GENERAL AIRSTAGE Technical Reference

ASTG18KMCB / ASTG22KMCB / ASTG24KMCB

Design & Technical Information
Wall-mounted R32 inverter heat pump systems with AOTG18KMCB / AOTG22KMCB / AOTG24KMCB outdoor units
This article provides key technical, installation, airflow, electrical, refrigerant, control and function-setting information for the ASTG18KMCB, ASTG22KMCB and ASTG24KMCB wall-mounted indoor units and their matching outdoor units.
Important: This information is intended for qualified service and installation personnel. Installation, electrical work, refrigerant handling and commissioning must be completed in accordance with the applicable installation instructions and local regulations.

1. Applicable models

Indoor UnitOutdoor UnitRated CoolingRated Heating
ASTG18KMCBAOTG18KMCB5.00 kW6.00 kW
ASTG22KMCBAOTG22KMCB6.00 kW7.20 kW
ASTG24KMCBAOTG24KMCB7.10 kW8.00 kW
System type: Wall-mounted inverter heat pump
Refrigerant: R32
Power supply: 240 V ~ 50 Hz
Power supply intake: Outdoor unit
Available voltage range: 198-264 V

2. Key specifications

SpecificationASTG18ASTG22ASTG24
Rated cooling capacity5.00 kW6.00 kW7.10 kW
Cooling capacity range1.00-6.50 kW1.10-7.50 kW1.10-8.30 kW
Rated heating capacity6.00 kW7.20 kW8.00 kW
Heating capacity range1.05-8.30 kW1.10-9.70 kW1.10-10.60 kW
Rated cooling input1.22 kW1.59 kW2.01 kW
Rated heating input1.42 kW1.77 kW2.12 kW
Maximum operating current - heating13.5 A16.0 A16.0 A

Indoor unit dimensions

Dimensions: 295 × 940 × 270 mm (H × W × D)
Net weight: 14 kg
Gross weight: 17 kg

Outdoor unit dimensions

Dimensions: 620 × 790 × 290 mm (H × W × D)
Net weight: 40 kg
Gross weight: 44 kg

Indoor airflow

ModelHighMediumLowQuiet
ASTG18KMCB258 L/s
930 m³/h
217 L/s
780 m³/h
175 L/s
630 m³/h
139 L/s
500 m³/h
ASTG22KMCB278 L/s
1,000 m³/h
231 L/s
830 m³/h
189 L/s
680 m³/h
161 L/s
580 m³/h
ASTG24KMCB311 L/s
1,120 m³/h
231 L/s
830 m³/h
189 L/s
680 m³/h
161 L/s
580 m³/h

Indoor sound pressure

ModelHighMediumLowQuiet
ASTG18KMCB46 dB(A)40 dB(A)35 dB(A)29 dB(A)
ASTG22KMCB48 dB(A)42 dB(A)37 dB(A)32 dB(A)
ASTG24KMCB49 dB(A)42 dB(A)37 dB(A)32 dB(A)

Outdoor sound pressure

Outdoor ModelCoolingHeating
AOTG18KMCB47 dB(A)48 dB(A)
AOTG22KMCB49 dB(A)52 dB(A)
AOTG24KMCB52 dB(A)52 dB(A)
Sound pressure levels are measured under manufacturer test conditions. Actual installed sound levels can vary depending on the surrounding environment, mounting and installation conditions.

3. Refrigerant and piping

RefrigerantR32
Factory refrigerant charge1,270 g
Liquid pipe6.35 mm (1/4 in)
Gas pipe12.70 mm (1/2 in)
Factory pre-charge length20 m
Maximum pipe length30 m
Maximum height difference20 m

Additional refrigerant charge

Total pipe lengthAdditional R32 charge
20 m or less0 g
25 m100 g
30 m maximum200 g
Charge rate beyond 20 m: 20 g/m.

Operating range

OperationIndoorOutdoor
Cooling18-32°C, 80% RH or less-10 to 46°C
Heating16-30°C-15 to 24°C

Indoor installation clearances

The indoor-unit installation-space diagram specifies the following clearances:
  • 50 mm or more at the upper side areas shown in the installation diagram
  • 127 mm or more on the left lower side
  • 133 mm or more on the right lower side
  • 1,500 mm or more in front/below the indoor unit
  • 1,800 mm or more mounting height reference shown in the manual

Outdoor installation clearances

Obstacle conditionMinimum clearance
Rear obstacle only100 mm or more
Front obstacle only600 mm or more
Rear and side obstacles100 mm rear, with side clearances as shown in the installation diagram including 250 mm on one side
Rear and upper obstruction100 mm rear, 600 mm front/open area, maximum upper obstruction depth 200 mm
Cold climate installation: When outdoor temperature is 0°C or below, the manual advises not to use the accessory drain pipe and drain cap because the drain water may freeze. In heavy snowfall areas, the outdoor unit air inlet and outlet must also be protected from snow blockage.

4. Electrical characteristics

ItemAOTG18KMCBAOTG22KMCBAOTG24KMCB
Maximum operating current13.5 A16.0 A16.0 A
Starting current6.0 A7.5 A9.0 A
Circuit breaker16 A20 A20 A
Power cable2.5 mm²4.0 mm²4.0 mm²
Indoor/outdoor connection cable1.5 mm²
Connection cable limited length31 m
Electrical cable and circuit protection must be selected in accordance with applicable local requirements. The technical manual specifies that voltage drop should be limited to less than 2%; increase conductor size if required.

5. External control

External input and output

ConnectorFunction
CNA01Control input
CNB01Operation status output
CNB02Error status output
External input:
  • Operation/Stop or Forced Stop can be selected using the indoor-unit function settings.
  • Use twisted-pair 22 AWG cable.
  • Maximum external-input wiring length is 150 m.
  • Keep the control cable separate from power wiring.
  • Use non-polar relays and switches.

External control accessories

PartModel
External connect kitUTY-XWZXZ5
Communication kitUTY-TWBXF1
Important: The communication kit is required in addition to the UTY-XWZXZ5 external connect kit when using the external control functions described in this manual.

Group control

Up to 16 indoor units can be controlled by one compatible wired remote controller using group control.
Total remote-controller cable lengthCable cross-section
100 m or less0.3-0.8 mm²
100-200 m0.5-0.8 mm²
200-300 m0.8 mm²
Maximum group-control remote-controller wiring length: 300 m.

Group control parts

PartPart / Model Number
Communication kitUTY-TWBXF1 / UTY-XCBXZ2
Wire with connector9705932012

6. Function settings

Caution: Incorrect function settings can cause the product to malfunction.

Entering function-setting mode using the wireless controller

  1. While pressing the POWERFUL button and the TEMP ▲ button simultaneously, press RESET.
  2. Use the TEMP buttons to select the function number.
  3. Press POWERFUL to move to the setting value.
  4. Use the TEMP buttons to select the required setting value.
  5. Press MODE once and confirm the beep.
  6. Press START/STOP to confirm the setting.
  7. Press RESET to exit function-setting mode.
  8. Disconnect the power supply after completing the settings.
  9. Wait at least 30 seconds, then reconnect power.
FunctionDescription
11Filter sign
30 / 31Room temperature control for indoor-unit sensor - cooling / heating
35 / 36Room temperature control for wired remote-controller sensor
40Auto restart
42Room temperature sensor switching
44Remote controller custom code
46External input control
48Room temperature sensor switching - auxiliary
49Indoor fan control for energy saving during cooling
95Heat insulation condition / building insulation

Function 40 - Auto restart

00Enable - factory setting
01Disable

Function 42 - Room temperature sensor switching

00Indoor-unit sensor - factory setting
01Both indoor-unit and wired-controller sensor

Function 44 - Remote controller custom code

00Code A - factory setting
01Code B
02Code C
03Code D

Function 46 - External input control

00Operation / Stop mode 1 - factory setting
01Setting prohibited
02Forced Stop
03Operation / Stop mode 2

Function 48 - Temperature sensor switching

00Both - factory setting
01Wired remote controller only
Note: Function 48 operates only when Function 42 has been set to Both (01).

Function 95 - Building insulation

00Standard insulation - factory setting
01High insulation
Important: Set Function 95 before adjusting Functions 30, 31, 35 or 36. Changing Function 95 afterwards resets those room-temperature correction settings to 0.0°C.

7. Compatible controllers and optional parts

PartModelDescription
Wired remote controllerUTY-RVNYNPolar 3-wire wired remote controller. Communication kit required for installation.
Wired remote controllerUTY-RNNYNPolar 3-wire controller with built-in temperature sensor. Communication kit required.
Simple remote controllerUTY-RSNYNProvides basic Start/Stop, fan, temperature and operating-mode control. Communication kit required.
External connect kitUTY-XWZXZ5Required when an external device is connected.
Communication kitUTY-TWBXF1Used to connect optional devices to the indoor-unit PCB.
Group-control communication kitUTY-TWBXF1 / UTY-XCBXZ2Communication-kit options listed for wall-mounted group-control applications.
Group-control service wire9705932012Wire with connector used for group-control wiring.

8. Safety devices

Indoor unit

PCB fuse250 V, 3.15 A
Fan motor protection activation150 ±15°C - fan motor stop
Fan motor protection reset120 ±15°C - fan motor restart

Outdoor unit

PCB fuses250 V, 25 A and 250 V, 5 A
Outdoor fan protection activation100 ±15°C - fan motor stop
Outdoor fan protection reset95 ±10°C - fan motor restart
Compressor discharge protection110°C - compressor stop
Compressor restartAfter 7 minutes
Terminal thermal fuse1 A, 70°C
Technical manual reference: DR_AS038EF_10, dated 10 July 2020. Product specifications and design may change without notice. Always confirm the latest applicable product documentation before installation or service work.