General Air Conditioning | Technical Support

Remote Controller Function Settings

Operation Mode Exemption / Mode Prohibition
How to hide selected operating modes from the wired remote controller menu
Timing requirement: Complete the entry procedure within 3 minutes of turning on the power to the controller and indoor unit.
Purpose: Operation Mode Exemption removes selected modes from the wired controller's operation menu. It does not disable those modes at the indoor unit itself.

1. Overview

The wired remote controller includes a service-level function that allows selected operating modes to be hidden from the normal user menu. This is useful where the site requires restricted operation, such as cooling-only or heating-only use.



SettingEffect
Mode availableThe mode remains visible and can be selected by the user.
Mode exemptedThe mode is removed from the wired controller's operation-mode menu.
Important: This setting only changes what can be selected from the controller. It does not remove the operating mode from the indoor unit's internal capability.

2. Enter the Remote Controller Function Setting

Step 1 - Turn the power on

Turn on the power supply and begin the following procedure within 3 minutes.

Step 2 - Open the Service screen

From the controller menu, enter the following path:

Menu / Submenu → Service
Step 3 - Enter the hidden function-setting mode

Simultaneously press and hold the following three buttons for 5 seconds:

Screen switch button
(left)
Enter buttonCursor button
(down)
Button-pressure note: The command may not register if the buttons are pressed too firmly. Apply normal, even pressure to all three buttons at the same time.
Step 4 - Open R.C. Function Setting

From the Function Setting screen, select:

R.C. function setting → Operation mode exemption

3. Select the Modes to Exempt

On the Operation Mode Exemption screen, review each mode and select the modes that must be removed from the normal controller menu.

ModeTypical purpose
CoolCooling operation
DryDehumidification operation
FanAir circulation without active heating or cooling
HeatHeating operation
AutoAutomatic heating or cooling selection
To save the setting: Select the required exemption status for each mode, then press OK / Enter to confirm.

4. Dual Remote Controller Systems

Primary and secondary controllers must match: Where two wired controllers are connected, apply the same Operation Mode Exemption settings to both controllers. Settings entered on the primary controller are not automatically transferred to the secondary controller.

5. Final Checks

CheckRequirement
1Return to the normal operation screen.
2Confirm the exempted modes are no longer displayed in the operation-mode menu.
3Operate the system in a mode that has not been exempted.
4Confirm the indoor unit starts, runs, and responds normally.
Memory behaviour: The indoor unit memorises the last operating mode. It is not necessary to overwrite the memorised operating mode after changing the exemption settings.

6. Quick Reference

Menu path
Service → Function setting → R.C. function setting → Operation mode exemption
Hidden-entry button sequence
Screen switch (left) + Enter + Cursor down — hold together for 5 seconds