UTY-XWZXZ5 External Input / Output Kit

External ON/OFF or Forced Stop input, operation output and error output
Installation manual reference: Part No. 9319446004
The UTY-XWZXZ5 allows a compatible indoor unit to interface with external equipment such as a BMS, timer, occupancy system, card-key switch, automation controller or remote status panel.
Compatibility must be confirmed: This kit is not universal. Confirm the full indoor-unit model number, required communication kit or PCB connection, and the applicable indoor-unit installation manual before installation.

1. Kit contents and wire colours

LeadWire coloursPurpose
External inputOrange / YellowOperation/Stop or Forced Stop input
Operation outputBlue / PurpleRun/stop status output
Error outputRed / WhiteNormal/error status output
Fixing hardwareBinder clamp, binder and screwSecures the accessory wiring inside the indoor unit

2. External input

The Orange and Yellow wires connect to a field-supplied dry contact. The indoor-unit function setting determines whether the input operates as Operation/Stop or Forced Stop.
SpecificationRequirement
Input typeField-supplied no-voltage contact
Required contact rating24 V DC or more, 10 mA or more
Maximum wiring distance10 m from the communication-kit PCB to the connected device
Input wiresOrange and Yellow

Operation/Stop mode

Input signalIndoor-unit response
ONOperation
OFFStop
When started by the external input, the unit resumes the mode, set temperature and airflow settings that were active before the previous stop. These settings must be changed using the normal remote controller.

Forced Stop mode

When the external input is active, the indoor unit is forced to stop and remote-controller operation is invalid. When the forced-stop signal is removed, normal remote-controller operation becomes available again.
Input stateCommandRemote controller
Forced-stop input activeForced stopOperation invalid
Forced-stop input inactiveNormal controlOperation available
Do not apply external voltage directly to the Orange and Yellow wires. Use a field-supplied isolated contact or interposing relay that meets the specified contact rating.

Typical input applications

BMS relay Card-key switch Occupancy relay External timer Fire or shutdown interface

3. External outputs

Operation-status output

SpecificationRequirement
WiresBlue / Purple
Output loadRelay: maximum 24 V DC, 10 mA to less than 500 mA
Maximum wiring distance10 m
Indoor unit operatingOutput ON
Indoor unit stoppedOutput OFF
The operation output indicates only run or stop. It does not provide operating mode, set temperature or airflow information.

Error-status output

SpecificationRequirement
WiresRed / White
Output loadRelay: maximum 24 V DC, 10 mA to less than 500 mA
Maximum wiring distance10 m
Normal conditionOutput OFF
Error conditionOutput ON
Error-output limitation: The output indicates only normal or error status. The actual fault code must be read from the indoor unit, remote controller or applicable service display.

4. Installation procedure

1Isolate all power.
Confirm the indoor and outdoor units are electrically isolated before removing covers.
2Confirm the correct PCB connection.
Refer to the indoor-unit installation manual and communication-kit instructions.
3Connect the required harnesses.
Orange/Yellow for input, Blue/Purple for operation output and Red/White for error output.
4Secure the wiring.
Use the binder clamp and binder so the leads cannot contact sharp edges, moving components or high-voltage wiring.
5Connect the field equipment.
Use suitable interposing relays and insulate all extended joints.
6Set the required input function.
Select Operation/Stop or Forced Stop using the indoor-unit function setting.
7Commission all functions.
Test ON/OFF or Forced Stop, operation status and error status individually.

5. Functional summary

FunctionSupported?
Remote Operation/StopYes
Forced StopYes
Operation-status outputYes
Error-status outputYes
Mode selection by external inputNo
Temperature adjustment by external inputNo
Detailed fault-code outputNo

6. Compatible models supplied for reference

Compatibility should still be confirmed against the current model-specific documentation before installation.
Wall-mounted splitFloor-mounted
ASTH24KMTE-NXTAGTG09KVCA
ASTH30KMTD-NXTAGTG12KVCA
ASTH24KMTEAGTG14KVCA
ASTG22LVCC
ASTG09LVCC
ASTG18LVCC
ASTG12LVCC
ASTG09KMTC-NXT / ASTG09KMTC
ASTG12KMTC-NXT / ASTG12KMTC
ASTH18KMTD / ASTH18KMTD-NXT
ASTH22KMTD / ASTH22KMTD-NXT
ASTH24KMTD / ASTH24KMTD-NXT
ASTH30KMTD / ASTH30KMTD-NXT
ASTH34KMTD / ASTH34KMTD-NXT
ASTG18KMTC / ASTG22KMTC / ASTG24KMTC
ASTG30KMTC / ASTG34KMTC

7. Commissioning checklist

CheckDone
Exact indoor-unit model confirmed compatible
Required communication kit or PCB connection confirmed
Input function set to Operation/Stop or Forced Stop as required
Field input uses an isolated dry contact
All external wiring is 10 m or less
Operation output tested
Error output tested using an approved diagnostic method
Extended joints insulated and wiring securely restrained
The output circuits require a field-supplied DC power supply and relay or interface device. Do not exceed the stated voltage or current limits.
Based on Fujitsu General UTY-XWZXZ5 External Connect Kit Installation Manual, Part No. 9319446004. This simplified reference does not replace the indoor-unit installation manual, communication-kit instructions or current compatibility information.