General Assist Technical Reference

Testing Three-Phase Outdoor Units - PFC PCB

Diode-test procedure for Power Factor Correction boards
Applicable to AOTD**LATT, AOTD**LBTT and AOTG**LATT outdoor units
Three-phase outdoor units use a Power Factor Correction (PFC) PCB as part of the active-converter circuit. A common symptom of PFC PCB failure is the main circuit breaker tripping as soon as the system is energised.
Electrical safety: This procedure must only be completed by qualified service personnel. Isolate the unit from the mains supply, prove that power is disconnected and allow the DC capacitors to discharge before touching or testing the PCB.

1. Scope

ItemDetails
Applicable modelsAOTD**LATT, AOTD**LBTT and AOTG**LATT
PCB under testPFC - Power Factor Correction PCB
Required meter functionDiode-test mode

2. Common symptoms

  • Main circuit breaker trips when the outdoor unit is energised.
  • The unit shuts down immediately after power is applied.
  • There may be visible heat damage, carbon tracking or a burnt smell around high-current components.
A breaker that trips immediately on power-up, before compressor operation begins, is a strong indication that the PFC PCB or another component in the DC power circuit is shorted. Testing is required before parts are replaced.

3. Test points

TerminalIdentificationPurpose
TM504OrangePositive connection
TM505PurpleNegative connection
TM500 / TM501 / TM502Intermediate terminalsUsed to verify the internal diode paths
PFC PCB terminal locations and colour-coded test points
PFC PCB terminal locations. TM504 is identified in orange and TM505 in purple.

4. Testing procedure

1Isolate power. Disconnect the unit from the mains supply, prove the circuit is de-energised and wait for the DC bus capacitors to discharge.
2Access the PFC PCB. Locate TM500, TM501, TM502, TM504 and TM505.
3Select diode mode. Confirm the multimeter and test leads are functioning correctly before testing the PCB.
4Complete every test below. Probe polarity is important. Record the result for each terminal pair.
Red lead (+)Black lead (-)Expected reading
TM504TM500OL
TM504TM501OL
TM504TM502OL
TM505TM500Approx. 0.4 V
TM505TM501Approx. 0.4 V
TM505TM502Approx. 0.4 V
TM501TM504Approx. 0.4 V
TM502TM504Approx. 0.4 V
TM500TM504Approx. 0.4 V
TM501TM505OL
TM502TM505OL
TM500TM505OL
Example PFC PCB diode test and original reference table
Example meter connection and original reference readings.

5. Interpreting the results

ResultInterpretationAction
Expected OL and approximately 0.4 V readingsThe tested diode paths are operating normally.Continue diagnosis if the breaker still trips.
0.0 V on any testThe circuit is shorted and the PFC PCB has failed the test.Replace the PFC PCB assembly.
OL on every testThe board may be disconnected, a fuse may be open or the probe contact may be poor.Check harnesses, fuses, meter operation and terminal contact before condemning the PCB.
Reading tolerance: The reference document shows approximately 0.4 V. Small variations are normal because the PFC circuit includes choke coils. A reading around 0.3-0.5 V is generally consistent with a healthy semiconductor junction, provided the reverse-polarity result is OL.

6. Final service checks

  • Inspect the board for moisture ingress, carbon tracking, cracked components and heat damage.
  • Check the three-phase supply for phase imbalance, under-voltage and over-voltage.
  • Confirm the compressor and inverter/IPM circuits are not shorted before energising a replacement board.
  • Confirm all earth connections and protective devices are secure before restoring power.