UTY-RNRT Function Settings - ARTH45/54/60KHTA

Purpose: This article explains how to change indoor unit Function Settings using the UTY-RNRT wired remote controller and provides the applicable function numbers and setting values for ARTH45/54/60KHTA ducted indoor units.

Important: Incorrect function settings can cause abnormal operation. Confirm the indoor unit model and apply settings only where required by the installation or site design.

Before You Start

  • The installer password may be required. Default installer password: 0000.
  • Confirm the indoor unit is ARTH45KHTA, ARTH54KHTA or ARTH60KHTA.
  • Identify whether the setting is being applied to one indoor unit address or to All connected indoor units.

How to Change Function Settings

  1. From Monitor Mode, open Menu and navigate to Maintenance.
  2. Select Function Setting.
  3. Touch Address.
  4. Use ▲/▼ to select the indoor unit address, or select All, then touch OK.
  5. Touch Function No., select the required Function Number with ▲/▼, then touch OK.
  6. Touch Setting No., select the required Setting Value with ▲/▼, then touch OK.
  7. Touch Setting to write the selected values to the chosen address.
  8. Touch Back to return to the Maintenance screen.
  9. When all required settings are complete, power-cycle the system OFF then ON.

Function Setting Reference

Function 11 - Filter Sign Interval

Factory setting: 03 - No indication

SettingFunction
00Standard - 2500 hours
01Long interval - 4400 hours
02Short interval - 1250 hours
03No indication - factory setting

Functions 30 / 31 - Indoor Unit Sensor Correction

30 = Cooling   |   31 = Heating
Factory setting: 00 - Standard setting

SettingCorrection
00Standard setting - factory
010.0°C
02-09-0.5°C to -4.0°C - More cooling / Less heating
10-17+0.5°C to +4.0°C - Less cooling / More heating

Functions 35 / 36 - Wired Controller Sensor Correction

35 = Cooling   |   36 = Heating
Factory setting: 00 - No correction

SettingCorrection
00No correction - factory
010.0°C
02-09-0.5°C to -4.0°C
10-17+0.5°C to +4.0°C

Controller sensor note: For wired-controller sensor control, Function 42 must be set to 01 (Both) and the Thermo Sensor icon must be displayed on the controller.

Function 26 - Static Pressure

Factory setting: 31 - Standard 60 Pa

SettingStatic Pressure
06-2660-260 Pa in 10 Pa increments (06=60 Pa, 07=70 Pa ... 26=260 Pa)
31Standard 60 Pa - factory setting
32Automatic airflow adjustment

Automatic airflow adjustment - Setting 32:

  • Do not use where a booster fan is installed between ducts.
  • Ensure external static pressure remains within the allowable range.
  • Set Function 26 to 32, operate Fan mode - High, allow the unit to run and stop automatically, then power-cycle the system and record the obtained setting.

Function 40 - Auto Restart

SettingBehaviour
00Enable - factory setting
01Disable

Functions 42 / 48 - Room Temperature Sensor Switching

FunctionSettingSelection
4200Indoor unit - factory setting
4201Both
4800Both
4801Wired remote controller - factory setting

Function 48 only operates when Function 42 is set to 01 (Both).

Function 43 - Cold Air Prevention

SettingFunction
00Enable - factory setting
01Disable

Function 46 - External Input Control

SettingMode
00Operation/Stop mode 1 - factory setting
01Setting prohibited
02Forced stop mode
03Operation/Stop mode 2

Function 49 - Cooling Energy-Saving Fan Control

Factory setting: 02 - Remote controller

SettingBehaviour
00Disable - continuous indoor fan when outdoor unit is stopped
01Enable - intermittent very low fan speed
02Remote controller - factory setting

Function 60 - External Output Terminal

SettingOutput Function
00Operation status - factory setting
09Error status
10Fresh air control
11Auxiliary heater

Functions 68 / 69 - Auto Mode

FunctionSettingSelection
6800Single setpoint auto - factory setting
6801Dual setpoint auto
69000°C deadband - factory setting
6901-090.5°C to 4.5°C in 0.5°C increments

Final check: Record any altered function numbers and setting values on the commissioning documentation. After changes are complete, power-cycle the system and verify normal heating, cooling and fan operation.