UTY-XWZX External Input / Output Kit

Dry-contact ON/OFF input and operation-status output
Installation manual reference: Part No. 9317807012
The UTY-XWZX is an external connect kit that allows a compatible indoor unit to receive an external ON/OFF command and provide an external operation-status output.
Compatibility must be confirmed: The kit does not suit every General or Fujitsu General indoor unit. Confirm the exact indoor-unit model and the applicable installation manual before connection.

1. Kit contents

ItemWire colours / purpose
External input leadOrange / Yellow — connects the indoor-unit input to a field-supplied dry-contact device
External output leadBlue / Purple — connects the indoor-unit operation-status output to a field-supplied device
Binder clampSecures the accessory wiring inside the indoor unit
BinderCable restraint
ScrewFixes the binder clamp

2. External control input

The external input provides remote ON/OFF control of the air conditioner using a field-supplied voltage-free contact.
SpecificationRequirement
Signal typeVoltage-free ON/OFF continuous contact
Contact capacityDC 12 V, 10 mA
Input wiresOrange and Yellow
Contact closedAir conditioner operates
Contact openAir conditioner stops

Typical applications

Remote switch External timer BMS dry contact Card-key contact Occupancy control
When started by external input, the air conditioner resumes the operating settings that were active before it stopped. Use the normal remote controller to change mode, temperature or fan speed.

External input operating logic

External contact conditionIndoor-unit responseImportant note
Contact closes and remains closedThe indoor unit receives an ON command and operates using the mode, set temperature and fan settings stored before the previous stop.The input is a continuous maintained contact, not a momentary pulse.
Contact opens and remains openThe indoor unit receives an OFF command and stops.The unit will remain stopped while the contact is open.
Contact is controlled by an external timerThe timer schedule starts and stops the air conditioner by closing and opening the dry contact.Use an isolated relay contact suitable for DC 12 V, 10 mA.
Contact is controlled by a BMS or remote switchThe field device provides the maintained ON/OFF command.Use a true voltage-free relay contact. Do not connect a powered BMS output directly.
Maintained-contact operation: The Orange and Yellow wires must be continuously shorted for ON and continuously open for OFF. A brief pulse will not provide reliable control unless the external device uses a latching relay to maintain the required contact state.

Remote switch wiring concept

Indoor-unit input leadOrange wire → field-supplied dry contact → Yellow wire
Contact closedON / operation command
Contact openOFF / stop command
Field deviceSwitch, timer relay, card-key relay, occupancy relay or BMS interposing relay
Never connect mains voltage, 24 V AC, 24 V DC or any other powered signal directly to the Orange and Yellow wires. The input circuit supplies its own DC 12 V sensing voltage and requires only an isolated dry contact.

Interaction with the normal remote controller

  • The external input controls only whether the unit is commanded ON or OFF.
  • The normal remote controller remains necessary to select cooling, heating, dry or fan mode.
  • The normal remote controller is also required to set temperature, fan speed, louvre position and timer functions.
  • When the external contact starts the unit, it resumes the operating settings stored before the previous stop.
  • Where a site requires the external device to have overriding control, users should be advised that opening the maintained contact will stop the unit.

External input commissioning checks

CheckDone
External device provides a voltage-free maintained contact
No external voltage is present across the field contact
Contact and relay rating is suitable for DC 12 V, 10 mA
Closing the contact starts the indoor unit
Opening the contact stops the indoor unit
Unit resumes the expected previous mode and setpoint
Extended joints are insulated and wiring is mechanically secured

3. External operation-status output

The external output changes state to indicate whether the indoor unit is operating or stopped.
SpecificationRequirement
Output typeVoltage-free contact
Contact ratingMaximum DC 24 V, 10 mA to 1 A or less
Output wiresBlue and Purple
Indoor unit operatingOutput contact short / closed
Indoor unit stoppedOutput contact open
Output limitation: This kit provides only an operation/stop indication. It does not provide operating mode, set temperature, airflow or detailed fault-code information.

Typical output devices

  • Operation indicator lamp
  • BMS digital input
  • Relay or interface module within the stated contact rating
  • Remote status panel

4. Installation procedure

1Isolate all power.
Confirm the indoor and outdoor units are electrically isolated before opening covers or connecting the kit.
2Confirm compatibility and connector location.
Use the indoor-unit installation manual to identify the correct PCB connector and wiring route.
3Connect the required accessory lead.
Use Orange/Yellow for input and Blue/Purple for output.
4Route and secure the wiring.
Install the binder clamp and binder so the wiring cannot contact moving parts, sharp edges or high-voltage components.
5Connect the field-supplied device.
If the lead must be extended, use suitable cable and fully insulate the joint.
6Reassemble and test.
Restore power and verify external ON/OFF control and operation-status output.
Do not apply external voltage to the Orange/Yellow input. It is designed for a voltage-free contact only. Applying voltage can damage the indoor control board.

5. Functional limitations

FunctionSupported?
Remote ON/OFF controlYes
Operation-status outputYes
Select cooling or heating modeNo
Adjust set temperatureNo
Adjust fan speedNo
Detailed fault-code outputNo
Operating-mode feedbackNo

6. Troubleshooting

SymptomChecks
External input does not start the unitConfirm compatibility, PCB connector seating, Orange/Yellow continuity, dry-contact operation and that no external voltage is present.
Unit starts but uses the wrong mode or temperatureThe kit recalls the previous operating settings. Change mode and setpoint using the normal remote controller.
Output does not change stateConfirm Blue/Purple wiring, field-device supply, contact loading and whether the indoor unit is actually in operation rather than standby.
Field relay or indicator is unstableConfirm the device is within the DC 24 V, 10 mA to 1 A rating and add a suitable interface relay where required.

7. Information required for compatibility confirmation

  • Complete indoor-unit model number
  • Complete outdoor-unit model number
  • Indoor-unit serial number
  • Required function: ON/OFF input, status output or both
  • External device type and its electrical contact specification
  • Whether a wired controller, Wi-Fi adaptor or other optional PCB is already installed
  • Photo of the indoor PCB and available accessory connector
Terminology: The UTY-XWZX is commonly described as an external connect kit, external input/output kit or dry-contact interface. The exact compatible connector and mounting method are determined by the indoor-unit model.
Based on Fujitsu General UTY-XWZX External Connect Kit Installation Manual, Part No. 9317807012. This simplified field reference does not replace the indoor-unit installation manual or current compatibility information.


 

WALL MOUNT SPLITCONSOLECASSETTEFLOORDUCTED
ASTA07JCABTA30LBTAUTA30LBLUAGTV09LACARTC90LATU
ASTA09JECABTA36LATAUTA36LCLUAGTV14LACARTC72LATU
ASTA09LFCABTA45LATAUTA45LCLUAGTG09KVCAARTG24LMLC
ASTA12JECABTA54LCTAUTA54LCLUAGTG14KVCAARTG30LHTAC
ASTA12LFCABTG18LVTAAUTG09LVLAAGTG12KVCAARTG36LHTA
ASTA18JCCABTG24LVTCAUTG09LVLB
ARTG45LHTA
ASTA24JCCABTG54LRTAAUTG12LVLA
ARTG30LHTA
ASTA24JFCBABTH54KRTAAUTG12LVLB
ARTG36LHTB
ASTA24LCCABTH54KRTA-3PHAUTG18LVLA
ARTG45LHTB
ASTA24LFCABTH36KRTA-3PHAUTG24LVLC
ARTG45LHTAC
ASTA30JCCABTH36KRTAAUTG54LRLA
ARTG54LHTC
ASTA30JFCABTH18KRTA

ARTG36LHTAC
ASTA30JFCBABTH45KRTA-3PH

ARTG60LHTA
ASTA30LCCABTH45KRTA

ARTG65LHTA
ASTA30LFCABTH30KRTA

ARTH60KHTB
ASTA34JCCABTH24KRTA

ARTH60KHTA-3PH
ASTA34JFC


ARTH54KMTAP
ASTB24LDC


ARTH54KHTA-3PH
ASTB30LDC


ARTH54KHTA-HP
ASTG07JECB


ARTH60KHTA
ASTG07LVCA


ARTH45KHTA-3PH
ASTG09JECA


ARTH54KHTA
ASTG09JECB


ARTH45KHTA-HP
ASTG09LVCA


ARTH36KHTA-HP
ASTG12JECA


ARTH36KHTA-3PH
ASTG12JECB


ARTH36KHTA
ASTG12LVCA


ARTH45KHTA
ASTG12LVCB


ARTH30KHTA-HP
ASTG18LFCA


ARTH30KHTA
ASTG18LVCA


ARTH45KMTAP
ASTG18LVCB


ARTH30KMTAP-HP
ASTG22LVCB


ARTH30KMTAP
ASTG24JFCC


ARTH36KMTAP
ASTG24LFCA


ARTH24KMTAP-HP
ASTG24LFCB


ARTG30LHTDP
ASTG24LFCC


ARTG54LDTA
ASTG24LVCA


ARTG45LHTDP
ASTG30CMTA


ARTG36LHTDP
ASTG30CMTB


ARTG54LHTDP
ASTG30JFCC


ARTG60LDTA
ASTG30KMTA


ARTG45LDTA
ASTG30KMTB


ARTG24LHTDP
ASTG30LFCA


ARTH18KLLAP
ASTG30LFCB


ARTH12KSLAP
ASTG30LFCC


ARTH09KLLAP
ASTG34CMTA


ARTH09KSLAP
ASTG34CMTB


ARTH18KSLAP
ASTG34JFCC


ARTH12KLLAP
ASTG34KMTA


ARTH24KHTA
ASTG34KMTB


ARTH18KMTAP
ASTG34LFCA



ASTG34LFCB



ASTG34LFCC



ASTH18KNTA



ASTH22KNTA



ASTH24KNTA



ASTH07KNCA



ASTH12KNCA



ASTH14KNCA



ASTH09KNCA



ASTH09CNCA



ASTH12CNCA



ASTH18CNTA



ASTH24CNTA



ASTH30CNTA



ASTH30KMTD



ASTH30KNTA



ASTH34CNTA



ASTH34KMTD



ASTH34KNTA



ASTH24KMTE-NXT



ASTH30KMTD-NXT



ASTH24KMTE



ASTG22LVCC



ASTG09LVCC



ASTG18LVCC



ASTG12LVCC



ASTG09KMTC-NXT



ASTG09KMTC



ASTH34KMTD-NXT



ASTH24KMTD-NXT



ASTH22KMTD-NXT



ASTH18KMTD-NXT



ASTG12KMTC-NXT



ASTG12KMTC



ASTH24KMTD



ASTH34KMTD



ASTH30KMTD



ASTH18KMTD



ASTH22KMTD



ASTG24KMTC



ASTG22KMTC



ASTG18KMTC



ASTG34KMTC



ASTG30KMTC