General Assist Technical Reference

VRF Master Indoor Unit Setup

Administrative indoor unit configuration for 2-pipe AIRSTAGE VRF systems
Outdoor unit function setup, wired remote controller configuration and system verification
The Administrative Indoor Unit, commonly referred to as the Master Indoor Unit, controls the operating mode for all indoor units connected to the same 2-pipe refrigerant system. Each indoor unit can still maintain its own temperature setpoint.
Important: Only one Master Indoor Unit may be configured per refrigerant system. Complete system addressing before carrying out this procedure.

1. Purpose

The Administrative Indoor Unit, commonly referred to as the Master Indoor Unit, controls the operating mode - Cool, Heat or Auto - for all connected indoor units in a 2-pipe system.

  • All slave indoor units follow the operating mode selected by the Master.
  • Each indoor unit can maintain an independent temperature setpoint.
  • The first indoor unit powered on may dictate the initial Cool or Heat mode until a Master is configured.
  • Master setup must be completed before commissioning.
Master indoor unit overview

2. Preparation

  1. Verify all indoor units and the outdoor unit are powered on.
  2. Confirm system addressing has been completed, either manually or automatically.
  3. Confirm the communication wiring X1 / X2 is correctly installed and polarity is maintained.
  4. Confirm there are no active outdoor unit errors. LED101 should be illuminated green and LED102 should be off.

3. Enable Administrative Control at the Outdoor Unit

Use the outdoor unit PCB push buttons to enable Function F2-21-02.

StepActionDisplay
1Press MODE/EXIT (SW107) onceF1
2Press SELECT (SW108) onceF2
3Press ENTER (SW109) once00 00
4Press SELECT (SW108) eight times21 00
5Press ENTER (SW109) once21 00 confirmed
6Press SELECT (SW108) twice21 02
7Press ENTER (SW109) once21 02 confirmed
8Press MODE/EXIT (SW107) three timesDisplay clears and the function is saved
Function result: F2-21-02 enables Administrative Indoor Unit operation for the connected refrigerant system.
Outdoor unit function setting

4. Set the Master Indoor Unit on the Wired Remote Controller

Use the touch-screen Wired Remote Controller connected to the indoor unit that will become the Master.

  1. From the Monitor screen, press Menu.
  2. On Main Menu Page 1, select Next Page.
  3. On Main Menu Page 2, select Initial Setting.
  4. On Initial Setting Page 1, press Next Page.
  5. On Initial Setting Page 2, select Master Indoor Unit Setting.
  6. Enter the installer password. The factory default is 0000. If the password has been changed, enter the current installer password.
  7. When the screen shows Not Master Indoor Unit, press Set.
  8. At the confirmation prompt, press Yes.
The connected indoor unit is now registered as the system's Master Indoor Unit.
Wired remote controller master indoor unit setup

5. Verification

  • The Master controller should display a Master indicator.
  • Slave units should follow the Master's Cool, Heat or Auto mode.
  • Each slave unit should retain its own temperature setpoint.
  • Only one Master should be configured for each refrigerant system.

6. Notes for 2-Pipe Systems

  • All indoor units on the same outdoor circuit follow the Master's operating mode.
  • Cool-to-Heat or Heat-to-Cool changes must be initiated from the Master unit.
  • A slave attempting to select the opposite mode may display Operation restricted by Master.

7. Optional RB Unit Priority Settings

For systems with multiple indoor units connected through an RB unit, DIP switch SET2 controls operating-mode priority and Cool/Heat control time.

SettingDIP Switch PositionResult
Factory mode prioritySET2-1 OFF, SET2-2 OFFPriority to first command
Administrative IU prioritySET2-1 OFF, SET2-2 ONPriority to Administrative Indoor Unit
Factory Cool/Heat control timeSET2-3 OFF, SET2-4 OFF6-minute control time

8. Final Confirmation

  1. Turn on the Master indoor unit.
  2. Confirm the system enters the selected Cool or Heat mode.
  3. Verify all slave units respond in the same operating mode.
  4. Record the Master indoor unit address and remote controller ID in the commissioning documentation.

9. Troubleshooting

SymptomPossible CauseCorrective Action
Cannot select MasterOutdoor function F2-21-02 is not enabledComplete the outdoor unit function setup
Master not recognizedSystem addressing is incompleteRe-address indoor units and repeat verification
Slave units do not follow the MasterCommunication wiring fault or duplicate MastersCheck X1/X2 wiring and confirm only one Master is assigned
Installer password rejectedThe factory password has been changedConfirm the current installer password with the system administrator
Setup sequence: Enable F2-21-02 at the outdoor unit, nominate the Master using the touch-screen wired remote controller, then confirm mode synchronisation across the refrigerant system.