AOTG30LBTA4 Service Manual
Outdoor unit specifications, refrigerant charge and multi-split piping limits
AOTG30LBTA4 four-room multi inverter outdoor unit and compatible indoor-unit combinations
This article provides the principal service specifications for the AOTG30LBTA4 outdoor unit. It is intended as a quick technical reference and does not replace the applicable service manual, installation manual or approved combination table.
Important: Before charging, commissioning or replacing components, confirm the complete indoor-unit combination, total connected capacity, pipe lengths, unit serial number and the latest model-specific documentation.
1. Quick answer
| Question | Answer |
|---|---|
| Cooling capacity | 8.0 kW |
| Heating capacity | 9.6 kW |
| EER | 3.60 kW/kW |
| COP | 4.00 kW/kW |
| Power supply | Single phase, 240 V, 50 Hz |
| Refrigerant | R410A |
| Outdoor dimensions | 830 × 900 × 330 mm (H × W × D) |
| Maximum total pipe length | 70 m |
2. Model mapping
| Outdoor unit | AOTG30LBTA4 |
| System type | Four-room multi inverter |
| Indoor units | Multiple compatible indoor-unit models, subject to the approved combination table and connected-capacity limits |
Combination check: Do not approve an indoor-unit combination from model capacity alone. Confirm the exact combination against the applicable multi-split combination table.
3. Electrical and performance specifications
| Item | Cooling | Heating |
|---|---|---|
| Rated capacity | 8.0 kW | 9.6 kW |
| Power consumption | 2.22 kW | 2.40 kW |
| Efficiency | EER 3.60 kW/kW | COP 4.00 kW/kW |
| Rated operating current | 9.3 A | 10.1 A |
Power supply
- Single phase
- 240 V
- 50 Hz
4. Compressor and refrigerant
Compressor
| Type | Hermetic inverter, twin rotary |
| Motor | 4-pole, 3-phase DC motor |
| Model | TNB220FPBMT |
| Weight | 14.3 kg, including oil |
Refrigerant charge
| Total piping length | Full refrigerant charge |
|---|---|
| 50 m | 2,800 g |
| 60 m | 3,050 g |
| 70 m | 3,300 g |
- Refrigerant: R410A
- Standard factory charge: 2,800 g
- Additional charge rate: 25 g per metre, where required by the service procedure
Charging control: Confirm whether the quoted total piping length is within the factory-charged allowance before adding refrigerant. Use the latest service procedure and calculate from the actual installed total pipe length.
5. Piping limits
| Requirement | Limit |
|---|---|
| Maximum total pipe length | 70 m |
| Maximum pipe length per indoor unit | 25 m |
| Minimum pipe length per indoor unit | 5 m |
| Minimum total pipe length | 20 m |
| Maximum elevation between indoor units | 10 m |
| Maximum elevation between indoor and outdoor units | 15 m |
6. Outdoor fan, airflow and sound
| Fan motor | MFE-60TVT |
| Cooling fan speed | 820 rpm |
| Heating fan speed | 780 rpm |
| Outdoor airflow | 3,300 m³/h |
| Sound pressure level | 50 dB cooling / 51 dB heating |
7. Dimensions and weight
| Dimensions | 830 × 900 × 330 mm (H × W × D) |
| Net weight | 68 kg |
| Shipping weight | 75 kg |
8. Service and identification notes
- Confirm the outdoor model from the rating label before applying these specifications.
- Record the complete serial number when checking production changes, replacement PCBs or superseded components.
- Where a service bulletin identifies a serial-number change, compare both the carton label and the unit rating label.
- PCB identification must be taken from the printed board number and revision marking on the actual component.
- Do not select a replacement PCB from appearance alone; confirm the model, serial range, board number and current spare-parts listing.
- After PCB replacement, copy all applicable switch settings and complete the required commissioning checks.
Support response: When asked whether the system supports a particular pipe length, confirm both the 70 m total-system limit and the 25 m limit for each individual indoor-unit branch.
9. Document references
Use the current controlled versions of the following documents:
- AOTG30LBTA4 service manual
- AOTG30LBTA4 installation manual
- Approved multi-split indoor-unit combination table
- Current spare-parts listing and applicable service bulletins