FGA anywAiR iO RTPU Auto Mode

Smart Temp SMT-770 integration with Rubix Compute 5 and Danfoss PAC control

Overview

This solution describes the configuration and operating logic used to integrate a Smart Temp SMT-770 wall controller with a Fujitsu rooftop packaged unit controlled by a Danfoss controller. A Rubix Compute 5 acts as the intermediary controller and processes the Modbus logic required for automatic heating, cooling, scheduling, after-hours operation and fault indication.

Important: The SMT-770 does not directly control the compressors. It sends operating requests and setpoints to the Rubix Compute 5, which then communicates with the Danfoss controller over the RS485 Modbus network.

1. System components

ComponentPurpose
Rubix Compute 5Processes the control logic and communicates with the SMT-770 and Danfoss controller.
4G router and SIM moduleProvides authorised remote access for monitoring, programming and support.
Smart Temp SMT-770User interface for setpoint adjustment, mode selection, scheduling and after-hours override.
Danfoss PAC controllerControls the rooftop packaged unit and supplies return-air temperature and fault information.
RS485 Modbus networkProvides serial communication between the three control devices.
anywAiR iO RTPU Auto Mode system architecture

System architecture showing the Rubix Compute, SMT-770 and Danfoss controller network.

2. System operation

The user can operate the PAC unit from the SMT-770 wall controller. The controller is normally configured to show the setpoint only. The room temperature displayed by the SMT-770 is not used for system control; the operating temperature is taken from the wired return-air sensor connected to the Danfoss controller.

The SMT-770 provides the following functions:

  • Change the temperature setpoint.
  • Set a seven-day operating schedule.
  • Select Off, Cooling, Heating or Auto mode.
  • Start or cancel an after-hours override.
  • Display an error indication when the Danfoss controller reports a fault.

3. Auto Mode operation

When Auto Mode is selected, the Rubix program compares the Danfoss return-air temperature against the setpoint entered on the SMT-770. The unit starts in ventilation mode and automatically changes between cooling and heating as required.

ConditionSystem response
Return-air temperature is above Setpoint + DeadbandThe unit enters Cooling Mode and remains in cooling until the temperature reaches setpoint.
Return-air temperature is below Setpoint - DeadbandThe unit enters Heating Mode and remains in heating until the temperature reaches setpoint.
Return-air temperature is within the deadbandThe compressors are disabled and the unit operates in Ventilation Mode.

Cooling and heating compressor stages are controlled according to the temperature deviation from setpoint. In heating mode, the reversing valve remains energised until the unit is disabled or another operating mode is selected.

Cooling, heating and after-hours control diagrams

4. After-hours override

  1. Press the Override button on the SMT-770.
  2. The word Override appears on the controller display while the function is active.
  3. The PAC unit runs for the configured after-hours period.
  4. Press the Override button again to cancel the function before the timer expires.

The default after-hours duration is 120 minutes and can be adjusted by a technician.

5. SMT-770 programmable modes

ModeDIP switch settingFunctions
ResidentialSwitch 6 up, Switch 8 upBasic unit control, setpoint adjustment and one schedule.
CommercialSwitch 6 up, Switch 8 downMultiple schedules, after-hours operation and setpoint lockout. This is the default configuration.

6. Default adjustable parameters

ParameterDefaultAdjustment
Mode change delay0.5 minutesConfigured in the Rubix logic.
High setpoint limit30°CUser adjustable within the configured range.
Low setpoint limit18°CUser adjustable within the configured range.
Heating offset0.5°CTechnician adjustable.
Cooling offset0.5°CTechnician adjustable.
After-hours duration120 minutesTechnician adjustable.

7. Modbus communication settings

Device / networkAddress / portBaud rateParity
Serial networkRS485-1 or RS485-2 as configured9600None
Danfoss controller109600None
SMT-77079600None
Rubix CE Modbus serial network setup

Danfoss controller points

PointRegisterTypeUse
Cool_Temp_Setpoint8621Int16Cooling setpoint written from the wall controller.
Heat_Temp_Setpoint8264Int16Heating setpoint written from the wall controller.
System_On_Off8398Int161 = On, 0 = Off.
On-Off Status16388Int16Read-only operating status.
System_heat_cool8400Int161 = Heating, 0 = Cooling.
RT_Temp21804Int16Return-air temperature used for system control.
Danfoss controller Modbus setup and points list

SMT-770 points

PointRegisterFunction
Thermostat Mode20 = Off, 2 = Heat, 3 = Cool, 4 = Auto.
Setpoint17User-entered temperature setpoint.
Fan_Mode3Read-only fan mode value.
Room_Temp322SMT-770 temperature value; not the default system control temperature.
Deadband400.5°C increments: 1 = 0.5°C, 2 = 1.0°C, 3 = 1.5°C.
Display_Mode240 = room and set temperature, 1 = set temperature only.
Heat Limit30Highest permitted heating setpoint.
Cool Limit31Lowest permitted cooling setpoint.
SMT-770 Modbus setup and points list

8. Fault display

The Rubix Compute polls the Danfoss alarm registers over Modbus. When a Danfoss fault is detected, the SMT-770 displays Error on its LCD.

The SMT-770 only provides a general error indication. The technician must check the Danfoss controller to identify the specific fault and refer to the applicable Danfoss service information.

9. Rubix CE configuration

  1. Select the correct serial port in Rubix CE.
  2. Set the serial network to 9600 baud and no parity.
  3. Import the SMT-770 and Danfoss controller backups onto the Modbus network.
  4. Add a Flow Network node and select the correct MQTT topic.
  5. Deploy the node, load the approved Wires program and deploy the completed flow.
  6. Confirm that all required points are online and updating before testing the unit.

10. Functional testing

Complete the following checks after programming or replacing any controller:

  • Confirm setpoint changes on the SMT-770 are reflected on the Danfoss display.
  • Verify the setpoint cannot be reduced below 18°C or increased above 30°C.
  • Test schedule ON and OFF operation and confirm the PAC fan starts and stops.
  • Test Off, Cooling, Heating and Auto modes.
  • In Auto Mode, test operation with the setpoint equal to, below and above the return-air temperature.
  • Test after-hours override start and cancellation.
  • Simulate a Danfoss fault and confirm that Error appears on the SMT-770.
  • Clear the fault and confirm the Error indication is removed.

Summary

The anywAiR iO RTPU Auto Mode configuration provides automatic heating and cooling changeover, seven-day scheduling, after-hours operation, controlled setpoint limits and basic fault indication. Correct Modbus addressing, approved Rubix programming and complete functional testing are essential for reliable operation.