AIRSTAGE Technical Reference

Pressure Transducer Sensor Testing

Live voltage, diode testing and fault diagnosis
For outdoor-unit refrigerant pressure sensors used in heating and cooling systems
The pressure transducer converts refrigerant pressure into a proportional DC voltage signal. The outdoor control PCB uses this signal to manage compressor frequency, expansion valve operation and system protection.
Safety: Live testing must only be completed by suitably qualified personnel. Isolate power before unplugging the sensor or performing diode checks, and allow capacitors to discharge fully.

1. Function overview

  • The sensor receives a 5 V DC reference supply from the outdoor control PCB.
  • It returns a variable 0.5-4.5 V DC signal proportional to refrigerant pressure.
  • The sensing element uses a semiconductor diaphragm and strain gauge that changes resistance as pressure changes.
Terminal colourFunction
Red+5 V DC supply from PCB
BlackGround (0 V)
WhiteSignal return / pressure output

2. Power-on test

Objective: Confirm the correct sensor supply voltage and pressure-dependent output signal.
  1. Power on the outdoor unit and allow the system to operate for several minutes.
  2. Set the multimeter to DC voltage.
  3. Measure between the red wire and black wire. Confirm approximately 5.0 V DC.
  4. Measure between the white wire and black wire. Record the signal voltage.
  5. Compare the voltage with the corresponding refrigerant pressure using the reference chart or the M Technician App.
Measured voltageApprox. pressure
0.5 V0 kPa - vacuum / low pressure
1.0 V700 kPa
1.5 V1400 kPa
2.0 V2100 kPa
2.5 V2700 kPa
2.8 V2875 kPa
3.0 V3000 kPa
4.0 V4200 kPa
4.5 V5000 kPa - high pressure cut
Measurement tip: Use the sensor's black ground wire as the reference point for all live voltage measurements.
Pressure transducer live voltage test

Example: A 2.8 V DC return signal corresponds to approximately 2875 kPa.

Pressure transducer voltage to pressure reference

3. Power-off diode test

Objective: Verify the internal sensor circuit and identify short, open or earth faults.
  1. Turn off system power and ensure all capacitors have discharged.
  2. Unplug the transducer connector from the PCB.
  3. Set the multimeter to diode mode.
  4. Measure each terminal combination shown below.
Multimeter leadsExpected reading
Black to White1.0-1.1 V
Black to Red1.2-1.3 V
White to Red1.6-1.7 V
Red to Black0.6-0.7 V
White to Black0.5-0.6 V
Red to White0.6-0.7 V
Earth to any leadO/L
Pressure transducer diode test reference

Interpretation

  • All readings within range: sensor condition is normal.
  • O/L between signal and supply: possible open circuit.
  • Very low reading below 0.3 V: possible internal short or moisture intrusion.
  • Continuity to earth: ground fault; replace the sensor.

4. Fault diagnosis

SymptomPossible causeService action
No voltage outputOpen circuit or disconnected plugCheck connector and harness continuity
Fixed at 0.5 V or 5 VInternal sensor failureReplace sensor
Unstable or fluctuating voltageLoose terminal or moistureClean, dry and reseat connector
Incorrect voltage-pressure relationshipCalibration drift or sensor wearReplace pressure sensor
Discharge or suction sensor errorPCB detects short or open circuitConfirm with live and diode tests, then replace as required

5. Service notes

  • Normal signal range is 0.5-4.5 V DC.
  • A reading below 0.5 V may indicate vacuum or no pressure. A reading above 4.5 V may indicate an overpressure condition.
  • Test only under stable running conditions. Start-up and defrost readings may be transient and unsuitable for diagnosis.
  • Do not megger test the pressure transducer. High insulation-test voltage can damage the sensing element.

6. Summary

  • Supply: 5.0 V DC between red and black.
  • Signal: 0.5-4.5 V DC between white and black, proportional to refrigerant pressure.
  • Power-off test: Diode readings confirm internal circuit integrity.
  • Reference: Compare voltage and pressure using the M Technician App.