General Assist Customer Support

Split System Is Running but Not Cooling

What to check when the indoor unit is blowing air but the room is not getting cold
Quick answer: If your split system is set to COOL but only blows room-temperature air, the indoor fan may be operating while the refrigeration system is not producing cooling. Start with the settings, airflow and power-reset checks below. If cooling does not return, service may be required.

1. Confirm the settings

  1. Set the air conditioner to COOL mode - usually shown by a snowflake icon. Do not use AUTO for this test.
  2. Set the temperature to 18-20°C.
  3. Set the indoor fan speed to HIGH.
  4. Allow the system 10-15 minutes to stabilise.
Why this matters: Testing in COOL mode at a low set temperature removes most normal control variables and makes it easier to confirm whether the refrigeration system is actually producing cooling.

2. Basic checks at home

CheckWhat to look for
FiltersClean dirty filters. Restricted airflow can reduce performance and may contribute to protection operation.
Outdoor unitCheck whether the outdoor unit appears to be operating normally, including fan operation and normal operating sound.
IcingLook for ice on the indoor coil behind the filters or on exposed outdoor pipework.
If you see significant ice: Turn the system off and arrange service. Continued operation while iced can worsen the condition and may cause water leakage when the ice melts.

3. Perform a safe reset

  1. Turn the air conditioner OFF using the remote controller.
  2. Turn power OFF at the air-conditioning isolator, switch or circuit for approximately 2 minutes.
  3. Restore power.
  4. Set the system back to COOL, 18-20°C and HIGH fan, then retest.

4. If it still does not cool

If the unit continues to blow room-temperature air after the checks above, a technician will generally need to inspect the system.

Possible cause: low refrigerant due to a leak

Refrigerant does not normally get "used up". If a system is low on refrigerant, there is usually a leak that should be located and repaired. Simply adding refrigerant without addressing the leak can result in the same fault returning.

Possible cause: outdoor unit or control fault

Electrical, inverter, compressor or control faults can prevent the outdoor unit from producing cooling even though the indoor fan continues to run.

5. What a technician will typically check

  • Confirm system operation and cooling performance
  • Measure relevant temperatures and operating pressures
  • Carry out leak checks where indicated
  • Repair any confirmed leak and recharge the system to specification where required
  • Check the outdoor unit, electrical controls, inverter and compressor operation as applicable
  • Verify correct cooling output before completion

6. Information to provide when contacting support

To help speed up diagnosis, provide:

  • Model number from the indoor unit rating label
  • Confirmation that the unit is set to COOL
  • Whether the outdoor unit is operating
  • Any flashing lights or displayed error codes
  • A photo or short video showing the indoor display/indicator lights and the outdoor unit while the system is running
Safety: Do not open refrigeration components or attempt to add refrigerant yourself. Refrigerant handling and sealed-system work must be completed by an appropriately licensed technician.
Outcome: If correct COOL-mode settings, clean airflow paths and a power reset do not restore cooling, arrange service so the refrigeration circuit, outdoor unit and controls can be properly tested.
General Assist Customer Support