GENERAL AIRSTAGE Technical Reference

ASTG09KMTC / ASTG12KMTC Service Reference

Specifications, refrigerant circuit, error codes, PCB data and optional controls
Indoor units: ASTG09KMTC / ASTG12KMTC   |   Outdoor units: AOTG09KMTC / AOTG12KMTC
This reference consolidates key service information for the KMTC wall-mounted R32 inverter systems. Use the model-specific service and installation documentation where a complete commissioning, repair or diagnostic procedure is required.
Qualified service personnel only: Isolate mains power before accessing electrical components. Refrigerant work must be carried out using procedures and equipment suitable for R32 refrigerant.

1. Model applicability

System sizeIndoor unitOutdoor unit
2.5 kW classASTG09KMTCAOTG09KMTC
3.5 kW classASTG12KMTCAOTG12KMTC

2. Key specifications

ItemASTG09KMTC / AOTG09KMTCASTG12KMTC / AOTG12KMTC
Power supply240 V ~ 50 Hz, outdoor unit supply
Available voltage range198-264 V
Cooling capacity2.5 kW rated
0.9-3.6 kW range
3.5 kW rated
0.9-4.1 kW range
Heating capacity3.2 kW rated
0.9-5.3 kW range
4.1 kW rated
0.9-6.1 kW range
Rated input - cooling0.53 kW0.89 kW
Rated input - heating0.66 kW0.79 kW
Maximum operating currentCooling 6.0 A
Heating 7.5 A
Cooling 6.5 A
Heating 9.0 A
Indoor dimensions270 x 834 x 222 mm (H x W x D)
Outdoor dimensions542 x 799 x 290 mm (H x W x D)
Indoor net weight10 kg
Outdoor net weight32 kg
Outdoor operating range: Cooling -10°C to 46°C; Heating -15°C to 24°C. Protective functions may operate when equipment is used outside the specified range.

3. Refrigerant and piping

RefrigerantR32
Factory charge850 g
Pre-charge pipe length15 m
Maximum pipe length20 m
Maximum height difference15 m
Liquid pipe6.35 mm (1/4 in) flare
Gas pipe9.52 mm (3/8 in) flare
Refrigerant oilPOE (RB68A), 340 cm3

The refrigerant circuit contains the compressor, 4-way valve, outdoor heat exchanger, expansion valve, strainers, 2-way and 3-way service valves, indoor heat exchanger and associated thermistors.

Thermistors shown in the circuit

  • ThD - Discharge temperature
  • ThO - Outdoor temperature
  • ThHO - Outdoor heat exchanger outlet temperature
  • ThHM - Indoor heat exchanger middle temperature
  • ThR - Room temperature
  • ThPI - Pipe temperature

4. PCB and electrical service data

Indoor unit

ItemASTG09KMTCASTG12KMTC
Control unitEZ-01836HSEEZ-01837HSE
Main PCB identificationK18RA-1806HSE-C1K18RA-1807HSE-C1

Indoor thermistor reference - CN1

Sensor0°C20°C30°C
Pipe thermistor176.0 kOhm62.9 kOhm39.6 kOhm
Room thermistor33.6 kOhm12.5 kOhm8.0 kOhm

Outdoor unit

ItemAOTG09KMTCAOTG12KMTC
Inverter assemblyEZ-018FHUEEZ-0187HUE
Main PCB identificationK17LG-1803HUE-C1K17LG-1800HUE-C1
Compressor winding resistance1.975 Ohm at 25°C (U-V / V-W / U-W)
4-way valve coil2,780 Ohm at 20°C
Expansion valve coil46.0 Ohm at 20°C

Outdoor thermistor reference

Sensor0°C20°C30°C
Discharge thermistor168.6 kOhm62.6 kOhm40.0 kOhm
Outdoor temperature thermistor35.2 kOhm12.6 kOhm8.0 kOhm
Pipe thermistor16.1 kOhm6.0 kOhm3.8 kOhm

5. Error indication and common codes

When a wireless controller is used, the indoor indicator lamps display the fault as a flashing pattern. With a compatible wired controller, the error code is shown directly on the controller display. Error indication is displayed during operation.

Indoor display: OPERATION lamp = green, TIMER lamp = orange, ECONOMY lamp = green. The number in brackets in the service table represents the number of flashes.
CodeDescription
11Serial communication error
12Wired remote controller / server room control communication error
15Check run unfinished / automatic airflow adjustment error
18External communication error
23Combination error
32Indoor unit PCB model information error
35Manual auto switch error
41Room temperature sensor error
42Indoor heat exchanger middle temperature sensor error
44Human sensor error
51Indoor unit fan motor error
62Outdoor unit main PCB model information / communication error
63Inverter error
64Active filter / PFC circuit error
65Trip terminal L error
71Discharge temperature sensor error
73Outdoor heat exchanger liquid temperature sensor error
74Outdoor temperature sensor error
84Current sensor error
94Trip detection
95Compressor rotor position detection error
97Outdoor unit fan motor 1 error
994-way valve error
A1Discharge temperature error
Important: An error code identifies the detected condition; it does not automatically identify the failed part. Confirm wiring, connectors, sensor values and supply conditions before replacing components.

6. Controllers and optional interfaces

AccessoryModelNotes
Wired remote controllerUTY-RNRYZ*Non-polar 2-wire. Communication kit required.
Wired remote controllerUTY-RLRYNon-polar 2-wire. Communication kit required.
Simple remote controllerUTY-RSRYNon-polar 2-wire. Communication kit required.
Simple remote controllerUTY-RHRYNon-polar 2-wire. Communication kit required.
Communication kitUTY-TWRXZ2Required to connect a non-polar 2-core wired controller.
External input/output PCBUTY-XCSXZ2Provides connection to external devices.
External connect kitUTY-XWZXZ5Communication kit also required.
Wireless LAN adapterUTY-TFSXF3Provides mobile-device control.
Controller note: The service manual states that group control using the wired remote controller is prohibited for this product.

7. Standard accessories

The indoor unit is supplied with the operating manual, installation manual, wall hook bracket, wireless remote controller, remote controller holder, two batteries, five large tapping screws, two small tapping screws, cloth tape, two filter holders and one air cleaning filter set. The outdoor unit accessory set includes an installation manual, drain pipe and cable tie.

Technical information should be confirmed against the latest GENERAL AIRSTAGE service and installation documentation before service work is performed.