VRF J Type Commissioning

This article provides a quick-reference guide for commissioning J Series VRF systems, including outdoor unit addressing and indoor unit addressing.

Important Commissioning Notes
  • This information is intended as a reminder and quick reference.
  • All installations must comply with the applicable installation manuals, design and technical manuals, and project selection documentation.
  • Commissioning information may vary between models, unit types and product generations.
  • Always refer to the specific documentation for the model being commissioned.

Outdoor Unit Addressing

Each outdoor unit connected to a common VRF wiring network requires a unique address.

  • Even where units are not connected as one combined system, it is recommended that each outdoor unit is assigned a unique REF address.
  • This makes future connection to a central controller easier.
  • It also improves troubleshooting by helping identify individual outdoor units.
Before applying power: Set the refrigerant circuit / outdoor unit address using the applicable rotary switch setting before the outdoor unit is powered.

When manually addressing outdoor units, Fujitsu recommends starting at 01 for the outdoor units and assigning each unit a unique address.

Refrigerant Circuit Address

The outdoor unit uses rotary switches to set the refrigerant circuit address. The correct switch combination depends on the required address.

Record the selected address for each outdoor unit as part of the commissioning documentation.

Indoor Unit Addressing by PCB

Indoor units can also be manually addressed using the rotary switches located on the indoor unit PCB.

  1. Confirm the outdoor unit and all indoor units are configured with the same refrigerant circuit address.
  2. Assign each indoor unit a unique indoor unit address.
  3. Do not duplicate an indoor unit address on the same refrigerant circuit.
  4. Set all required addresses while the units are not powered, unless the model-specific procedure states otherwise.
  5. After changing PCB address settings, power-cycle the applicable units if required for the new settings to take effect.

Recommended Addressing Practice

ItemRecommended Practice
Outdoor unit addressUse a unique address for every outdoor unit on the wiring network.
Refrigerant circuitOutdoor and associated indoor units must use the same refrigerant circuit address.
Indoor unit addressEach indoor unit requires a unique address within the refrigerant circuit.
Before power-upConfirm all rotary switch and PCB address settings are correct.

Commissioning Checklist

  1. Confirm the correct model-specific installation and technical documentation is available.
  2. Set the outdoor refrigerant circuit address.
  3. Assign a unique outdoor unit address where applicable.
  4. Confirm all indoor units are on the correct refrigerant circuit.
  5. Assign a unique address to every indoor unit.
  6. Check for duplicated or missing addresses.
  7. Power the system and confirm the addressing is recognised correctly.
  8. Record the final address configuration for future service and controls integration.
Source: VRF J Type Commissioning article reference.