Overview

Field reports have identified intermittent cooling performance issues across Fujitsu Multi Systems — specifically AOTG36LBTA4 and AOTG30LBTA4 models — where some indoor heads fail to cool while others experience coil flooding.
This condition can often be misdiagnosed as a refrigerant charge issue or faulty electronic expansion valve (EEV) body, when in fact the underlying cause may be related to control PCB malfunction.


1. Reported Symptoms

  • Some indoor units not cooling at all, others overfeeding refrigerant (flooded coil).

  • System pressure readings inconsistent between heads.

  • Audible difference during EEV initialization — some valves faint or silent.

  • Refrigerant charge and EEV coil resistances test normal.


2. Preliminary Diagnostics

Initial fault-finding steps undertaken:

  1. Refrigerant Reclaimed and full system charge verified — no improvement.

  2. All four EEV bodies replaced — issue persisted.

  3. Piping and wiring confirmed correct per schematic.

  4. EEV electrical testing showed all four coils within factory resistance tolerance and continuity confirmed.

Despite correct mechanical and electrical readings, the issue remained unchanged — indicating a control logic or output fault.


3. Root Cause

Investigation revealed that the indoor EEV control outputs from the outdoor main PCB were inconsistent.
During system start-up:

  • Valve A produced the normal, strong initialization click.

  • Valves B, C, and D emitted faint or irregular sounds.

  • Electrical signal testing confirmed all four EEVs were being energized, but output voltage amplitude was significantly reduced on circuits B–D.

This pointed to a degraded control PCB driver circuit responsible for EEV actuation, causing improper metering and cooling distribution.


4. Corrective Action

  1. Replaced outdoor control PCB (main board).

  2. Recommissioned the system, verifying proper valve sequencing during initialization.

  3. Confirmed all four EEVs produced a consistent, sharp activation sound at power-up.

  4. System achieved uniform cooling performance across all indoor units.


5. Key Diagnostic Indicator

During system initialization, each EEV should emit an identical clicking or buzzing sound as the stepper motors calibrate.

ObservationIndication
All EEVs sound consistentNormal operation
One or more faint / silentPCB signal fault or driver output issue
Random valve noise variationPossible intermittent PCB or harness issue

6. Field Advisory

When fault-finding multi-head systems:

  • Always listen to all EEVs during start-up before reclaiming charge or replacing components.

  • Uneven valve sounds indicate a control PCB output issue, not necessarily an EEV fault.

  • Save time and resources by performing this auditory test early in the diagnostic process.


7. Recommended Procedure Summary

Check PointTest / ObservationExpected Result
Refrigerant chargeWeigh in full chargeVerified
EEV coil resistanceMeasure with multimeterWithin spec (typically ~500Ω)
Valve sound testPower ON, listen for equal clicksAll consistent
Outdoor PCB outputCheck for stable DC voltage to all EEVsUniform across channels
System operationCooling confirmed across all headsStable suction pressure, even coil temp

Conclusion

Fault traced to outdoor main control PCB, where uneven EEV drive signal prevented correct refrigerant metering.
Replacing the PCB resolved the issue completely.
This serves as a valuable field diagnostic note — always verify EEV initialization sounds before proceeding with component replacement or refrigerant work.

AOTG30LBTA4 issues. 

Some heads weren’t cooling at all and some were flooding the coil. Had suspected either faulty ev body or gas charge. Reclaimed full charge so ended up replacing all 4 body’s to only have the same issue still. 

After checking out wiring/piping we noticed that not all ev’s sounded the same when initializing. Valve A sounded normal and B, C, D sounded faint. All 4 evs tested out correctly so we ended up replacing the control pcb which fixed our issue in the end. Something to keep in mind when fault finding these system is to make sure all valves make the same sound when initializing. It could save you a lot of trouble.