VR-II Refrigerant Charge Calculator

This article explains how to calculate the total refrigerant charge for a VR-II system using up to three outdoor units.

Quick Answer
  • Total refrigerant charge = A + B + C
  • A = Total factory charge of all connected outdoor units
  • B = Total additional charge for the selected outdoor units
  • C = Additional refrigerant for liquid-line pipe length
  • 1/4 in. pipe: 0.021 kg/m
  • 3/8 in. pipe: 0.058 kg/m
  • 1/2 in. pipe: 0.114 kg/m
  • 5/8 in. pipe: 0.178 kg/m
  • 3/4 in. pipe: 0.268 kg/m

Calculation Structure

SectionDescription
ACombined factory refrigerant charge for Outdoor 1 (Master), Outdoor 2 (Slave 1) and Outdoor 3 (Slave 2), where applicable
BCombined additional charge for the selected outdoor units
CAdditional refrigerant calculated from the total liquid-line pipe lengths
Formula
Total Refrigerant Charge (kg) = A + B + C

Step 1 - Select the Outdoor Units

Select the applicable outdoor unit models in the calculator:

  • Outdoor 1 - Master
  • Outdoor 2 - Slave 1, where fitted
  • Outdoor 3 - Slave 2, where fitted

The calculator provides the factory charge and any additional outdoor-unit charge for each selected unit.

Step 2 - Calculate Section A

A = Outdoor 1 Factory Charge + Outdoor 2 Factory Charge + Outdoor 3 Factory Charge

If only one or two outdoor units are installed, unused outdoor unit positions remain at zero.

Step 3 - Calculate Section B

B = Outdoor 1 Additional Charge + Outdoor 2 Additional Charge + Outdoor 3 Additional Charge

Step 4 - Enter Liquid-Line Pipe Lengths

Enter the total applicable liquid-line pipe length in metres for each pipe size.

Pipe SizeAdditional Charge RateCalculation
1/4 in.0.021 kg/mLength (m) x 0.021
3/8 in.0.058 kg/mLength (m) x 0.058
1/2 in.0.114 kg/mLength (m) x 0.114
5/8 in.0.178 kg/mLength (m) x 0.178
3/4 in.0.268 kg/mLength (m) x 0.268

Add the calculated charge for all pipe sizes together. This becomes Section C.

Example Shown in the Calculator

The screenshot shows the following entered pipe lengths:

Pipe SizeLengthCalculated Charge
1/4 in.48 m1.008 kg
3/8 in.26 m1.508 kg
1/2 in.40 m4.560 kg
5/8 in.0 m0 kg
3/4 in.0 m0 kg

Total additional pipe charge (C):
1.008 + 1.508 + 4.560 = 7.076 kg

The calculator displays this rounded as 7.08 kg.

Maximum System Charge

Outdoor Unit ConfigurationMaximum System Charge
1 Outdoor Unit35 kg
2 Outdoor Units70 kg
3 Outdoor Units105 kg
Maximum charge check: The final A + B + C quantity must not exceed the maximum permitted refrigerant charge for the number of connected outdoor units.

Technician Checklist

  1. Select the correct Master and Slave outdoor unit models.
  2. Confirm the factory charge for each outdoor unit.
  3. Add the factory charges to calculate Section A.
  4. Add any outdoor-unit additional charges to calculate Section B.
  5. Measure the applicable 1/4, 3/8, 1/2, 5/8 and 3/4 in. liquid-line lengths.
  6. Calculate the charge for each pipe size and add them together to calculate Section C.
  7. Calculate the total system charge using A + B + C.
  8. Confirm the final charge is below the applicable maximum system charge.
  9. Record the final refrigerant charge on the commissioning documentation.
Source: VR-II Refrigerant Charge Calculator supplied in the service reference material.