GENERAL AIRSTAGE Technical Reference

ASTG09KMCB / ASTG12KMCB

Design & Technical Information
Wall-mounted R32 inverter heat pump systems with AOTG09KMCB / AOTG12KMCB outdoor units
This article summarises the key design, installation, electrical, airflow, control and optional-accessory information for the ASTG09KMCB and ASTG12KMCB indoor units and their matching AOTG09KMCB and AOTG12KMCB outdoor units.
Important: This is a technical reference for qualified personnel. Installation, electrical work, refrigerant handling and commissioning must be completed in accordance with the applicable installation instructions and local regulations.

1. Applicable models

Indoor UnitOutdoor UnitRated CoolingRated Heating
ASTG09KMCBAOTG09KMCB2.50 kW3.20 kW
ASTG12KMCBAOTG12KMCB3.50 kW3.70 kW
System type: Wall-mounted inverter heat pump
Refrigerant: R32
Power supply: 240 V ~ 50 Hz, supplied to the outdoor unit
Available voltage range: 198-264 V

2. Key specifications

SpecificationASTG09 / AOTG09ASTG12 / AOTG12
Cooling capacity range0.90-3.60 kW0.90-4.10 kW
Heating capacity range0.90-5.30 kW0.90-5.60 kW
Rated cooling input0.51 kW0.86 kW
Rated heating input0.65 kW0.81 kW
Maximum operating currentCooling 6.0 A / Heating 7.5 ACooling 6.5 A / Heating 9.0 A
Indoor dimensions H × W × D268 × 840 × 203 mm
Indoor net weight8.5 kg
Outdoor dimensions H × W × D540 × 790 × 290 mm
Outdoor net weight34 kg

Indoor airflow

ModelHighMediumLowQuiet
ASTG09 cooling194 L/s156 L/s125 L/s86 L/s
ASTG12 cooling200 L/s169 L/s133 L/s86 L/s

Sound pressure level

ModelIndoor high / quietOutdoor
0940 / 21 dB(A) cooling47 dB(A)
1242 / 21 dB(A) cooling49 dB(A)
Sound pressure values are manufacturer test-room values. Actual installed sound levels may be higher depending on the surrounding environment.

3. Refrigerant, piping and installation

RefrigerantR32
Factory charge850 g
Liquid pipe6.35 mm (1/4 in)
Gas pipe9.52 mm (3/8 in)
Maximum pipe length20 m
Maximum height difference15 m
Additional refrigerant0 g for total pipe length up to 20 m

Operating range

ConditionIndoorOutdoor
Cooling18-32°C, 80% RH or less10-46°C
Heating16-30°C-15 to 24°C

Indoor installation clearances

The technical manual specifies minimum clearances around the indoor unit, including 25 mm or more to the left, 52 mm or more to the right, 70 mm or more on the left pipe-entry side, 130 mm or more on the right pipe-entry side, and approximately 1,500 mm or more below the unit. The installation drawing should be checked when positioning the unit.

Outdoor installation clearances - common examples

Obstacle conditionMinimum space
Rear only100 mm or more
Front only600 mm or more
Rear + sidesRear 100 mm or more, sides 250 mm / 100 mm or more as shown in the installation layout
Rear + upper obstructionRear 100 mm or more, front/opening 600 mm or more, upper obstruction max. 200 mm
Cold-climate drainage: The technical manual advises not to use the accessory drain pipe and drain cap when the outdoor temperature is 0°C or below, as drain water may freeze. In heavy snowfall areas, prevent snow from blocking the air inlet or outlet.

4. Electrical characteristics

ItemAOTG09KMCBAOTG12KMCB
Maximum operating current7.5 A9.0 A
Starting current3.3 A4.2 A
Circuit breaker10 A16 A
Power cable1.5 mm²
Connection cable1.5 mm², limited wiring length 21 m
Cable and breaker selection must comply with local electrical requirements. The technical manual states that voltage drop should be limited to less than 2%.

5. External control and group connection

External input / output

ConnectorFunction
CNA01Control input - Operation/Stop or Forced Stop
CNB01Operation status output
CNB02Error status output
  • External input wiring: twisted pair 22 AWG, maximum 150 m.
  • Keep control wiring separate from the power cable.
  • The wall-mounted unit requires the communication kit plus the external connect wire for external functions.

Group control

Up to 16 indoor units can be controlled by one wired remote controller in a compatible group connection. The maximum total remote-controller cable length is 300 m. Cable cross-section requirements increase as the total wiring length increases.
Total remote-controller cable lengthCable cross-section
100 m or less0.3-0.8 mm²
100-200 m0.5-0.8 mm²
200-300 m0.8 mm²

6. Function settings

Caution: Incorrect function settings can cause product malfunction. After changing settings with the wireless controller, disconnect the power supply, wait at least 30 seconds, then reconnect power for the new setting to become active.
Function No.FunctionKey information
11Filter sign400 h / 1000 h / 200 h / no indication
30 / 31Indoor unit room-temperature correctionCooling / heating sensor correction, -4.0°C to +4.0°C options
35 / 36Wired-controller sensor correctionRequires Function 42 set to Both
40Auto restart00 Enable (factory) / 01 Disable
42Room temperature sensor switching00 Indoor unit / 01 Both
44Wireless remote custom codeA / B / C / D
46External input controlOperation/Stop mode 1, Forced Stop, or Operation/Stop mode 2
48Room temperature sensor switching (Aux.)Both or wired remote controller only
49Indoor fan energy-saving control in coolingDisable / Enable / Remote controller
95Building insulation condition00 Standard insulation / 01 High insulation
Function 95: Set the building-insulation condition before making Functions 30, 31, 35 or 36 changes. Changing Function 95 later resets those room-temperature correction settings to 0.0°C.

7. Compatible controllers and optional parts

PartModelUse
Wired remote controllerUTY-RVNYNPolar 3-wire wired controller
Wired remote controllerUTY-RNNYNPolar 3-wire controller with built-in room sensor
Simple remote controllerUTY-RSNYNBasic Start/Stop, mode, fan and temperature control
External connect kitUTY-XWZXZ5External input/output wire
Communication kitUTY-XCBXZ2Connects optional devices to the indoor PCB
Group connection communication kitUTY-TWBXF1 / UTY-XCBXZ2Required for compatible wall-mounted group-control applications
Service wire with connector9705932012Used in group/multiple remote-control wiring

8. Safety-device reference

DeviceProtection
Indoor PCB fuse250 V, 3.15 A
Outdoor main PCB fuses250 V, 20 A and 250 V, 5 A
Outdoor fan motor protectionStops at 150±15°C; restart threshold 120±15°C
Compressor discharge-temperature protectionCompressor stop at 110°C; restart after 2 minutes 20 seconds
Terminal thermal fuse1 A, 70°C
Technical manual reference: DR_AS044EF_06, dated 10 July 2020. Product specifications and design may change without notice. Always confirm the latest applicable documentation before installation or service work.