General Assist Technical Reference

UTY-CDRXZC / UTY-CDRXZD Zone Controller

Initial configuration, zone setup and function settings
For 2-wire zone controller systems managing multiple dampers and temperature sensors on a single indoor unit
The UTY-CDRXZC and UTY-CDRXZD controllers manage multiple conditioned zones connected to one indoor unit. Correct zone, sensor and outlet configuration is required to achieve stable temperature control and correct damper operation.
Important: Complete all zone, group and sensor associations before changing the zone function settings. Incorrect configuration may cause inaccurate room temperature control or unexpected damper operation.

1. Preparation

Before configuring the zone controller, confirm the following:

1The indoor unit and zone controller are correctly connected using the approved 2-wire remote-controller circuit.
2The indoor unit's Room Temperature Sensor Switching setting is configured to Both.
3All zone dampers, optional sensors and associated wiring are installed and identified.
4The number of outlets or dampers serving each zone has been confirmed from the duct design.
Sensor requirement: Where the primary or secondary controller sensor is enabled, the indoor unit sensor setting must remain set to Both so the system can use the controller and indoor-unit temperature inputs correctly.

2. Initial zone setup

Zone temperature sensor selection

Assign the required temperature sensor to each zone through:

Zone Setting → Zone Temp. Sensor Selection

Complete the sensor assignment for Zones 1-8. Confirm that every active zone has an appropriate sensor source.

Zone group setting

Up to four zone groups can be created. Allocate Zones 1-8 to the required groups and nominate a priority sensor for each group where applicable.

Zone and sensor naming

SettingPurposeExample
Zone Name SettingIdentifies each conditioned area on the controller.Living, Bedroom 1, Office
Sensor Name SettingIdentifies Sensors 1-11 according to their installed location.Hall Sensor, Master Bedroom

3. Accessing zone function settings

Menu → Maintenance → Zone Function Setting
1Select the required Function Number.
2Select the required Setting Number.
3Press OK to save the setting.
4Record the Function Number and Setting Number on the commissioning sheet.

4. Zone function setting list

FunctionFunction No.Setting No.DefaultApplication
Primary controller sensor70 = Disable
1 = Enable
0Enable when the primary controller temperature sensor is required.
Secondary controller sensor80 = Disable
1 = Enable
0Enable when the secondary controller temperature sensor is required.
Number of outlets11-190-10 outlets1Sets the number of dampers or outlets connected to each zone and the common outlet.
Spring-return damper200 = Not in use
1 = In use
0Select In use when spring-return dampers are installed.
Optional sensor connection31-380 = Not in use
1 = In use
0Enables optional sensors for Zones 1-8.
Temperature correction - cooling41-4800-1600Applies a temperature correction to each zone during cooling.
Temperature correction - heating51-5800-1600Applies a temperature correction to each zone during heating.

Number of outlets - example

ZoneFunction No.Setting No.Configured outlets
Zone 11144
Zone 21222
Zone 31311
Zone 4140None
Common outlet1911
Airflow configuration: The outlet setting must reflect the actual duct and damper arrangement. Do not use the example values unless they match the installed system.

5. Room temperature correction

Cooling functions 41-48 and heating functions 51-58 allow individual zone temperature correction from +4.0 °C to -4.0 °C.

Setting No.CorrectionSetting No.Correction
000.0 °C09-0.5 °C
01+4.0 °C10-1.0 °C
02+3.5 °C11-1.5 °C
03+3.0 °C12-2.0 °C
04+2.5 °C13-2.5 °C
05+2.0 °C14-3.0 °C
06+1.5 °C15-3.5 °C
07+1.0 °C16-4.0 °C
08+0.5 °C
Do not use temperature correction to compensate for poor sensor location. First check for direct sunlight, wall heat transfer, supply-air influence, draughts or poor room-air circulation.

6. Commissioning verification

1Operate each zone individually and confirm the correct damper opens and closes.
2Confirm every active zone displays the expected temperature sensor reading.
3Confirm grouped zones respond correctly to the nominated priority sensor.
4Verify the number-of-outlets settings match the installed damper arrangement.
5Run the system in heating and cooling and confirm stable temperature control.
6Record all Function Numbers, Setting Numbers, zone names and sensor assignments on the commissioning documentation.
Escalation information: When requesting technical assistance, provide the indoor unit model, controller model, zone layout, sensor assignments, outlet counts and a list of all modified function settings.