displays an error code (with “Er” in the set room temperature display) and indicates the indoor unit number.
B) Indicator PCB – Error Display Mapping (Wired Remote / Lamps)
Error display references include:
Operation lamp (green)
Timer lamp (orange)
Eco lamp (green)
Common code groups listed in the source include (examples):
Serial communication error
Wired remote control communication error
Indoor unit capacity error
Indoor power supply interruption
Manual auto switch error
Indoor fan motor driving circuit error
Inlet air temp sensor error
Indoor heat exchanger middle temp sensor error
Drainage error
Outdoor unit model information error
Inverter error / IPM error
Discharge / compressor / outdoor temp / heat sink temp / current sensor faults
Pressure sensor error / high pressure switch error
Over current / compressor control error
Outdoor fan motor 1 / 2 error
4-way valve error
Refrigerant system discharge temp error / compressor temp error / low pressure error
C) Outdoor Unit – Indicator PCB LED Pattern Table
The outdoor indicator PCB uses LED states (ON / OFF / blinking) across:
POWER, ERROR, PUMP DOWN, LOW NOISE, PEAK CUT, MODE (L1–L6)
Workflow (field use):
Confirm ERROR LED is blinking.
Press ENTER once to step through the detail display.
Match the LED blink counts/states to the fault table to identify the specific error group (communication / sensor / inverter / pressure / motor / valve / refrigerant system).
6) Outdoor Unit – Test Run
Pre-checks (must be confirmed before test run)
Outdoor unit securely installed
Gas leak inspection completed (joints, brazing/flared connections)
Heat insulation completed (gas pipe, liquid pipe, drain extension)
Drain discharge confirmed OK
Cables connected correctly and meet specification
Earth wire correctly connected
No airflow obstructions at suction/discharge
Correct refrigerant charge confirmed
Stop valves fully open (gas & liquid)
Crankcase heater energized for more than 6 hours prior to operation
Test Run – Board Button Method (Outdoor Unit Display Board)
Enter standby (power ON)
Press ENTER for > 3 seconds to enter test run setting mode
Use SELECT to toggle COOL / HEAT
Perform the first test run in COOL
Press ENTER to start test operation
To stop: press ENTER again
Operational checks during test run:
Abnormal noise/vibration (outdoor)
Correct discharge air temp relative to mode (indoor)
If ERROR indication occurs, identify via LED patterns and rectify before repeating test
7) Outdoor Unit – Pump Down
Safety Warnings
Do not touch electrical components other than the display-board buttons.
During pump down, ensure the compressor is OFF before removing refrigerant piping.
Do not remove connection pipes while compressor is operating with valves open (risk of abnormal pressure and injury).
Procedure (Board Button Method)
Confirm both 3-way valves (liquid & gas) are open.
Turn power ON.
After 3 minutes from power on, press PUMP DOWN for ≥ 3 seconds.
Unit runs; after ~3 minutes from compressor start, fully close the liquid-side 3-way valve.
When LED state changes again, fully close the gas-side 3-way valve.
Pump down completes; fans and compressor stop automatically.
Turn power OFF.
Notes:
To stop pump down: press PUMP DOWN again.
If pump down halts due to error: power OFF → open valves → wait 3 minutes → power ON → retry.
If pump down cannot be completed, recover refrigerant from the service port.
8) Parts – Indoor Unit (Selected Lists)
Exterior / Chassis
Panel Top Sub Assy: 9380191001
Panel Rear Sub Assy: 9380205005
Panel Side R Sub Assy: 9380194002
Panel Side L Sub Assy: 9380203001
Pipe Panel: 9380262008
Drain Pan Sub Assy: 9380193005
S Drain Pan Sub Assy: 9380204008
Hook: 9372055007
Remote Control: 9318593020
Fan / Motor / Controls
Front Panel Assy: 9380271000
Sirocco Fan: 9372059029
Fan Motor: 9603087012
Controller PCB Assy (45): 9708281032
Controller PCB Assy (54): 9708281049
Power Supply PCB Assy: 9708279015
Filter PCB Assy: 9708277028
Thermistor: 9704265012
Pipe Thermistor: 9900558000
Room Thermistor: 9703299254
Evaporator Sub Assy: 9380206002
9) Parts – Outdoor Unit (Selected Lists)
Cabinet / Fans
Top Panel Sub Assy: 9374417056
Front Panel Sub Assy: 9374414109
Service Panel Sub Assy: 9374415090
Right Panel Sub Assy: 9374416189
Motor DC Brushless: 9602843039
Propeller Fan Assy: 9366378020
Base Assy: 9374166220
Drain Assy: 9303029015
Drain Cap: 313166024302
Electrical (Control Box)
Inverter PCB Assy (45): 9708690032
Inverter PCB Assy (54): 9708690049
Indicator PCB Assy: 9708678016
Power Supply PCB Assy: 9708688015
Capacitor PCB Assy: 9707257083
ACTPM: 9707592016
Transistor PCB Assy: 9708647043
Thermistor (Outdoor): 9900210069
Thermistor Assy (Heat Ex. Med/Out): 9900599027
Thermistor Assy (Discharge/Comp): 9900598013
Refrigerant Circuit Components
Compressor: 9810153005
Accumulator: 9379014021
Expansion Valve Assy: 9370947243
Expansion Valve Coil: 9970096044
4-way Valve Assy: 9374425235
Pressure Switch: 9900186012
Sensor: 9900505080
10) Accessories & Optional Parts
Indoor Unit – Accessories
Special nut A (Large flange) ×4 (ceiling suspension)
Special nut A (Small flange) ×4
Coupler heat insulation (Large) ×1 (gas pipe side)
Coupler heat insulation (Small) ×1 (liquid pipe side)
Binder (Large) ×4
Binder (Medium) ×4
Binder (Small) ×1
Remote control ×1
Screws (flush heads) ×2 (controller mounting)
Optional Parts
Wired remote control: UTY-RNNYN
Remote sensor: UTY-XSZX
External control set: UTD-ECS5A
Outdoor Unit – Accessories
Drain pipe ×1 (may vary by model)
Drain cap ×2
Binder ×3
One-touch bush ×2 (cable installation)