1. Purpose of RB Address Setting

The Refrigerant Branch (RB) Unit serves as the intermediate junction between the outdoor and indoor units in a VRF Heat Recovery System.
To ensure correct communication and refrigerant control:

  • The Refrigerant Circuit Address (REF AD) of the RB unit must match the outdoor and indoor units.

  • The RB Address (RB AD) must correspond to the indoor unit(s) connected downstream of it.


2. Location of Address Dials

On the RB Unit PCB, you will find two sets of rotary switches:

Switch TypePurposeLabel on PCB
REF AD (x10 / x1)Refrigerant circuit addressSW606, SW607
RB AD (x10 / x1)RB unit addressSW604, SW605

The positions may differ slightly depending on the RB model (single or multi-port type), but the setting method is identical.



3. Step 1 – Set the Refrigerant Circuit Address (REF AD)

Each RB unit must share the same REF AD as the outdoor and indoor units within the same refrigerant circuit.

ExampleREF AD x10REF AD x1
0303
1111
2525

Setting Range: 00 – 99

If the RB’s REF AD differs from the outdoor unit, the system will not operate.



4. Step 2 – Set the RB Unit Address (RB AD)

Each RB unit must be assigned a unique address within its refrigerant circuit to identify which indoor unit group it serves.

Procedure:

  1. Locate the rotary switches marked RB AD x10 and RB AD x1.

  2. Set each dial to the desired address number using the tables or diagrams.

  3. Match the RB address to the Indoor Unit address of the connected zone.

| Example Configuration |
|:--|:--|
| REF AD = 03 (common for the system) | RB AD = same as corresponding IU AD |

RB UnitREF ADRB ADConnected IU AD
RB1030101
RB2030202
RB3030404

Recommendation:
Set the RB AD to the same number as the Indoor Unit (IU AD) it serves.
This simplifies fault tracing and service verification.


5. Step 3 – Address Range and Restrictions

Setting TypeValid RangeInvalid RangeRemarks
REF AD00 – 99Must match Outdoor and IU
RB AD00 – 6364 – 9964–99 cannot communicate with the outdoor unit

If an RB unit address is set between 64 and 99, communication failure will occur, and the system will not recognize that RB unit.


6. Step 4 – Multi-Port RB Unit Configuration

For multi-type RB units, each refrigerant control port has its own PCB (circuit board).
Set addresses individually for each active board (connected port).

RB PortConnectionSetting Requirement
IU connectedSet REF AD and RB AD
IU connectedSet REF AD and RB AD
No IU connectedLeave unset
IU connectedSet REF AD and RB AD

Only configure ports that are connected to indoor units.
Blank ports do not require address assignment.



7. Step 5 – Verification

After setting all addresses:

  1. Power ON the system.

  2. Confirm communication via the indoor controller or commissioning tool.

  3. Ensure that:

    • REF AD is identical across all units (OU, RB, IU).

    • RB AD matches the corresponding IU AD.

    • No duplicate RB addresses exist within the same refrigerant circuit.


8. Quick Reference Summary

ComponentAddress TypeSetting RangeRelationship
Outdoor UnitREF AD00–99Common across system
RB UnitREF AD00–99Match Outdoor Unit
RB UnitRB AD00–63Match connected IU AD
Indoor UnitREF AD00–99Match Outdoor Unit
Indoor UnitIU AD00–63Unique per IU

9. Notes & Best Practices

  • Always confirm address positions before power-up to avoid bus communication errors.

  • When replacing RB PCBs, reapply the same address settings.

  • For multi-split or multi-branch systems, document all REF and RB addresses for service traceability.