Overview
Three-phase outdoor units operate differently from single-phase systems due to their PFC (Power Factor Correction) PCB and Active Converter Technology Power Module (ACTPM).
The PFC PCB is a critical component that manages current draw balance and power efficiency.
When faulty, it commonly results in circuit breaker tripping immediately upon energizing the system.
This procedure applies to:
Models: AOTDLATT, AOTDLBTT, AOTGLATT
PCB type: PFC (Power Factor Correction Board)
1. Common Symptoms of PFC PCB Failure
Main power breaker trips when unit is energized.
No power indication or immediate shutdown after power-up.
Possible burnt smell or visible board damage around high-current components.
⚠️ If the system trips on power-up without compressor engagement, the PFC board is the most likely cause.
2. Required Tools
Digital multimeter with diode test function.
Insulated probes suitable for PCB testing.
Correct wiring diagram or service schematic for reference.
3. Test Setup and Safety
Isolate Power: Disconnect the air conditioner completely from mains supply.
Access PCB: Open the outdoor unit and locate the PFC board (refer to diagram, page 1 of the guide).
Identify Test Points:
TM504 (Orange) → Positive terminal
TM505 (Purple) → Negative terminal
TM500, TM501, TM502 → Intermediate test points used for circuit verification
Refer to page 1 image of the provided guide showing test point color coding and probe placements
PFC testing
.
4. Testing Procedure
Using the multimeter in diode mode, perform the following tests between the listed terminal pairs:
| Red Lead (+) | Black Lead (–) | Expected Reading (V) | Result Interpretation |
|---|---|---|---|
| TM504 | TM500 | OL | Normal |
| TM504 | TM501 | OL | Normal |
| TM504 | TM502 | OL | Normal |
| TM505 | TM500 | 0.4 | Normal |
| TM505 | TM501 | 0.4 | Normal |
| TM505 | TM502 | 0.4 | Normal |
| TM501 | TM504 | 0.4 | Normal |
| TM502 | TM504 | 0.4 | Normal |
| TM505 | TM504 | OL | Normal |
| TM502 | TM505 | OL | Normal |
Acceptable Range: Readings between 0.3 V and 0.5 V on diode scale are considered healthy junctions.
Failure Condition: If any test returns 0.0 V, the PCB is shorted and must be replaced.
5. Test Interpretation
All readings normal (0.4 V / OL): PCB is functional.
0.0 V reading (short): Internal diode or transistor failure – replace PFC PCB.
Open circuit on all tests: Check for disconnected harness or blown board fuse before replacing PCB.
6. Service Notes
Testing the PFC PCB is similar to testing the IPM (Inverter Power Module), but the presence of choke coils introduces added resistance—expect slight measurement variation.
Always perform testing with complete discharge of the board’s capacitors to avoid false readings.
If the PFC is faulty, replace as a complete assembly; component-level repair is not recommended.
7. Technician Advisory
PFC failures are most often caused by:
Power surges or unbalanced supply voltage.
Moisture ingress or carbon tracking on PCB surface.
Compressor or IPM faults backfeeding current through the PFC.
After replacement, ensure correct earthing and surge protection to prevent recurrence.