Overview

These controllers allow management of multiple zones connected to a single indoor unit using a 2-wire remote controller system.
Function settings must be configured based on site layout, number of zones, and sensor usage to ensure accurate temperature control and damper operation.


1. Initial Setup (via Wired Remote Controller)

(Refer to pages 1–5 of the manual)

Before performing any configuration:

  • Confirm the indoor unit’s Room Temperature Sensor Switching is set to “Both” (unit and controller sensors active).

Initial setup includes:

  1. Zone Temperature Sensor Selection

    • Assign sensors to each zone (Zone 1–8).

    • Access via Zone Setting → Zone Temp. Sensor Selection.

  2. Zone Group Setting

    • Define up to 4 groups and allocate zones (1–8) within each.

    • Set Priority Sensors per group for accurate control.

  3. Zone Name Setting

    • Label each zone for easier operation (e.g., “Living”, “Room A”).

  4. Sensor Name Setting

    • Name sensors (Sensor 1–11) to match physical installation points.


2. Zone Function Settings

(Refer to pages 6–9 of the manual)

Access Path

Menu → Maintenance → Zone Function Setting

Setup Procedure

  1. Select Function No.

  2. Select Setting No.

  3. Adjust the parameter, then press OK to confirm.


3. Function Setting List (Summary Table)

(Refer to page 7–8)

FunctionFunction No.Setting No.Factory DefaultDetails / Notes
Primary Controller Sensor70 = Disable / 1 = Enable0Set to “Enable” if using remote sensor; indoor unit must be “Both”.
Secondary Controller Sensor80 = Disable / 1 = Enable0Same condition as primary.
Number of Outlets11–190–101Set per zone according to number of connected dampers.
Spring Return Damper200 = Not in use / 1 = In use0Set to “In use” when spring-return dampers installed.
Optional Sensor Connection31–380 = Not in use / 1 = In use0Up to 8 optional sensors supported.
Temp. Correction (Cooling)41–480–160Adjust based on calibration offset (+4.0°C to -4.0°C).
Temp. Correction (Heating)51–580–160Same range as cooling correction.

4. Number of Outlets (Example Configuration)

(Refer to page 9 diagram)

ZoneFunction No.Setting No. (Outlets)
Zone 1114
Zone 2122
Zone 3131
Zone 4140
Common191

Each setting corresponds to the number of dampers/outlets per zone. The system will proportion airflow and temperature control accordingly.


5. Room Temperature Correction Table

Setting No.Correction Value (°C)
000.0 (standard)
01+4.0
02+3.5
03+3.0
04+2.5
05+2.0
06+1.5
07+1.0
08+0.5
09-0.5
10-1.0
11-1.5
12-2.0
13-2.5
14-3.0
15-3.5
16-4.0

Technician Notes

  • Always complete all zone, group, and sensor associations before setting function numbers.

  • For accurate control, confirm indoor unit and controller sensors both enabled.

  • Document all Function and Setting Numbers on commissioning paperwork for future service reference.


Would you like me to prepare a 1-page technician quick reference sheet (PDF format) summarising the key