GENERAL AIRSTAGE Technical Reference

ASTG18KMCA / ASTG22KMCA / ASTG24KMCA

Design, specifications, airflow, controls, pipework and function settings
Indoor: ASTG18KMCA / ASTG22KMCA / ASTG24KMCA
Outdoor: AOTG18KMCA / AOTG22KMCA / AOTG24KMCA
Refrigerant: R32
This article provides a consolidated technical reference for the ASTG18KMCA, ASTG22KMCA and ASTG24KMCA wall-mounted systems, including capacities, airflow, refrigerant requirements, electrical data, controls, external input/output and function settings.
Important: Installation, electrical and refrigerant work must be completed by appropriately qualified personnel. Always refer to the relevant installation and service documentation before carrying out work.

1. Applicable Models

Indoor UnitOutdoor UnitRated CoolingRated Heating
ASTG18KMCAAOTG18KMCA5.00 kW6.00 kW
ASTG22KMCAAOTG22KMCA6.00 kW7.20 kW
ASTG24KMCAAOTG24KMCA7.10 kW8.00 kW

2. Key Specifications

Specification182224
Power supply240 V ~ 50 Hz
Available voltage range198 - 264 V
Cooling range1.00 - 6.50 kW1.10 - 7.50 kW1.10 - 8.30 kW
Heating range1.05 - 8.30 kW1.10 - 9.70 kW1.10 - 10.60 kW
Indoor dimensions295 x 940 x 270 mm
Indoor net weight14 kg
Outdoor dimensions620 x 790 x 290 mm
Outdoor net weight40 kg
Outdoor operating range:
Cooling: -10°C to 46°C
Heating: -15°C to 24°C

3. Indoor Airflow

ModelHighMediumLowQuiet
ASTG18KMCA930 m³/h
258 L/s
780 m³/h
217 L/s
630 m³/h
175 L/s
500 m³/h
139 L/s
ASTG22KMCA1000 m³/h
278 L/s
830 m³/h
231 L/s
680 m³/h
189 L/s
580 m³/h
161 L/s
ASTG24KMCA1120 m³/h
311 L/s
830 m³/h
231 L/s
680 m³/h
189 L/s
580 m³/h
161 L/s

Indoor Sound Pressure

ModelHighMediumLowQuiet
ASTG18KMCA46 dB(A)40 dB(A)35 dB(A)29 dB(A)
ASTG22KMCA48 dB(A)42 dB(A)37 dB(A)32 dB(A)
ASTG24KMCA49 dB(A)42 dB(A)37 dB(A)32 dB(A)

4. Refrigerant and Pipework

RefrigerantR32
Factory charge1270 g
Liquid pipe6.35 mm (1/4")
Gas pipe12.70 mm (1/2")
Factory pre-charge pipe length20 m
Maximum pipe length30 m
Maximum height difference20 m
Additional refrigerant above 20 m20 g/m

Additional Refrigerant Charge

Total Pipe LengthAdditional Charge
20 m or less0 g
25 m100 g
30 m200 g
Refrigerant charging: The outdoor unit contains 1270 g of R32 and is pre-charged for up to 20 m of total pipe length. For pipe lengths greater than 20 m, add R32 at 20 g per metre.

5. Electrical Characteristics

SpecificationAOTG18KMCAAOTG22KMCAAOTG24KMCA
Maximum operating current13.5 A16.0 A16.0 A
Starting current6.0 A7.5 A9.0 A
Circuit breaker16 A20 A20 A
Power cable2.5 mm²4.0 mm²4.0 mm²
Indoor interconnection: The indoor unit technical data specifies a connection cable of 1.5 - 2.5 mm² with a limited wiring length of 31 m. Voltage drop should be kept below 2%.

6. Wireless Remote Controller Features

  • Auto, Cool, Dry, Fan and Heat operating modes.
  • ON timer.
  • OFF timer.
  • Weekly timer.
  • Program timer.
  • Sleep timer.
  • Powerful operation.
  • Economy operation.
  • Human Sensor energy-saving operation.
  • 10°C HEAT operation.
  • Outdoor Unit Low Noise operation.
  • Remote controller custom codes A, B, C and D.
Powerful Operation: The system can operate for approximately 20 minutes using maximum airflow and maximum compressor speed to provide rapid cooling or heating.
10°C HEAT: When selected, the system can maintain the room at approximately 10°C when the room temperature drops below 10°C.
Human Sensor: The indoor unit detects movement within the room and can reduce operating capacity when the room is unoccupied. When occupancy is detected again, the unit returns to its previous operating mode.

7. Function Settings

FunctionFunction No.Settings
Filter sign1100 Standard 400 h / 01 Long 1000 h / 02 Short 200 h / 03 No indication (factory)
Room temperature correction - cooling3000 Standard (factory) / 01 Slightly lower / 02 Lower / 03 Higher
Room temperature correction - heating3100 Standard (factory) / 01 Lower / 02 Slightly higher / 03 Higher
Auto restart4000 Enable (factory) / 01 Disable
Room temperature sensor switching4200 Indoor unit sensor (factory) / 01 Indoor unit + wired controller sensor
Remote controller custom code4400 A (factory) / 01 B / 02 C / 03 D
External input control4600 Operation/Stop (factory) / 01 Setting prohibited / 02 Forced Stop
Indoor fan energy saving - cooling4900 Disable (factory) / 01 Enable

Entering Function Setting Mode

  1. Turn the system power on.
  2. While pressing POWERFUL and SET TEMP simultaneously, press RESET.
  3. Use the SET TEMP buttons to select the required function number.
  4. Use the 10°C HEAT button to move between the left and right digits.
  5. Press POWERFUL to move to the setting value.
  6. Select the required setting value using SET TEMP.
  7. Press MODE to confirm the setting.
  8. Confirm the indoor unit produces a beep.
  9. Press START/STOP and confirm another beep.
  10. Press RESET to exit Function Setting mode.
  11. Turn the system power off.
  12. Wait at least 30 seconds before restoring power.
Important: Function setting changes will not become active until the system power has been switched off and then back on. Wait at least 30 seconds before restoring power.

8. External Input and Output

ConnectorFunctionDescription
CNA01Control inputOperation/Stop or Forced Stop input depending on Function 46.
CNB01Operation status outputProvides an operating status signal from the indoor unit.
CNB02Error status outputProvides an error status signal from the indoor unit.
Required components:
Communication Kit: UTY-TWBXF1
External Connect Kit: UTY-XWZXZ5

The communication kit is required when connecting external devices to these indoor units.
External connection limits: The maximum distance between the indoor unit PC board and the connected external device is 10 m.

9. Optional Controllers and Accessories

TypeModelNotes
Wired Remote ControllerUTY-RVNYNRequires UTY-TWBXF1 Communication Kit.
Wired Remote ControllerUTY-RNNYNIncludes built-in room temperature sensor. Requires UTY-TWBXF1.
Simple Remote ControllerUTY-RSNYNProvides basic Start/Stop, fan speed, temperature and mode control. Requires UTY-TWBXF1.
Communication KitUTY-TWBXF1Provides the interface between compatible optional devices and the indoor unit PC board.
External Connect KitUTY-XWZXZ5Used for external input/output connections. UTY-TWBXF1 is also required.

10. Service and Protection Information

Indoor PCB fuse250 V / 3.15 A
Outdoor main PCB fuses250 V / 25 A and 250 V / 5 A
Outdoor fan motor protection OFF100 ± 15°C
Outdoor fan motor protection ON95 ± 10°C
Compressor discharge temperature protectionOFF at 110°C
Compressor restart after thermal protectionAfter 7 minutes

11. Quick Reference

Refrigerant: R32
Factory charge: 1270 g
Pre-charge: 20 m
Maximum pipe length: 30 m
Maximum height difference: 20 m
Additional charge: 20 g/m above 20 m
Liquid pipe: 6.35 mm
Gas pipe: 12.70 mm
Cooling outdoor range: -10°C to 46°C
Heating outdoor range: -15°C to 24°C
Communication kit: UTY-TWBXF1
Technical reference: Design & Technical Manual DTR_AS082E_04 / DTR_AO144E_03 for ASTG18KMCA, ASTG22KMCA, ASTG24KMCA and AOTG18KMCA, AOTG22KMCA, AOTG24KMCA. Refer to the complete technical documentation for wiring diagrams, dimensional drawings, capacity correction tables, refrigerant circuit diagrams and sound curves.