General Assist Technical Reference
VRF Outdoor Unit DIP Switch Settings
SET1–SET5 and REF AD reference by outdoor unit model
Reference covering S-Series, R-Series, VR-II, V-III and VR-IV outdoor units
The outdoor PCB DIP switch configuration varies according to model, compressor capacity and product generation. Always confirm the exact outdoor unit model before changing SET1–SET5.
How to read the tables: Each SET column shows DIP switches 1 / 2 / 3 / 4 in that order. For example, OFF / ON / OFF / OFF means switch 1 OFF, switch 2 ON, switch 3 OFF and switch 4 OFF.
1. S-Series / R-Series Outdoor Units
| Models | SET1 1 / 2 / 3 / 4 | SET2 | SET3 | SET4 | SET5 | Reference |
|---|---|---|---|---|---|---|
| AJYA72GALH AJHA72GALH AJTA72GALH AJQ224LALBH | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 8 HP 65 cc compressor S-Series |
| AJYA90GALH AJHA90GALH AJTA90GALH AJQ280LALBH | OFF / OFF / ON / OFF | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 10 HP 65 cc compressor S-Series |
| AJY108GALH AJH108GALH AJQ335GALH AJQ335LALBH AJY108LALCH AJH108LALCH | OFF / ON / OFF / OFF | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 12 HP 65 cc compressor S-Series |
| AJT108GALH | ON / OFF / ON / OFF | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 12 HP 79 cc compressor S-Series |
| AJY126GALH / AJH126GALH / AJT126GALH AJQ400GALAH / AJQ400LALBH AJY126LALBH / AJH126LALBH AJZ126LALBH / AJZ126LALCH AJY126LNLBH / AJH126LNLBH AJG126LNLBH / AJG126LNLCH and associated 126-series models shown in the source table | OFF / ON / ON / OFF | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 14 HP 79 cc compressor R-Series |
| AJY144GALH AJH144GALH AJQ450GALAH AJQ450LALBH AJT144GBLH | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 16 HP 79 cc compressor R-Series |
2. Regional Outdoor Units
| Model | SET1 | SET2 | SET3 | SET4 | SET5 | Application |
|---|---|---|---|---|---|---|
| AJU072GALAH | ON / ON / OFF / OFF | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 8 HP / 65 cc / S-Series / North America |
| AJU096GALAH | ON / ON / ON / OFF | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 10 HP / 65 cc / S-Series / North America |
| AJU120GALAH | OFF / OFF / OFF / ON | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 12.6 HP / 79 cc / R-Series / North America |
| AJQ280GALAH | OFF / OFF / ON / ON | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 10 HP / 65 cc / S-Series / China |
3. VR-II – 460 V
| Model | SET1 | SET2 | SET3 | SET4 | SET5 | Capacity |
|---|---|---|---|---|---|---|
| AJR072GALAH | OFF / ON / OFF / ON | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 8 HP / 65 cc |
| AJR096GALAH | OFF / ON / ON / ON | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 10 HP / 65 cc |
| AJR120GALAH | ON / OFF / OFF / ON | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 12.6 HP / 79 cc |
| AJR072LALBH | OFF / OFF / OFF / ON | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 8 HP / 65 cc |
| AJR096LALBH | OFF / OFF / ON / ON | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 10 HP / 65 cc |
| AJR120LALBH | OFF / ON / OFF / ON | OFF / OFF / OFF / OFF | OFF / OFF / OFF / OFF | ON / OFF / OFF / OFF | OFF / OFF / OFF / OFF | 12.6 HP / 79 cc |
4. V-III Outdoor Units
The V-III models shown in the source use SET2, SET3 and SET5 all OFF, with SET4 = ON / OFF / OFF / OFF. SET1 identifies the capacity.
| Capacity | SET1 | Compressor | Typical Model Family |
|---|---|---|---|
| 8 HP | ON / OFF / ON / OFF | 65 cc S-Series | AJY072 / AJH072 / AJZ072 / AJG072 series and associated variants |
| 10 HP | ON / ON / OFF / OFF | 65 cc S-Series | AJY090 / AJH090 / AJZ090 / AJG090 series and associated variants |
| 12 HP | OFF / ON / ON / ON | 79 cc | AJY108 / AJH108 / AJZ108 / AJG108 series and associated variants |
| 16 HP | ON / ON / ON / OFF | 79 cc R-Series | AJY144 / AJH144 / AJZ144 / AJG144 series and associated variants |
| 18 HP | ON / OFF / OFF / ON | 79 cc R-Series | AJY162 / AJH162 / AJZ162 / AJG162 series and associated variants |
5. VR-IV Outdoor Units
On the VR-IV models shown, SET2 switch 4 is ON. SET3 and SET5 remain OFF, while SET4 is ON / OFF / OFF / OFF.
| Models | Capacity | SET1 | SET2 |
|---|---|---|---|
| AJY072GALBH AJH072GALBH AJT072GALBH | 8 HP | OFF / OFF / OFF / OFF | OFF / OFF / OFF / ON |
| AJY090GALBH AJH090GALBH AJT090GALCH | 10 HP | OFF / OFF / ON / OFF | OFF / OFF / OFF / ON |
| AJY108GALBH AJH108GALBH AJT108GALCH | 12 HP | OFF / ON / OFF / OFF | OFF / OFF / OFF / ON |
| AJY126GALBH AJH126GALBH AJT126GALCH | 14 HP | OFF / ON / ON / OFF | OFF / OFF / OFF / ON |
| AJY144GALBH AJH144GALBH AJT144GALCH | 16 HP | ON / OFF / OFF / OFF | OFF / OFF / OFF / ON |
6. REF AD Setting
The source tables also show two rotary REF AD switches:
- ×10 – tens digit
- ×1 – units digit
These rotary switches are used for refrigerant-system addressing. Set the address according to the installation and system configuration requirements rather than using the DIP capacity setting alone.
Important: Do not change outdoor-unit DIP switches purely on the basis of capacity. Confirm the full model number and series. Similar-capacity outdoor units from different generations use different SET1 and SET2 combinations.
Service procedure: Isolate power before altering PCB DIP switches. Changes should be made by appropriately qualified service personnel and checked against the applicable service or installation documentation before power is restored.