GENERAL AIRSTAGE Technical Reference

ASTG09KMTC / ASTG12KMTC

Design, installation, controls and technical data
Indoor units ASTG09KMTC / ASTG12KMTC with outdoor units AOTG09KMTC / AOTG12KMTC
This article consolidates key technical information for the ASTG09KMTC and ASTG12KMTC wall-mounted R32 inverter systems, including capacities, airflow, dimensions, installation clearances, optional controllers, function settings, external input/output and outdoor-unit data.
Important: Installation, electrical work, refrigerant handling and servicing must be carried out by appropriately qualified personnel and in accordance with applicable local regulations. Always refer to the current installation and service documentation before carrying out work.

1. Applicable models

SystemIndoor unitOutdoor unitRefrigerant
2.5 kW classASTG09KMTCAOTG09KMTCR32
3.5 kW classASTG12KMTCAOTG12KMTCR32

2. Key specifications

SpecificationASTG09KMTCASTG12KMTC
Cooling capacity2.5 kW rated (0.8–3.6 kW)3.5 kW rated (0.8–4.1 kW)
Heating capacity3.2 kW rated (0.9–5.3 kW)3.7 kW rated (0.9–6.1 kW)
Power supply240 V ~ 50 Hz, power supplied to outdoor unit
Available voltage range198–264 V
Indoor dimensions (H × W × D)270 × 834 × 222 mm
Indoor net weight10 kg
Pipe sizesLiquid Ø6.35 mm (1/4 in) / Gas Ø9.52 mm (3/8 in)
Indoor operating rangeCooling 18–32°C / Heating 16–30°C

Indoor airflow

ModeFan speedASTG09KMTCASTG12KMTC
CoolingHigh700 m³/h (194 L/s)700 m³/h (194 L/s)
Medium560 m³/h560 m³/h
Low430 m³/h430 m³/h
Quiet250 m³/h250 m³/h
HeatingHigh710 m³/h (197 L/s)770 m³/h (214 L/s)
Medium550 m³/h640 m³/h
Low470 m³/h520 m³/h
Quiet310 m³/h310 m³/h

Indoor sound pressure

ModeASTG09KMTCASTG12KMTC
Cooling - High40 dB(A)40 dB(A)
Cooling - Medium35 dB(A)35 dB(A)
Cooling - Low30 dB(A)30 dB(A)
Cooling - Quiet19 dB(A)19 dB(A)
Heating - High40 dB(A)42 dB(A)
Heating - Quiet21 dB(A)21 dB(A)

3. Indoor installation

Indoor unit minimum clearances

Above indoor unit50 mm or more
Right-hand side70 mm or more
Left-hand side40 mm or more
Distance from floor1,800 mm or more
Clear space in front of unit1,500 mm or more
The indoor unit dimensions are 834 mm wide × 270 mm high × 222 mm deep. Pipe entry holes are Ø65 mm.

4. Controls and optional interfaces

The ASTG09KMTC and ASTG12KMTC are supplied with a wireless remote controller. Wired control and external input/output functions can also be added using the appropriate optional interfaces.

Optional controllers

Part numberDescription
UTY-RNRYZWired remote controller, non-polar 2-wire.
UTY-RSRYSimple remote controller with Start/Stop, fan, temperature and operation mode controls.
UTY-RHRYSimple remote controller with Start/Stop, fan and temperature adjustment.
UTY-TWRXZ2Communication kit required for compatible non-polar 2-wire wired remote controllers.

External input and output

Part numberPurpose
UTY-XCSXZ2External input and output PCB.
UTY-XWZXZ5External connect kit used when connecting an external device.

External input functions include:

  • Operation / Stop
  • Forced Stop
  • Forced Thermostat Off

Available external outputs include:

  • Operation status
  • Error status
  • Indoor fan operation status
  • External heater output
External input wiring should use twisted-pair cable with a maximum length of 150 m and must be separated from power wiring. External output wiring should use 22 AWG twisted-pair cable with a maximum length of 25 m.

Group control

Multiple indoor units can be operated at the same time using a single compatible wired remote controller.

  • Up to 16 indoor units can be connected when automatic addressing is used.
  • Total remote-controller wiring length must not exceed 500 m.
  • If addresses are manually assigned, connect up to 15 indoor units.
  • Each manually addressed indoor unit must have a unique remote-controller address.
Note: When different indoor-unit types are connected within the same group-control system, some functions may no longer be available.

5. Function settings

Function settings allow the indoor unit to be configured to suit the installation environment and control requirements.

Function No.FunctionSummary
00Remote controller addressSets the indoor-unit number for group control.
11Filter sign400 h / 1,000 h / 200 h / no indication.
30 / 31Indoor sensor temperature correctionCooling / heating correction settings.
35 / 36Wired controller sensor correctionAvailable when Function 42 is set to Both.
40Auto restart00 Enable (factory) / 01 Disable.
42Room temperature sensor switching00 Indoor unit / 01 Both indoor and wired controller.
44Wireless remote custom codeA / B / C / D selection.
46External input control00 Operation/Stop mode 1 / 02 Forced stop / 03 Operation/Stop mode 2.
48Room sensor switching (Aux.)00 Both / 01 Wired remote controller only.
49Indoor fan energy saving in coolingControls fan behaviour while the outdoor unit is stopped.
61 / 62External heater controlSelect external-heater control method and operating temperature conditions.
66 / 67Outdoor temperature zone boundariesUsed with external-heater control by outdoor temperature.

Entering function setting mode with the wireless remote

  1. While pressing POWERFUL and TEMP ▲ together, press RESET.
  2. Use the TEMP buttons to select the function number. Use 10°C HEAT to move between digits.
  3. Press POWERFUL to move to the setting value.
  4. Select the required value with the TEMP buttons.
  5. Press MODE once and confirm the beep.
  6. Press START/STOP to store the setting and confirm the beep.
  7. Press RESET to exit.
  8. Disconnect the power supply, wait at least 30 seconds, then reconnect power for the setting to take effect.

6. Outdoor unit technical data

SpecificationAOTG09KMTCAOTG12KMTC
Dimensions (H × W × D)542 × 799 × 290 mm
Net weight32 kg
Refrigerant / factory chargeR32 / 850 g
Pre-charge length15 m
Maximum pipe length20 m
Maximum height difference15 m
Cooling operating range-10°C to 46°C
Heating operating range-15°C to 24°C
Sound pressure46 dB(A)49 dB(A)
Maximum operating current7.5 A9.0 A
Circuit breaker10 A

Additional refrigerant charge

The outdoor unit is factory charged for up to 15 m of total pipe length. For pipe lengths above 15 m up to the maximum 20 m, add 20 g/m of R32. At 20 m total pipe length, the additional charge is 100 g.

Outdoor installation space – common single-unit examples

Obstacle at rear only100 mm or more
Obstacles at rear and sidesRear 100 mm or more / sides 100 mm or more / 250 mm or more as shown in installation diagram
Obstacle at front600 mm or more
Obstacles at front and rearFront 600 mm or more / rear 100 mm or more
Do not guess outdoor clearances. The required space changes depending on surrounding obstacles, overhead obstructions and whether multiple units are installed. Use the installation-space diagrams in the technical manual for the actual site arrangement.

7. Service notes

  • The outdoor refrigerant circuit includes compressor, 4-way valve, expansion valve, strainers and indoor/outdoor heat exchangers.
  • The indoor-unit PCB includes protection by a 250 V, 3.15 A fuse and fan-motor thermal protection.
  • The outdoor unit includes compressor discharge-temperature protection and low outdoor-temperature protection in COOL/DRY operation.
  • Actual sound levels at site can be higher than published values due to surrounding surfaces and the installation environment.
Technical information summarised from Design & Technical Manual DR_AS079EF_05 for ASTG09KMTC / ASTG12KMTC and AOTG09KMTC / AOTG12KMTC. Product specifications and design are subject to change. Always verify against current technical documentation before installation or service work.