General Air Conditioning | Technical Support Reference

Ducted Fan Operation on Heat

Hidden function setting 33 = 04 to stop the indoor fan after the heating set point is reached
Overview: During heating operation, the indoor fan normally continues at a super-low or pulsed speed after the room reaches the set temperature. This is standard operation intended to maintain even room temperature and minimise sudden temperature swings.
Customer comfort concern: Some occupants may experience a cool draft once the heating demand has been satisfied. On compatible models, Function 33 = 04 can be used to stop the indoor fan completely at set point.

1. Function purpose

This setting changes the indoor fan behaviour in heating mode after the selected room temperature has been reached.

SettingIndoor fan behaviour at heating set point
Default factory settingThe indoor fan continues to operate in super-low or pulse mode.
Function 33 = 04The indoor fan stops completely once the heating set point is reached.
Result: Stopping the fan prevents unheated air from being circulated through the ductwork after the system has satisfied the temperature demand, helping reduce cool-draft complaints.

2. How to enable the setting

Hidden function adjustment - wired wall controller
1Stop indoor unit operation.
2Enter the Function Setting Mode on the wired wall controller.
3Navigate to Function No. 33.
4Change the setting value to 04.
5Power down the indoor unit.
6Leave the power off for a minimum of 5 minutes, then restore power and test operation.
Important: The power cycle is required to ensure the revised function setting is stored and applied correctly.
Operating scope: This adjustment only changes indoor fan behaviour in heating mode. Cooling operation remains unchanged.

3. Model compatibility

Function 33 = 04 is only available on supported indoor units. Confirm the full indoor model and production date before applying the setting.

Model seriesFunction 33 = 04Notes
LHTC✔ AvailableSupported on units produced after January 2015.
LMLC✔ AvailableSupported on units produced after January 2015.
LATU✖ Not availableUnsupported hardware.
LBTU✖ Not availableUnsupported hardware.
LHTDP✔ AvailableSupported on all production runs.
ARTH - all H models✔ AvailableSupported across the H-series ducted range.
Compatibility check: Do not assume the setting is available based on controller type alone. Confirm the indoor unit model and, where relevant, its production date.

4. Summary

1The default heating behaviour is super-low or pulsed indoor fan operation after the set point is reached.
2Setting Function 33 = 04 stops the indoor fan completely at set point to help reduce cool-draft complaints.
3The indoor unit must be powered down for at least 5 minutes after changing the setting.
4The function is supported on compatible LHTC, LMLC, LHTDP and ARTH H-series models, subject to the production requirements shown above.
Technical reminder: After applying the setting, operate the system in heating mode and confirm that the fan stops after the room reaches set point and restarts correctly when heating demand returns.