Technical Service Reference

Intelligent Power Module Testing

IPM / TR PCB diode-test procedure and diagnostic interpretation
For qualified technicians diagnosing inverter compressor drive circuits
The Intelligent Power Module (IPM), also referred to as the TR PCB, switches and drives the compressor motor. This procedure checks the integrity of the module's internal transistors and diodes using a digital multimeter.
High-voltage hazard: Isolate all electrical supplies and fully discharge capacitors before testing. Failure to do so may cause electric shock, serious injury, or permanent PCB damage.

1. Testing conditions

  • Power must be OFF and isolated.
  • Discharge the DC bus capacitors and verify that stored voltage has reduced to a safe level.
  • Disconnect all control harnesses and the compressor terminal harness U, V and W.
  • Set a digital multimeter to Diode Test Mode.
Do not perform resistance or diode measurements on an energised circuit. Do not reconnect the compressor until all measurements and inspections are complete.

2. Test procedure

Identify the IPM terminals

TerminalFunction
U, V, WCompressor output phases
PPositive DC bus
NNegative DC bus
1Positive bus test: Place the black lead on P. Place the red lead on U, V and W one at a time. Each reading should be approximately 0.4 V.
2Negative bus test: Place the red lead on N. Place the black lead on U, V and W one at a time. Each reading should be approximately 0.4 V.
3DC bus test: Black lead on P and red lead on N should read 0.7-0.9 V.
4Reverse DC bus test: Black lead on N and red lead on P should show open circuit (O/L).

3. Reference values

Black leadRed leadExpected value
PUApprox. 0.4 V
PVApprox. 0.4 V
PWApprox. 0.4 V
UNApprox. 0.4 V
VNApprox. 0.4 V
WNApprox. 0.4 V
PN0.7-0.9 V
NPO/L

4. Diagnosis and interpretation

ObservationLikely diagnosisRecommended action
Readings within specificationIPM diode paths appear normalContinue diagnosis of the compressor, power supply and control circuits as required
0 V across all measurementsIPM short circuitReplace the IPM board
O/L on all readingsInternal transistor or diode path openReplace the IPM board
Low or inconsistent readingsPartial short, leakage, or damaged junctionReplace the IPM board
Fuse or circuit breaker trips during power-upInternal IPM fault or DC bus shortInspect the power board and DC bus before replacing the IPM

5. Technical notes

  • Confirm the ACTPM and power supply boards are functioning correctly before replacing the IPM.
  • Inspect the compressor windings and terminals for earth leakage, phase-to-phase imbalance, or signs of heat damage.
  • When replacing the IPM, apply fresh thermal compound evenly between the module and heat sink.
  • Ensure all electrical connectors are clean, tight, correctly seated, and free from moisture or corrosion.

6. Board diagrams

IPM board terminal identification diagram
IPM diode test reference diagram
Service reminder: Always follow the applicable model service manual and wiring diagram. Component layout and expected readings may vary between inverter platforms.