Overview

The 3-Wire Remote Signal Test verifies communication integrity between the wall-mounted remote controller and the indoor unit.
This test confirms DC supply voltage and signal pulse transmission to ensure correct system control operation.


Safety Warning

⚠️ Low Voltage Circuit – Handle with Care
Always use insulated multimeter probes and avoid shorting terminals.
Testing is conducted on live DC circuits (approx. 12V DC).


Testing Conditions

  • Ensure the wall controller and indoor unit are connected and powered.

  • Use a digital multimeter capable of measuring DC voltage.

  • Test points: Y1 (12V), Y2 (Signal), and Y3 (Common) terminals located on the rear of the remote controller.


Terminal Identification

TerminalWire ColourFunction
Y1Red+12V DC Power
Y2WhiteSignal Line
Y3BlackCommon (GND)

Procedure

1. Verify DC Power Supply

  • Measure voltage between Y1 (Red) and Y3 (Black).

  • Expected reading: 12V DC (no less than 11.4V DC).

  • If no voltage is present, the controller PCB or power supply may be faulty.

2. Verify Signal Output from Remote

  • Disconnect the Y2 (White) signal wire from the terminal.

  • Measure between Y2 (White) and Y3 (Black) at the controller.

  • Expected reading: Fluctuating 7–12V DC (pulsed) — indicating active data transmission.

3. Verify Signal from Indoor Unit

  • With Y2 disconnected, measure between the Y3 (Black) terminal and the Y2 wire leading to the indoor unit.

  • Expected reading: Fluctuating 7–12V DC (pulsed).

  • This confirms signal communication between the remote and indoor PCB.

4. Confirm Indoor–Outdoor Communication

  • If all remote signal readings are correct, verify data transmission between indoor and outdoor units using the service communication test procedure.


Diagnosis and Interpretation

ObservationDiagnosisRecommended Action
12V DC present between Y1–Y3Power supply normalProceed with signal test
No voltage between Y1–Y3Faulty controller or missing DC supplyReplace controller PCB
7–12V fluctuating signal between Y2–Y3Signal circuit normalNo fault detected
No fluctuation on Y2–Y3Signal transmission faultReplace controller or indoor PCB
Signal correct but no operationIndoor–Outdoor comms faultPerform communication check

Technical Notes

  • The 3-wire communication uses a 12V DC power and data pulse system.

  • A fluctuating signal (7–12V DC) confirms active digital communication.

  • Stable voltage (no fluctuation) indicates a stuck signal or controller fault.

  • Always test continuity of the Y2 communication line if faults persist.