GENERAL AIRSTAGE Technical Reference

ASTG09KMCA / ASTG12KMCA

Design, specifications, airflow, controls, function settings and installation data
Indoor units: ASTG09KMCA / ASTG12KMCA  |  Outdoor units: AOTG09KMCA / AOTG12KMCA  |  Refrigerant: R32
This article consolidates the main service and design information for the ASTG09KMCA and ASTG12KMCA wall-mounted systems. Use it as a quick technical reference for model specifications, airflow, pipe limits, controls, external input/output and function settings.
Important: Installation, electrical and refrigerant work must be completed by suitably qualified personnel. Always confirm the latest installation and service information before carrying out work.

1. Applicable models

Indoor unitOutdoor unitRated coolingRated heating
ASTG09KMCAAOTG09KMCA2.50 kW3.20 kW
ASTG12KMCAAOTG12KMCA3.50 kW3.70 kW

2. Key specifications

SpecificationASTG09KMCA / AOTG09KMCAASTG12KMCA / AOTG12KMCA
Power supply240 V ~ 50 Hz
Available voltage range198-264 V
Cooling capacity range0.90-3.60 kW0.90-4.10 kW
Heating capacity range0.90-5.30 kW0.90-5.60 kW
Maximum operating current7.5 A9.0 A
Outdoor circuit breaker10 A16 A
Liquid pipe6.35 mm (1/4 in.)
Gas pipe9.52 mm (3/8 in.)
RefrigerantR32 - factory charge 850 g
Indoor dimensions (H x W x D)268 x 840 x 203 mm
Outdoor dimensions (H x W x D)540 x 790 x 290 mm
Operating range: Outdoor cooling operation is specified from 10°C to 46°C. Heating operation is specified from -15°C to 24°C.

3. Indoor airflow

ModelModeHighMediumLowQuiet
ASTG09KMCACooling700 m³/h
194 L/s
560 m³/h
156 L/s
450 m³/h
125 L/s
310 m³/h
86 L/s
Heating700 m³/h
194 L/s
560 m³/h
156 L/s
470 m³/h
131 L/s
330 m³/h
92 L/s
ASTG12KMCACooling720 m³/h
200 L/s
610 m³/h
169 L/s
480 m³/h
133 L/s
310 m³/h
86 L/s
Heating720 m³/h
200 L/s
610 m³/h
169 L/s
520 m³/h
144 L/s
330 m³/h
92 L/s

Indoor sound pressure

ModelOperationHighMediumLowQuiet
ASTG09KMCACooling40 dB(A)36 dB(A)31 dB(A)21 dB(A)
ASTG12KMCACooling42 dB(A)37 dB(A)32 dB(A)21 dB(A)

4. Refrigerant and pipework

RefrigerantR32
Factory refrigerant charge850 g
Liquid pipe6.35 mm (1/4")
Gas pipe9.52 mm (3/8")
Maximum pipe length20 m
Maximum height difference15 m
Additional refrigerant chargeNone required up to the maximum 20 m pipe length
Important: The outdoor unit is factory charged with 850 g of R32 for a total pipe length of up to 20 m. The technical manual specifies an additional refrigerant charge of 0 g within this limit.

5. Wireless remote controller and functions

  • Operating modes include Auto, Cool, Dry, Fan and Heat.
  • Five timer types are available: ON, OFF, WEEKLY, PROGRAM and SLEEP.
  • The weekly timer can be programmed up to four ON/OFF events per day and up to 28 events per week.
  • 10°C HEAT is available from the wireless remote controller.
  • Powerful, Economy, Human Sensor and Outdoor Unit Low Noise functions are available.
  • Wireless remote controller custom codes A, B, C or D can be used where multiple units are installed close together.
10°C HEAT: This function is intended to prevent the room becoming excessively cold while unoccupied. Operation begins when room temperature falls below 10°C and maintains the room at approximately 10°C.

6. Function settings

Function settings can be configured using the wireless remote controller. After changes are completed, the system power must be cycled for the new settings to become active.

FunctionFunction No.Setting values
Filter sign1100 Standard (400 h), 01 Long (1000 h), 02 Short (200 h), 03 No indication (factory)
Room temperature control - cooling3000 Standard (factory), 01 Slightly lower, 02 Lower, 03 Higher
Room temperature control - heating3100 Standard (factory), 01 Lower, 02 Slightly higher, 03 Higher
Auto restart4000 Enable (factory), 01 Disable
Room temperature sensor switching4200 Indoor unit sensor (factory), 01 Both indoor unit and wired controller sensors
Remote controller custom code4400 A (factory), 01 B, 02 C, 03 D
External input control4600 Operation/Stop (factory), 01 Setting change prohibited, 02 Forced Stop
Indoor fan energy saving - cooling4900 Disable (factory), 01 Enable

Entering function setting mode - wireless remote controller

  1. While pressing POWERFUL and SET TEMP. simultaneously, press RESET.
  2. Use the SET TEMP. buttons to select the required function number.
  3. Use the 10°C HEAT button to switch between the left and right digits.
  4. Press POWERFUL to proceed to the setting value.
  5. Select the required setting value using SET TEMP.
  6. Press MODE to confirm the setting and confirm the unit produces a beep.
  7. Press START/STOP and confirm the beep.
  8. Press RESET to exit Function Setting mode.
  9. Turn the system power off.
  10. Wait at least 30 seconds before restoring power.
Important: Function settings do not become active until the power has been turned off and back on. Wait at least 30 seconds after switching the power off before restoring power.

7. External input and output

ConnectorFunctionNotes
CNA01Control inputSelectable as Operation/Stop or Forced Stop using Function 46.
CNB01Operation status outputProvides an air conditioner operating status signal.
CNB02Error status outputProvides an air conditioner error status signal.
External I/O hardware: External functions require the UTY-XCBXZ2 Communication Kit. The UTY-XWZXZ5 External Connect Kit is used for the field connection. The maximum distance from the indoor unit PC board to the connected device is 10 m.

8. Optional controllers and accessories

PartModelNotes
Wired remote controllerUTY-RVNYNRequires UTY-XCBXZ2 Communication Kit.
Wired remote controllerUTY-RNNYNBuilt-in room temperature sensor. Requires UTY-XCBXZ2.
Simple remote controllerUTY-RSNYNProvides basic Start/Stop, fan, temperature and operation mode control. Requires UTY-XCBXZ2.
Communication kitUTY-XCBXZ2Interface used to connect compatible optional controllers and external devices to the indoor unit PC board.
External connect kitUTY-XWZXZ5Used for external input/output connections. The Communication Kit is also required.

9. Quick service notes

  • Indoor and outdoor power supply specification is 240 V ~ 50 Hz.
  • Permitted voltage range is 198-264 V.
  • The indoor PC board current fuse is 250 V 3.15 A.
  • The outdoor main PC board incorporates 250 V 20 A and 250 V 5 A fuses.
  • Compressor discharge temperature protection switches the compressor off at 110°C.
  • The Human Sensor energy-saving function reduces operating capacity when the room is unoccupied and returns to the previous operating mode when occupancy is detected.
  • Outdoor Unit Low Noise mode can reduce outdoor unit operating noise when operating conditions permit.
Technical reference: Design & Technical Manual DTR_AS081E_04 / DTR_AO143E_03 for ASTG09KMCA / ASTG12KMCA and AOTG09KMCA / AOTG12KMCA. For detailed capacity tables, wiring diagrams, dimensional drawings, refrigerant circuit diagrams and sound curves, refer to the complete technical manual.