Description

Electronic Expansion Valves (EEVs) regulate refrigerant flow through the system by using a stepper motor controlled via precise voltage pulses.
The EEV coil converts electrical signals from the outdoor PCB into linear or rotary motion to adjust valve position, ensuring efficient system performance during cooling, heating, and defrost operations.

Testing the EEV coil verifies electrical continuity and insulation integrity to confirm proper actuator function.


1. Test Objective

To measure the coil resistance of the EEV actuator and confirm it falls within the manufacturer’s specification.
Incorrect resistance readings indicate a damaged coil, shorted winding, or open circuit condition.


2. Tools Required

  • Digital multimeter (minimum 0.1 Ω accuracy)

  • Insulated test probes

  • Manufacturer’s coil resistance chart

  • Inspection torch and dielectric grease (for terminal corrosion prevention)


3. Inspection Before Testing

Before electrical measurement:

  • Visually inspect coil harness and connector pins for corrosion, oxidation, or moisture intrusion.

  • Ensure the coil is firmly clipped to the EEV body for effective magnetic coupling.

  • Verify that the EEV wiring harness is free from cuts or insulation damage.


4. Coil Testing – Resistance Method

Step 1 – Isolate Power

Disconnect system power supply and allow capacitors to discharge fully.
Unplug the EEV connector from the PCB before measurement.


Step 2 – Multimeter Setup

Set the digital multimeter to the Ω (resistance) range.


Step 3 – Measure and Record Readings

(a) 5-Wire Coil – 12 V Type

Test LeadsExpected Reading (Ω)Remarks
Red → White45 – 50 ΩNormal range
Red → Orange45 – 50 ΩNormal range
Red → Yellow45 – 50 ΩNormal range
Red → Blue45 – 50 ΩNormal range
Earth → All other leadsO/LNo continuity to ground

Coil identification: Red = common; remaining four are individual windings.


(b) 6-Wire Coil – 12 V Type

Test LeadsExpected Reading (Ω)Remarks
Red → White45 – 50 ΩNormal range
Red → Orange45 – 50 ΩNormal range
Brown → Yellow45 – 50 ΩNormal range
Brown → Blue45 – 50 ΩNormal range
Earth → All other leadsO/LNo continuity to ground

Coil identification: Red and Brown are common supply leads for two coil sets (4-phase stepper).


(c) J-Series High-Resistance Coil – 12 V Type

Test LeadsExpected Reading (Ω)Remarks
Red → White150 ΩStandard phase resistance
Red → Orange150 ΩStandard phase resistance
Brown → Yellow150 ΩStandard phase resistance
Brown → Blue150 ΩStandard phase resistance
Blue → Yellow300 ΩCombined coil reading
Orange → White300 ΩCombined coil reading
Earth → All other leadsO/LNo continuity to ground

Step 4 – Evaluate Results

ConditionObservationAction
NormalAll readings within rangeCoil OK
Open circuitO/L between red and phase wiresReplace coil
Short circuit< 40 Ω (low resistance)Replace coil
Ground faultResistance between coil and earthReplace coil and inspect wiring

5. Understanding the Coil Configuration

5-Wire Configuration

  • One common feed (Red) energizes four separate phases.

  • Each phase winding is controlled sequentially to move the valve step-by-step.

(Refer to diagram: Red = COM; White/Orange/Yellow/Blue = Phases)

6-Wire Configuration

  • Two common feeds (Red and Brown) control two paired phase sets.

  • Provides higher torque and smoother motion, commonly used in large-capacity VRF systems.

(Refer to diagram: Red/Brown = COM; White/Orange/Yellow/Blue = Phases)


6. Common Faults and Causes

SymptomLikely CauseCorrective Action
EEV not stepping / stuck openOpen circuit in one or more coil phasesReplace coil
Abnormal refrigerant pressuresMisalignment of coil on valve bodyRefit coil correctly
Intermittent cooling / heatingLoose coil connector or oxidationClean and reseat terminals
EEV humming or clickingShorted or unbalanced coil windingReplace coil
Error code (communication or stepper fault)PCB driver failure or coil shortCheck both PCB and EEV assembly

7. Technician Tips

  • Use insulated probes to avoid contact with adjacent pins.

  • When testing installed, always confirm the coil is not powered — induced voltage may damage the multimeter.

  • Do not megger test the coil; use standard resistance testing only.

  • After reassembly, apply dielectric grease to terminals to prevent moisture-induced resistance drift.


8. Summary

  • Standard EEV coils measure 45 – 50 Ω (12 V type) between common and phase wires.

  • High-resistance J-Series coils measure 150 Ω per phase.

  • All coils must read open (O/L) to earth.

  • Visual inspection and correct physical mounting are essential to prevent operational faults.