GENERAL Assist Technical Reference

AUT36RLB3W / AOT36RCG3L

Cassette Split System – Cooling & Heating
Indoor: AUT36RLB3W  |  Outdoor: AOT36RCG3L  |  Refrigerant: R22
This article provides a technical reference for the legacy AUT36RLB3W cassette indoor unit matched with the AOT36RCG3L outdoor unit, including system specifications, refrigerant piping, electrical information, fault codes and key service components.
Legacy R22 equipment: This is an older R22 system. Refrigerant handling, electrical work and servicing must be completed by appropriately qualified personnel and in accordance with current local requirements. Parts availability should be confirmed before quoting repairs.

1. Quick reference

ItemDetails
Indoor unitAUT36RLB3W – cassette type
Outdoor unitAOT36RCG3L – reverse-cycle outdoor unit
Cooling capacity10.3–10.5 kW
Heating capacity10.5–10.7 kW
Power supply415 / 380 V, 3 phase, 50 Hz
RefrigerantR22
Liquid / gas pipe9.53 mm (3/8 in) / 19.05 mm (3/4 in)
Maximum pipe length50 m
Maximum height difference30 m
Remote controllerWired

2. System specifications

SpecificationCoolingHeating
Capacity10.3–10.5 kW10.5–10.7 kW
Running current7.2–7.4 A6.2–6.6 A
Input power3.95–4.05 kW3.30–3.40 kW
EER / efficiency value shown in manual2.61–2.59 kW/kW3.18–3.15 kW/kW

Airflow, dimensions and weight

ItemIndoorOutdoor
Airflow1,500 m³/h5,900 m³/h
Fan speedHigh 580 / Med 500 / Low 420 rpm790 rpm
Dimensions (H × W × D)296 × 830 × 830 mm1,152 × 940 × 370 mm
Grille dimensions35 × 940 × 940 mm
Net / gross weight40 / 53 kg96 / 110 kg
Drain connection: The cassette dimensional drawing specifies an approximately 32 mm inside diameter / 37 mm outside diameter drain connection.

3. Refrigerant circuit and charge

ItemSpecification
RefrigerantR22
Liquid line9.53 mm (3/8 in)
Gas line19.05 mm (3/4 in)
Maximum pipe length50 m
Maximum height difference30 m
Additional refrigerant rate40 g/m

Charge amounts shown in the service manual – AUT36RLB3W

Total pipe lengthFull charge amount
20 m3,000 g
30 m3,400 g
40 m3,800 g
50 m4,200 g
Do not substitute refrigerants based on this article. The original equipment is specified for R22. Any retrofit or refrigerant conversion requires a separate engineering/service assessment and must comply with current regulations.

Reverse-cycle refrigerant circuit

  • Hermetic three-phase compressor.
  • 4-way reversing valve.
  • Electronic expansion valve.
  • Accumulator, strainer and dryer.
  • High-pressure switch.
  • Outdoor control thermistors for discharge, pipe and outdoor temperature.

4. Electrical and control information

ItemDetails
System supply415 / 380 V, 3 phase, 50 Hz
Starting current50 A
CompressorCR47KQ-TFD, hermetic 2-pole, three-phase induction motor, reciprocating type
Indoor controller supplyIndoor PCB diagram identifies a 240 V, 50 Hz supply section.
Indoor PCB fuseF101 – T 3.15 A, 250 V
Outdoor PCB fuseF1 – 6.3 A, 250 V
Remote controllerWired remote controller connection to indoor terminal board
Outdoor control components shown in the circuit diagram: two outdoor fan motors, fan capacitors, compressor magnetic relay, power relay, 4-way valve coil, electronic expansion valve coil, belt heater, high-pressure switch and outdoor thermistors.

5. Fault codes and self-diagnosis

How to display a fault on the wired remote controller

  1. If EE:EE flashes in the clock/current-time display, an air-conditioner error is present.
  2. Press the SET TIME and TEMP./DAY buttons simultaneously for more than 3 seconds.
  3. The self-diagnosis function will display the stored error code in the current-time display.
  4. After checking the code, troubleshoot using the table below.
CodeFault description
E:00Communication error – indoor unit / remote controller
E:01Communication error – indoor unit / outdoor unit
E:02Room temperature sensor open circuit
E:03Room temperature sensor short circuit
E:04Indoor heat exchanger temperature sensor open circuit
E:05Indoor heat exchanger temperature sensor short circuit
E:06Outdoor heat exchanger temperature sensor open circuit
E:07Outdoor heat exchanger temperature sensor short circuit
E:08Power source connection error
E:09Float switch operated
E:0AOutdoor temperature sensor open circuit
E:0BOutdoor temperature sensor short circuit
E:0CDischarge pipe temperature sensor open circuit
E:0DDischarge pipe temperature sensor short circuit
E:0EOutdoor high-pressure abnormal
E:0FDischarge pipe temperature abnormal
E:11Model abnormal
E:12Indoor fan abnormal
E:13Outdoor signal abnormal
E:14Outdoor EEPROM abnormal

Outdoor PCB LED diagnosis

The AOT36RCG3L outdoor PCB uses LED1 to LED6 to indicate outdoor faults. The manual identifies LED patterns for signal abnormal, indoor unit abnormal, discharge-pipe temperature abnormal, outdoor heat exchanger temperature abnormal, outdoor temperature abnormal, power-source connection error, EEPROM abnormal and outdoor high-pressure abnormal.

Once the fault is cleared, the outdoor LED indication normally turns off. The manual notes that discharge-pipe temperature and high-pressure abnormal indications can remain continuously displayed for up to 24 hours while power remains on.

6. Common service components and part numbers

AUT36RLB3W indoor unit

ComponentPart number
Fan motor capacitor9703306068
Fan motor assembly9600878019
Room thermistor assembly9703299025
Pipe thermistor assembly9703297014
Controller PCB assembly9700637028
Wired remote control unit9703173035
Float switch9703285004
Drain pump unit9703125010
Step motor9360307019

AOT36RCG3L outdoor unit

ComponentPart number
Controller PCB assembly9703230059
Compressor assembly9368020002
Fan motor assembly9600832028
Fan motor capacitor9357965024
4-way valve9353055002
Solenoid coil9359616108
High-pressure switch9704045003
Expansion valve – main9363454017
Expansion valve coil9363467017
Thermistor assembly9900129019
Belt heater9361140103
Magnetic relay9363277005
Parts note: The part numbers above are taken from the original service manual. As this is legacy equipment, supersessions and current availability must be checked before parts are ordered.

7. Standard accessories listed in the manual

  • Coupler heat insulation.
  • Remote-controller cord clamp.
  • Binders and installation screws.
  • Special mounting nuts – large and small flange.
  • Wired remote control unit – reverse-cycle model part number 9703173035.
  • Installation template.
  • Blower-cover insulation and hook wire.
  • Outdoor power cap, auxiliary pipe assembly, edge cover, binder, putty and coupler heat insulation.

8. Service notes

  • The cassette includes a float switch and drain pump; an E:09 code indicates float-switch operation.
  • During test operation, confirm there are no abnormal sounds or vibration.
  • The manual notes that at low outdoor temperatures the outdoor fans may reduce speed, and one fan may stop intermittently.
  • Use the circuit diagrams when checking the compressor magnetic relay, fan capacitors, 4-way valve, electronic expansion valve, pressure switch and thermistor circuits.
  • Because this is three-phase equipment, confirm supply condition and phase connections when investigating an E:08 power source connection error.
Reference: AUT36ALB3W / AUT36RLB3W with AOT36ACG3L / AOT36RCG3L cassette split-system service documentation, dated 2003. This article is a summary only. Refer to the original circuit diagrams, disassembly illustrations and service documentation when completing detailed diagnostics or repair work.