General Assist Technical Reference
ARTG30 / ARTG36 / ARTG45LHTA
Matched with AOTG30 / AOTG36 / AOTG45LBTC outdoor units
Ducted split system specifications, refrigerant data, fault codes, wiring reference and service parts
Quick reference: These are R410A, single-phase 240 V ducted systems. Correct matched combinations are ARTG30LHTA / AOTG30LBTC, ARTG36LHTA / AOTG36LBTC and ARTG45LHTA / AOTG45LBTC.
Service safety: This article is intended for qualified air-conditioning technicians. Isolate power before servicing. Inverter outdoor units contain high DC voltage after supply isolation; confirm capacitors are discharged before touching electrical components.
1. Model combinations
| Indoor unit | Outdoor unit | Cooling | Heating |
|---|---|---|---|
| ARTG30LHTA | AOTG30LBTC | 8.5 kW | 10.0 kW |
| ARTG36LHTA | AOTG36LBTC | 10.0 kW | 12.5 kW |
| ARTG45LHTA | AOTG45LBTC | 11.5 kW | 14.0 kW |
2. System specifications
| Specification | 30 | 36 | 45 |
|---|---|---|---|
| Power supply | 240 V, 50 Hz, single phase | ||
| Cooling capacity | 8.5 kW | 10.0 kW | 11.5 kW |
| Heating capacity | 10.0 kW | 12.5 kW | 14.0 kW |
| Cooling input | 2.61 kW | 3.08 kW | 3.70 kW |
| Heating input | 2.70 kW | 3.42 kW | 3.84 kW |
| Rated current - cooling | 11.0 A | 13.0 A | 15.5 A |
| Rated current - heating | 11.3 A | 14.4 A | 16.1 A |
| Maximum operating current | 17.1 A | 21.1 A | 23.5 A |
| EER | 3.26 | 3.25 | 3.11 |
| COP | 3.70 | 3.65 | 3.65 |
| Indoor airflow H / M / L | 2500 / 2100 / 1700 m³/h | 2500 / 2100 / 1700 m³/h | 3250 / 2750 / 2200 m³/h |
| Indoor dimensions H x W x D | 400 x 1050 x 500 mm | 400 x 1050 x 500 mm | 425 x 1250 x 490 mm |
| Outdoor dimensions H x W x D | 830 x 900 x 330 mm | 914 x 970 x 370 mm | 914 x 970 x 370 mm |
| Indoor net weight | 39 kg | 39 kg | 54 kg |
| Outdoor net weight | 61 kg | 75 kg | 75 kg |
3. Refrigerant and piping
Refrigerant: R410A. Maximum pipe height is 30 m. Liquid line is 9.52 mm (3/8 in) and gas line is 15.88 mm (5/8 in) for all three systems.
| Pipe length | ARTG30 / AOTG30 | ARTG36 / AOTG36 | ARTG45 / AOTG45 |
|---|---|---|---|
| 20 m | 2,100 g | 2,900 g | 2,900 g |
| 30 m | 2,500 g | 3,300 g | 3,300 g |
| 40 m | 2,900 g | 3,700 g | 3,700 g |
| 50 m | 3,300 g | 4,100 g | 4,100 g |
- Factory / precharged amount: 2,100 g for AOTG30LBTC.
- Factory / precharged amount: 2,900 g for AOTG36LBTC and AOTG45LBTC.
- Additional refrigerant: 40 g per metre above 20 m.
- Maximum pipe height: 30 m.
4. Wired controller / indoor fault codes
If a wired remote controller is connected, the error code is shown on the controller display. With the optional wireless receiver, the Operation, Timer and Economy lamps flash in matching patterns.
| Code | Description |
|---|---|
| 11 | Serial communication error |
| 12 | Wired remote control communication error |
| 15 | Check run unfinished |
| 21 | R.C. address or refrigerant circuit address setting error |
| 22 | Indoor unit capacity error |
| 23 | Combination error |
| 24 | Connection R.C. address error |
| 27 | Primary / secondary unit setup error |
| 31 | Power supply interruption error |
| 32 | Indoor unit PCB model information error |
| 35 | Manual Auto switch error |
| 41 | Inlet air temperature sensor error |
| 42 | Indoor heat exchanger middle temperature sensor error |
| 51 | Indoor fan motor 1 error |
| 53 | Drainage error |
| 57 | Damper error |
| 59 | Indoor fan motor 2 error / fan motor drive circuit error |
| 5U | Indoor unit error |
| 62 | Outdoor unit model information error |
| 63 | Inverter error |
| 64 | Active filter error / PFC circuit error |
| 65 | IPM error |
| 6A | Display PCB microcomputer communication error |
| 71 | Discharge temperature sensor error |
| 72 | Compressor temperature sensor error |
| 73 | Outdoor heat exchanger centre / liquid outlet temperature sensor error |
| 74 | Outdoor temperature sensor error |
| 75 | Suction gas temperature sensor error |
| 76 | 2-way / 3-way valve temperature sensor error |
| 77 | Heat sink temperature sensor error |
| 82 | Sub-cool heat exchanger gas inlet / outlet temperature sensor error |
| 83 | Liquid pipe temperature sensor error |
| 84 | Current sensor error |
| 86 | Pressure sensor / high pressure switch error |
| 94 | Over-current error |
| 95 | Compressor control error |
| 97 | Outdoor fan motor 1 error |
| 98 | Outdoor fan motor 2 error |
| 99 | 4-way valve / expansion valve coil error |
| A1 | Discharge temperature error |
| A3 | Compressor temperature error |
| A4 | High pressure error |
| A5 | Low pressure error |
| J2 | Branch box error - Flexible Multi |
5. Service and electrical reference
Indoor thermistor checks - ARTG30 / ARTG36
| Sensor | 0°C | 20°C | 30°C |
|---|---|---|---|
| Pipe thermistor | 176.0 kΩ | 62.9 kΩ | 39.6 kΩ |
| Room thermistor | 33.6 kΩ | 12.5 kΩ | 8.0 kΩ |
Outdoor thermistor reference
| Sensor | 0°C | 20°C | 30°C |
|---|---|---|---|
| Outdoor temperature | 35.2 kΩ | 12.6 kΩ | 8.0 kΩ |
| Compressor / discharge | 168.6-175.7 kΩ | 62.6-64.5 kΩ | 40.0-41.1 kΩ |
| Pipe / pipe-mid | 16.1 kΩ | 6.0-6.1 kΩ | 3.8-4.0 kΩ |
Key component checks
- AOTG30 compressor winding resistance: approximately 0.642 Ω at 20°C between U-V, V-W and U-W.
- AOTG36 / AOTG45 compressor winding resistance: approximately 0.432 Ω at 20°C between U-V, V-W and U-W.
- Outdoor expansion valve coil: approximately 46 Ω at 20°C from common to each winding.
- 4-way valve coil: supplied with 240 V AC when energised.
- Outdoor PTC thermistor initial resistance: approximately 40 Ω ±25% at 25°C.
Important: Do not condemn a PCB from a fault code alone. Confirm supply voltage, wiring, thermistor values, connector condition and component resistance before replacement.
6. Common service parts
ARTG30LHTA / ARTG36LHTA indoor
| Part | Part number |
|---|---|
| Remote controller | 9380219057 |
| Power supply PCB | 9707398281 |
| Main PCB - ARTG30 | 9710621987 |
| Main PCB - ARTG36 | 9710621994 |
| Fan motor | 9603086015 |
| Pipe thermistor | 9900814069 |
| Room thermistor | 9703299216 |
ARTG45LHTA indoor
| Part | Part number |
|---|---|
| Remote controller | 9380219057 |
| Main PCB | 9708281032 |
| Power supply PCB | 9708279015 |
| Filter PCB | 9708277028 |
| Fan motor | 9603087012 |
| Room thermistor | 9703299254 |
| Pipe thermistor | 9900951016 |
Outdoor units
| Part | AOTG30LBTC | AOTG36LBTC | AOTG45LBTC |
|---|---|---|---|
| Main PCB | 9709881293 | 9709904503 | 9709904510 |
| Fan motor | 9602843015 | 9603518004 | 9603518004 |
| Transistor PCB | 9708512136 | 9708646114 | 9708646114 |
| ACTPM | 9707592016 | 9707592016 | 9707592016 |
| Compressor | 9810135001 | 9810153005 | 9810153005 |
| Expansion valve coil | 9970095030 | 9970096044 | 9970096044 |
7. Accessories and control
- Standard wired remote controller: 9380219057.
- ARTG30 / ARTG36 include connections for a wired remote controller and optional receiver unit.
- ARTG45 includes terminals for external input, three external outputs, heater and fresh-air control, as shown in the service manual wiring diagram.
- AOTG36 / AOTG45 support an optional demand unit / demand PCB connection.
- Outdoor drain pipe: 9303029015; drain cap: 313166024302.
Technical data compiled from the ARTG30LHTA / ARTG36LHTA / ARTG45LHTA and AOTG30LBTC / AOTG36LBTC / AOTG45LBTC service manual. Always confirm current service documentation and replacement-part supersessions before ordering components.