General Assist Technical Reference

UTD-ECS5A External Control Set

External start/stop, operation status, fan-linked and auxiliary-heater interfaces
Installation manual reference: Part No. 9374983018-02
The UTD-ECS5A is an optional external control wiring set for compatible ducted and concealed indoor units. It provides field connections for remote start/stop, operation indication, fan-linked control and auxiliary electric-heater control.
Confirm the indoor PCB type before connection: The connector numbers differ between Type A and Type B indoor control boards. Connecting a harness to the wrong connector may damage the equipment or cause incorrect operation.

1. Available functions

FunctionHarness colourPurpose
Preparation leadBlackRequired on Type A boards when using the external input/output functions
Start/stop inputWhiteRemote ON/OFF control from a dry contact
Operation-status outputWhiteIndicates whether the indoor unit is operating or stopped
Fan-linked outputGreenControls a field-supplied secondary fan in synchronisation with the indoor fan
Auxiliary-heater outputOrangeControls a field-supplied booster heater on compatible ducted indoor units
The kit does not provide direct BMS communication, temperature adjustment, mode selection or detailed fault-code output. It provides discrete input/output functions only.

2. Indoor PCB types and connector locations

FunctionType A PCBType B PCB
Preparation leadCN106 to CN5Not used
Start/stop inputCN114CN102
Operation-status outputCN115CN103
Fan-linked outputCN14CN6
Auxiliary-heater outputCN15CN10
Page 1 of the manual shows the visual PCB layouts for Type A and Type B. Confirm the physical board layout rather than relying only on the indoor-unit family name.

3. Start/stop input

SpecificationRequirement
Signal typeNo-voltage contact
Contact capacityDC 12 V, 10 mA
Type A connectorCN114
Type B connectorCN102

Type A input selection

On Type A boards, DIP switch SW2-2 selects the input behaviour:

OFF = Edge signal
ON = Pulse signal
Input modeHow it operates
EdgeA change in contact state commands the indoor unit ON or OFF. The external state and remote-controller operation interact as shown in the manual timing chart.
PulseA pulse of at least approximately 200 ms commands ON or OFF operation. The manual shows separate pulse transitions for start and stop.

Type B input operation

Type B uses a continuous ON/OFF dry-contact signal at CN102. The input contact provides remote start/stop control without the Type A edge/pulse selection.
Do not apply voltage to the start/stop input. Use an isolated voltage-free contact. A powered BMS output must operate an interposing relay rather than connect directly to the indoor board.

Typical input applications

BMS relay Card-key relay Occupancy control External timer Remote wall switch

4. Operation-status and fan-linked outputs

Operation-status output

SpecificationRequirement
Output typeNo-voltage contact
Contact capacityMaximum DC 24 V, 10 mA to 1 A or less
Type A connectorCN115
Type B connectorCN103
Indoor unit operatingContact short / closed
Indoor unit stoppedContact open

Fan-linked output

SpecificationRequirement
Output typeDC 12 V output synchronised with indoor-fan operation
Type A connectorCN14
Type B connectorCN6
Indoor fan operatingApproximately 12 V
Indoor fan stopped0 V
Use a field-supplied relay, power supply and fuse suitable for the connected secondary fan or device. The indoor PCB output must not directly carry the external fan motor load.

5. Auxiliary-heater output

Ducted indoor units only: The auxiliary-heater output is intended for compatible ducted systems and must be engineered with appropriate heater safety controls, airflow proving and over-temperature protection.
ItemReference
Type A connectorCN15
Type B connectorCN10
Output when enabledApproximately 12 V
Heater ON conditionRoom temperature approximately 3°C to 10°C below setpoint
Heater OFF conditionRoom temperature approximately 1°C below setpoint
Fan overrun optionCut jumper JM3 to continue indoor-fan operation for approximately 1 minute after heating thermostat-off
The manual requires the external heater to be installed between the indoor unit and the supply ductwork. The one-minute fan-delay control must be used to dissipate residual heater heat.
The auxiliary output is a control signal only. Use a correctly rated field contactor or relay, independent heater supply, fusing, thermal cut-outs and airflow interlocks. Do not connect an electric heater directly to the indoor PCB.

6. Installation procedure

1Isolate all electrical supplies.
Confirm the indoor and outdoor units are safe before opening electrical covers.
2Identify the indoor PCB type.
Match the physical PCB layout to Type A or Type B.
3Install the preparation lead where required.
Type A uses the black CN106-to-CN5 lead; Type B does not.
4Connect only the required harnesses.
Use the correct connector numbers for the identified PCB type.
5Connect the field device.
Extend with suitable field wiring where required and fully insulate every joint.
6Configure Type A input mode.
Set SW2-2 to Edge or Pulse as required.
7Commission each function.
Test start/stop, operation output, fan-linked output and heater output separately.

7. Functional summary

FunctionSupported?
Remote ON/OFF inputYes
Edge input on Type AYes
Pulse input on Type AYes
Continuous input on Type BYes
Operation-status outputYes
Fan-linked outputYes
Auxiliary-heater outputYes, compatible ducted units only
Detailed fault outputNo
Mode or temperature controlNo

8. Compatibility information required

  • Complete indoor-unit model and serial number
  • Photo of the indoor control PCB
  • Confirmation whether the PCB is Type A or Type B
  • Required function: start/stop, status, fan-linked output or auxiliary heater
  • Field-device contact or relay specifications
  • Whether other optional controls or interface boards are already fitted
  • For auxiliary heat: heater capacity, safety controls, airflow proving and electrical design
Terminology: UTD-ECS5A may be described as an External Control Set, external connector kit or I/O harness set. It is not the same product as UTY-XWZX or UTY-XWZXZ5.
Based on Fujitsu General UTD-ECS5A External Control Set Installation Manual, Part No. 9374983018-02. This simplified field reference does not replace the indoor-unit installation manual, electrical design requirements or current model-compatibility information.