UTB-TUD Wired Remote Controller
1. Quick answer
| Controller model | UTB-TUD |
| Controller type | Wired remote controller |
| Cable | 3-wire, red / white / black, supplied length 10 m |
| Power | 12 V supplied from the indoor unit |
| Controller dimensions | 120 × 120 × 17 mm |
| Main features | ON/OFF timer, weekly timer, temperature setback, economy mode, sensor selection, child lock and self-diagnosis |
| Temperature range | Auto / Cool / Dry: 18–30°C; Heat: 16–30°C |
2. Australian wall-mounted compatibility
The technical bulletin identifies the following Australian wall-mounted models as compatible with the UTB-TUD.
| Chassis Type A | Chassis Type B |
|---|---|
| ASTA07JEC ASTA09JEC ASTA12JEC | ASTA18JCC ASTA24JCC ASTA30JCC ASTA34JCC ASTA24LCC ASTA30LCC ASTB24LDC ASTB30LDC |
- Group control and dual remote controller operation are not supported.
- On Chassis Type A units, the wireless remote cannot operate Coil Dry, 10°C Heat, Program Timer or Sleep Timer once the wired controller is installed.
- On Chassis Type B units, the wireless remote controller cannot be used after the wired controller is connected.
Note: Compatibility is model-specific. For indoor units not listed above, confirm suitability in the relevant indoor-unit installation manual before connecting the controller.
3. Basic operation
| Task | Procedure |
|---|---|
| Start or stop | Press START/STOP. |
| Select mode | Press MODE to select Auto, Cool, Dry, Heat or Fan. Available modes depend on the indoor unit. |
| Set temperature | Use the SET TEMP. up and down buttons. |
| Set fan speed | Press FAN to select Auto, High, Medium, Low or Quiet. Dry mode automatically uses Auto fan. |
| Economy operation | Press ECONOMY to turn economy mode on or off. On compatible single systems, maximum output is approximately 70% of normal operation. |
| Filter indication reset | After cleaning the filter, press and hold MAINTENANCE / FILTER RESET for at least 2 seconds. |
Set the current day and time
- Press and hold TIMER MODE / CLOCK ADJUST for at least 2 seconds.
- Press DAY to select the current day.
- Use the SET TIME left and right buttons to set the time.
- Press SET BACK to switch between 12-hour and 24-hour display.
- Press TIMER MODE / CLOCK ADJUST again to finish.
Child lock
Press and hold DAY and TIMER SET together for at least 2 seconds. Repeat the same action to unlock the controller. “CL” appears when a locked button is pressed.
Room-temperature sensor selection
Where the function has been enabled by an installer, press and hold ECONOMY / THERMO SENSOR for more than 2 seconds to select either the indoor-unit sensor or the controller sensor. When the thermo-sensor symbol is displayed, temperature is being detected at the wired controller.
4. Timer functions
ON or OFF timer
- Press TIMER MODE until the ON timer or OFF timer is displayed.
- Use SET TIME to select 1 to 24 hours.
- The timer starts automatically after the time is entered.
- Press TIMER DELETE to cancel.
Weekly timer
- Press TIMER MODE and select Weekly Timer.
- Press and hold TIMER SET for at least 2 seconds.
- Select the required day using DAY, then press TIMER SET.
- Use SET TIME to program ON-1, OFF-1, ON-2 and OFF-2 as required.
- Press TIMER SET to confirm each setting.
- Press and hold TIMER SET for at least 2 seconds to finish.
- Up to two ON and two OFF events can be programmed per day.
- Times are set in 30-minute increments.
- Both an ON and OFF time must be entered.
- Press TIMER DELETE while editing to remove the selected operating time.
Day Off
While editing the weekly timer, select the required day and press and hold DAY / DAY OFF for at least 2 seconds. The Day Off setting applies once and is automatically cancelled after the selected day passes.
Temperature setback timer
The setback timer changes the set temperature during programmed periods. It does not start or stop the air conditioner.
- Press SET BACK.
- Press and hold TIMER SET for at least 2 seconds.
- Select the day and operating time using the same method as the weekly timer.
- Use SET TEMP. to select the setback temperature.
- Press and hold TIMER SET for at least 2 seconds to finish.
5. Installation and wiring
Controller location
- Install where the room temperature is representative of the occupied space.
- Do not install in direct sunlight, in discharge airflow or close to another heat source.
- Keep controller wiring separate from mains, transmission and interconnection wiring.
- Use shielded cable where electromagnetic interference may be present.
Standard 3-wire connection
| Terminal | Wire colour |
|---|---|
| 1 | Red |
| 2 | White |
| 3 | Black |
DIP switch settings
| Switch | Purpose | Setting |
|---|---|---|
| DIP 1 No. 1 | Model-specific wall-mounted configuration | For Chassis Type B wall-mounted applications, set ON as shown in the technical bulletin. Otherwise follow the indoor-unit instructions. |
| DIP 1 No. 2 | Dual-controller master/slave selection | Master OFF; slave ON. Not applicable to the listed wall-mounted applications. |
| DIP 1 No. 3 | Filter reset operation and display | Set to suit the applicable indoor unit. |
| DIP 1 No. 6 | Memory backup | ON when the controller batteries are used for memory backup. |
Do not change unused switches. Incorrect DIP switch settings can cause communication faults or unavailable functions.
6. Test run and function settings
Test run
- Stop the air conditioner if it is operating.
- Press and hold MODE and FAN together for more than 2 seconds.
- The operation lamp illuminates and the test-run symbol appears.
- The test run operates for up to 60 minutes.
- Press START/STOP to finish early.
Enter function-setting mode
- Press both SET TEMP. buttons and FAN together for more than 5 seconds.
- Press SET BACK to select the indoor-unit number.
- Use SET TIME to select the function number.
- Use SET TEMP. to select the setting value.
- Press and hold TIMER SET until the value stops flashing.
- After completing all settings, exit function-setting mode and cycle power to the system.
| Function | Number | Settings |
|---|---|---|
| Cooling room-temperature correction | 30 | 00 Standard; 01 Lower control |
| Heating room-temperature correction | 31 | 00 Standard; 01 Lower; 02 Slightly warmer; 03 Warmer |
| Auto restart | 40 | 00 Yes; 01 No |
| Indoor room-temperature sensor switching | 42 | 00 No; 01 Yes |
7. Troubleshooting and error display
| Symptom or display | Meaning / action |
|---|---|
| Controller displays “EE” | A system fault is present. Record the unit number and error code and refer to authorised service personnel. |
| C0 / 1C | Indoor unit to remote-controller communication error. Check wiring polarity, terminals, connectors and DIP settings. |
| C0 / 1d | Incompatible indoor unit connected. |
| Thermo-sensor symbol flashes | Sensor selection may be locked, or the room-temperature sensor may require inspection. |
| Airflow stops during heating | This may be normal during automatic defrost. Heating can pause for approximately 4 to 15 minutes. |
| Unit enters standby on a multi system | Indoor units connected to the same outdoor unit cannot operate in conflicting modes such as heating and cooling. |
| Timer settings are lost after a power failure | Check memory-backup batteries and confirm DIP 1 No. 6 is set correctly. |
8. Reference details
- Operating manual part number: 9373329060-02
- Installation manual part number: 9373328063-04
- Technical bulletin: TB_RC001E/02, dated 16 July 2009
- Controller weight: approximately 160 g