Description

The pressure transducer sensor is a critical input component used to monitor the refrigerant system pressure in both heating and cooling modes. It converts the mechanical refrigerant pressure into a proportional DC voltage signal that the outdoor control PCB interprets to optimize compressor frequency, expansion valve operation, and system safety.

This procedure ensures the transducer’s voltage response and internal circuit integrity meet manufacturer specifications.


1. Function Overview

  • The sensor operates using a 5V DC reference supplied from the outdoor control board.

  • It provides a variable voltage output (0.5V–4.5V DC) proportional to system pressure.

  • The transducer consists of a semiconductor diaphragm with a strain gauge that changes resistance under pressure.

Terminal ColourFunction
Red+5V DC Supply (from PCB)
BlackGround (0V)
WhiteSignal Return (Pressure Output)

2. Power-On Test (Live Voltage Test)

Objective:

Confirm correct supply voltage and pressure signal output.

Procedure:

  1. Power on the outdoor unit and allow the system to operate for a few minutes.

  2. Set multimeter to DC voltage mode.

  3. Place multimeter probes as follows:

    • Red lead on Red wire

    • Black lead on Black wire

    • Confirm 5.0 V DC supply.

  4. Then measure the signal output voltage:

    • Red lead on White wire

    • Black lead on Black wire

    • Note the reading (should vary with pressure).

  5. Compare the voltage against the corresponding pressure value using the chart or M Technician App.

Example:

Measured Voltage (V)Approx. Pressure (kPa)
0.50 (Vacuum / Low pressure)
1.0700
1.51400
2.02100
2.52700
2.82875
3.03000
4.04200
4.55000 (High Pressure Cut)

Example Reading:
Measured 2.8V DC = approximately 2875 kPa, which is within normal discharge operating range.

Tip:
Use the black ground wire of the transducer as the reference point for all voltage measurements to ensure accuracy.


3. Power-Off Test (Diode / Resistance Check)

Objective:

Verify sensor circuit integrity and rule out short or open circuit conditions.

Procedure:

  1. Turn off system power and ensure capacitors are fully discharged.

  2. Unplug the transducer connector from the PCB.

  3. Set the multimeter to diode mode.

  4. Measure between the following pin combinations:

Multimeter LeadsExpected Reading (V)
Black → White1.0V – 1.1V
Black → Red1.2V – 1.3V
White → Red1.6V – 1.7V
Red → Black0.6V – 0.7V
White → Black0.5V – 0.6V
Red → White0.6V – 0.7V
Earth → Any leadO/L (Open Circuit)

Interpretation:

  • All readings within range → Sensor OK.

  • O/L between signal and supply → Open circuit fault.

  • Very low readings (<0.3V) → Internal short or moisture intrusion.

  • Continuity to earth → Ground fault; replace sensor.


4. Fault Diagnosis and Corrective Action

SymptomPossible CauseService Action
No voltage outputOpen circuit or disconnected plugCheck harness continuity
Fixed voltage (e.g., 0.5V or 5V)Sensor internal failureReplace sensor
Unstable or fluctuating voltageLoose pin contact / moistureClean, dry, and reseat connector
Incorrect voltage-pressure relationshipCalibration drift / sensor wearReplace pressure sensor
Error code (Discharge / Suction Sensor Error)Short or open detected by PCBVerify with diode test and replace as required

5. Service Notes

  • Normal operating range: 0.5V–4.5V DC.

  • Voltage <0.5V indicates vacuum / no pressure, >4.5V may indicate overpressure condition.

  • Always test under stable running conditions — transient readings during start-up or defrost are not valid.

  • Avoid megger testing the transducer — it can damage the sensing element.


6. Example Reference

Live Reading:

  • Voltage (White–Black): 2.8V DC

  • Calculated Pressure: ≈2875 kPa

Diode Check (Unplugged):

  • Black → White: 1.05V

  • Black → Red: 1.27V

  • White → Red: 1.67V
    → Sensor condition: Normal


7. Summary

  • Supply voltage: 5.0 V DC between Red and Black.

  • Signal output: 0.5 – 4.5 V DC proportional to refrigerant pressure.

  • Diode test: Confirms sensor integrity when unplugged.

  • Always compare voltage to pressure using the M Technician App for accurate diagnosis.



Example: 2.8V DC return corresponds to approximately 2875 kPa.


Power Off Test:

  1. Measure voltage resistance as per table below