Overview

The System Signal Test verifies serial communication between indoor and outdoor units in a split or multi-system configuration. This diagnostic ensures that both units are correctly exchanging control signals through the communication line.

Signal testing can be performed from either the indoor or outdoor terminal block, allowing technicians to isolate faults in the communication wiring or unit control boards.


Safety Warning

⚠️ Live DC and AC Circuits
Always use insulated probes and avoid shorting terminals.
Testing is performed with power ON—take necessary precautions.


Testing Conditions

  • Ensure power supply is active and both units are energized.

  • Use a digital multimeter set to DC voltage.

  • Identify the following terminals on both indoor and outdoor PCBs:

    • Terminal 1 – L (Live)

    • Terminal 2 – N (Neutral)

    • Terminal 3 – Signal


Procedure

1. Indoor Unit Test

  1. Locate the indoor terminal block.

  2. Disconnect the signal wire (Terminal 3) leading to the outdoor unit.

  3. Measure voltage between Terminal 2 (Neutral) and the disconnected signal wire.

    • This measures the outdoor unit signal returning to the indoor connection.

  4. Expected DC Voltage Range:

    • Depending on model type, expected readings vary (see table below).

Model TypeIndoor Signal
AST & ART/C60 – 120V DC
ASTA & ASTB40 – 90V DC
ASTGApprox. 200V DC (Static)
ARTG & 3 PhaseApprox. 295V DC (Static)
ARTH50 – 250V DC

2. Outdoor Unit Test

  1. Move to the outdoor unit’s terminal block.

  2. Disconnect the same signal cable (Terminal 3) connected to the indoor unit.

  3. Measure voltage between Terminal 2 (Neutral) and the disconnected signal wire.

    • This tests for the indoor unit signal reaching the outdoor terminal.

  4. Expected DC Voltage Range:

Model TypeOutdoor Signal
AOTA60 – 120V DC
AOTG3 – 110V DC
AOTH3 – 110V DC

3. Cross-Check Communication

  • If the indoor test shows normal voltage but outdoor test does not (or vice versa), the interconnecting signal cable may be damaged or open circuit.

  • If no signal is detected on both ends, suspect a fault on the indoor or outdoor control PCB.


Diagnosis and Interpretation

ObservationDiagnosisRecommended Action
Signal voltage within range on both unitsCommunication normalNo fault detected
Signal on one side onlyBroken or disconnected interconnect cableCheck and repair wiring
No signal from either unitPCB fault (indoor or outdoor)Replace control board
Unstable or fluctuating signalPoor connection or noise interferenceCheck terminations and grounding

Technical Notes

  • The communication line (Terminal 3) carries a DC serial data signal used for system control between indoor and outdoor units.

  • Typical voltage is measured as an average of pulsed DC—values may fluctuate during operation.

  • Always ensure terminal 2 (Neutral) is used as the reference when measuring.

  • For multi-split systems, test each indoor-to-outdoor pair individually.