GENERAL AIRSTAGE Technical Reference

ASTG18KMTC / ASTG22KMTC / ASTG24KMTC

Design, installation, controls and technical data
Indoor units ASTG18KMTC / ASTG22KMTC / ASTG24KMTC with outdoor units AOTG18KMTC / AOTG22KMTC / AOTG24KMTC
This article provides key technical information for the ASTG18KMTC, ASTG22KMTC and ASTG24KMTC wall-mounted R32 inverter systems, including capacities, airflow, dimensions, installation clearances, controls, function settings, external input/output and outdoor-unit requirements.
Important: Installation, electrical work, refrigerant handling and servicing must be carried out by appropriately qualified personnel and in accordance with applicable local regulations. Always refer to the current installation and service documentation before carrying out work.

1. Applicable models

SystemIndoor unitOutdoor unitRefrigerant
5.0 kW classASTG18KMTCAOTG18KMTCR32
6.0 kW classASTG22KMTCAOTG22KMTCR32
7.1 kW classASTG24KMTCAOTG24KMTCR32

2. Key specifications

SpecificationASTG18KMTCASTG22KMTCASTG24KMTC
Cooling capacity5.0 kW
1.0–6.5 kW
6.0 kW
1.1–7.5 kW
7.1 kW
1.1–8.3 kW
Heating capacity6.0 kW
1.05–8.7 kW
7.2 kW
1.1–9.4 kW
8.0 kW
1.1–10.1 kW
Power supply240 V ~ 50 Hz – power supplied to outdoor unit
Available voltage range198–264 V
Indoor dimensions280 × 980 × 240 mm (H × W × D)
Indoor net weight12.5 kg
Liquid pipeØ6.35 mm (1/4 in)
Gas pipeØ12.70 mm (1/2 in)
Indoor operating rangeCooling 18–32°C / Heating 16–30°C

Indoor airflow

Fan speedASTG18KMTCASTG22KMTCASTG24KMTC
High1,020 m³/h
283 L/s
1,060 m³/h
294 L/s
1,170 m³/h
325 L/s
Medium850 m³/h / 236 L/s
Low640 m³/h / 178 L/s
Quiet510 m³/h / 142 L/s

Indoor sound pressure

Fan speedASTG18KMTCASTG22KMTCASTG24KMTC
High46 dB(A)48 dB(A)49 dB(A)
Medium40 dB(A)
Low35 dB(A)
Quiet29 dB(A)

3. Indoor installation

Indoor unit minimum clearances

Above indoor unit50 mm or more
Left-hand side40 mm or more
Right-hand side70 mm or more
Clear space in front1,500 mm or more
Distance from floor1,800 mm or more
The indoor unit is 980 mm wide × 280 mm high × 240 mm deep. Pipe entry openings are Ø65 mm.

4. Controls and optional interfaces

These models are supplied with a wireless remote controller. Compatible wired controls and external interfaces can also be installed using the appropriate communication and connection kits.

Optional controllers

Part numberDescription
UTY-RNRYZWired remote controller with LCD display. Non-polar 2-wire connection.
UTY-RSRYSimple wired remote controller with Start/Stop, fan speed, temperature and operating mode control.
UTY-RHRYSimple remote controller providing Start/Stop, fan speed and temperature adjustment.
UTY-TWRXZ2Communication kit required to connect compatible non-polar 2-wire wired controllers.

External input and output

Part numberPurpose
UTY-XCSXZ2External input and output PCB for connecting external control devices.
UTY-XWZXZ5External connect kit required when an external device is connected.

External input functions include:

  • Operation / Stop
  • Forced Stop
  • Forced Thermostat Off

External output functions include:

  • Operation status
  • Error status
  • Indoor fan operation status
  • External heater output
External input wiring should use twisted-pair cable with a maximum length of 150 m and must be kept separate from power wiring.

External output wiring should use 22 AWG twisted-pair cable with a maximum length of 25 m.

Group control

Multiple indoor units can be operated together using one compatible wired remote controller.

  • Up to 16 indoor units can be connected when automatic addressing is used.
  • Total remote-controller wiring length must not exceed 500 m.
  • When manually addressing the system, connect up to 15 indoor units.
  • Each manually addressed indoor unit must use a unique remote-controller address.
Note: When different indoor-unit types are connected to the same group-control system, some functions may no longer be available.

5. Function settings

Function settings allow the indoor unit to be configured for the installation environment, sensor selection and external control requirements.

Function No.FunctionSummary
00Remote controller addressUnit numbers 0–15 for group control.
11Filter sign400 h / 1,000 h / 200 h / no indication.
30 / 31Indoor sensor temperature correctionCooling and heating temperature correction.
35 / 36Wired controller sensor correctionAvailable when Function 42 is configured for both sensors.
40Auto restart00 Enable / 01 Disable.
42Room temperature sensor switching00 Indoor unit / 01 Both indoor unit and wired controller.
44Wireless remote custom codeA / B / C / D selection.
46External input controlOperation/Stop mode 1, Forced Stop or Operation/Stop mode 2.
48Room temperature sensor switching (Aux.)Both sensors or wired remote controller only.
49Indoor fan energy savingControls indoor fan operation when the outdoor unit stops during cooling.
61External heater controlSelects the external heater control strategy.
62External heater operating temperatureSets heater ON/OFF temperature thresholds.
66 / 67Outdoor temperature zone boundariesUsed with external heater control based on outdoor temperature.

Entering function setting mode with the wireless remote

  1. Press and hold POWERFUL and the TEMP ▲ button together.
  2. While holding both buttons, press RESET.
  3. Use the TEMP buttons to select the function number.
  4. Press 10°C HEAT to switch between the left and right digits.
  5. Press POWERFUL to move to the setting value.
  6. Use the TEMP buttons to select the required value.
  7. Press MODE once and confirm the beep.
  8. Press START/STOP to store the setting.
  9. Press RESET to exit function setting mode.
  10. Disconnect power, wait at least 30 seconds, then reconnect power.
Caution: Function settings do not become active until the power supply has been disconnected and reconnected. Wait at least 30 seconds before restoring power.

6. Outdoor unit technical data

SpecificationAOTG18KMTCAOTG22KMTCAOTG24KMTC
Dimensions716 × 820 × 315 mm (H × W × D)
Net weight42 kg
RefrigerantR32
Factory charge1,320 g
Pre-charge pipe length15 m
Maximum pipe length30 m
Maximum height difference25 m
Cooling operating range-10°C to 46°C
Heating operating range-15°C to 24°C
Cooling sound pressure47 dB(A)49 dB(A)54 dB(A)
Heating sound pressure48 dB(A)52 dB(A)52 dB(A)
Starting current5.6 A7.4 A8.9 A

Outdoor airflow

ModelCoolingHeating
AOTG18KMTC2,330 m³/h
647 L/s
2,390 m³/h
664 L/s
AOTG22KMTC2,500 m³/h
695 L/s
2,820 m³/h
783 L/s
AOTG24KMTC3,240 m³/h
900 L/s
2,820 m³/h
783 L/s

Additional refrigerant charge

The outdoor unit contains 1,320 g of R32 and is pre-charged for up to 15 m of refrigerant pipe.

Additional refrigerant above 15 m is 20 g per metre.
Total pipe lengthAdditional R32
15 m or less0 g
20 m100 g
25 m200 g
30 m maximum300 g

Electrical characteristics

SpecificationAOTG18KMTCAOTG22KMTCAOTG24KMTC
Max operating current13.5 A16.0 A16.0 A
Starting current5.6 A7.4 A8.9 A
Circuit breaker16 A20 A20 A
Power cable2.5 mm²
Connection cable1.5–2.5 mm²
Limited wiring length31 m
Electrical note: Cable size and circuit protection must comply with applicable Australian or New Zealand electrical requirements. Where voltage drop reaches 2% or more, conductor size must be increased.

Outdoor installation clearances

Obstacle at rear only100 mm or more
Obstacle at front600 mm or more
Obstacles front and rearFront 600 mm or more / rear 100 mm or more
Multiple outdoor unitsMinimum 250 mm between units
Do not rely on one clearance dimension for every installation. Required clearances change depending on rear, side, front and overhead obstructions and whether multiple outdoor units are installed. Refer to the installation diagrams for the actual site configuration.

7. Service and protection information

Indoor unit protection

  • Indoor PCB fuse: 250 V, 3.15 A.
  • Fan motor thermal protection activates at approximately 150 ±15°C.
  • Fan motor restart occurs after the protection condition resets at approximately 120 ±15°C.

Outdoor unit protection

  • Main PCB protection includes 250 V, 25 A and 250 V, 5 A fuses.
  • Outdoor fan protection activates at approximately 100 ±15°C and resets at approximately 95 ±10°C.
  • Compressor discharge-temperature protection operates at approximately 110°C.
  • Compressor restart is permitted after approximately 7 minutes once the discharge-temperature protection has operated.
  • During COOL or DRY operation, low outdoor-temperature protection stops the compressor at approximately -15°C and allows restart at approximately -10°C.
Technical information summarised from Design & Technical Manual DR_AS088EF_07 for ASTG18KMTC / ASTG22KMTC / ASTG24KMTC and AOTG18KMTC / AOTG22KMTC / AOTG24KMTC. Product specifications and design are subject to change. Always verify against current technical documentation before installation or service work.