General Assist Technical Reference

Zone Controller Installation Guide

UTY-CDPXZC and UTY-CDPXZD
Simplified installation, wiring, commissioning and fault-reference guide for authorised service personnel
Authorised personnel only: Installation and electrical work must be completed by appropriately qualified personnel in accordance with national and local wiring rules. Isolate all power before opening the unit or commencing wiring.
Critical voltage warning: UTY-CDPXZC uses 24 V AC dampers. UTY-CDPXZD uses 240 V AC dampers. Connecting 240 V to the 24 V damper circuit will damage the dampers and may create a fire risk.

1. UTY-CDPXZC vs UTY-CDPXZD

ItemUTY-CDPXZCUTY-CDPXZD
Damper voltage24 V AC240 V AC
Damper power supplyExternal transformer requiredSupplied from the 240 V interface circuit
Damper connectionRJ12, 6-pin plug
1-2 OPEN / 3-4 COMMON / 5-6 CLOSE
Hard-wired terminal block
OPEN / COM / CLOSE
Maximum current per damper360 mA or less70 mA or less
Maximum power per damper7 VA or less12 VA or less
Maximum zones8 zones8 zones
Common to both models: 240 V interface power, up to 8 zones, up to 2 wired remote controllers, up to 2 optional remote sensors, connection to the indoor unit through CN6, and zone commissioning through the wired remote controller.

2. Electrical requirements

Cable / itemRequirement
240 V / 24 V power cable0.75 mm2, Type 60227 IEC52 or IEC53, 2 conductors plus earth
Remote controller cable0.33 mm2 / 22 AWG, polar 3-core shielded cable
UTY-CDPXZC damper cable0.48 mm2 or larger, RJ12 6-pole / 6-core
UTY-CDPXZD damper cable0.75 mm2, Type 60227 IEC52 or IEC53
Interface breaker1.0 A interface load, plus the total connected damper load where applicable
UTY-CDPXZC transformerSelect transformer capacity to suit the combined 24 V AC damper load
Never: connect power wiring to remote-controller terminals, bundle power and communication wiring together, omit protective earth, or energise the interface before wiring and covers are complete.

3. Installation sequence

1Confirm compatibility.
Install only on an indoor unit approved for the zone-control interface. Applicable examples in the manual include ART 36, ART 45/54/60 and ART 72/90 families.
2Select the mounting location.
Provide adequate support, service clearance and ventilation. Do not install in high salt, oil, steam, corrosive gas, flammable gas or high-temperature areas.
3Connect the indoor-unit interface cable.
At the indoor unit, connect the supplied zone-interface cable in place of the normal remote-controller cable. Terminal colours are Red / White / Black.
4Mount the interface.
Remove the cover, align the approved mounting holes and secure with the supplied M4 x 12 mm screws. Do not drill the indoor unit to force installation.
5Complete all electrical connections.
Connect CN6, remote controller, dampers, power supply and any optional remote sensors. Secure all cables with the supplied cable ties.
6Close and seal.
Refit the cover, install one-touch bushes in unused cable holes and seal remaining openings with putty to prevent insect entry.

Required service clearance

Indoor unit familyMinimum side clearanceAttic service space
ART 3635 mm or more450 mm or more
ART 45 / 54 / 6035 mm or more500 mm or more
ART 72 / 9035 mm or more450 mm or more

4. Wiring reference

Indoor unit connection

Indoor unit to zone interface: connect the supplied interface cable to CN6 on the main PCB. Secure the cable so no mechanical load is transferred to the connector.

Remote controller

TerminalWire colour
1Red
2White
3Black
Up to two wired remote controllers can be connected. When two controllers are used, connect through a locally supplied junction box.

UTY-CDPXZC damper wiring - 24 V AC

RJ12 pinsFunction
1 and 2OPEN
3 and 4COMMON
5 and 6CLOSE
UTY-CDPXZC requires a correctly sized 24 V AC transformer. Size the transformer for the total connected damper VA. Do not connect the 240 V supply directly to the 24 V damper terminal.

UTY-CDPXZD damper wiring - 240 V AC

Connect each zone to the correctly marked terminals:
OPENCOMCLOSE
Incorrectly interchanging OPEN, COM and CLOSE may damage the zone-interface PCB.

Optional remote sensors

ConnectorSensor
CN7 - WhiteRemote sensor 1 / primary
CN8 - BlackRemote sensor 2 / secondary

Terminal preparation and tightening

ItemRequirement
Power cable strip length30 mm outer preparation; earth 40 mm or longer
Remote-controller cable30 mm outer preparation; functional earth 50 mm or longer
Damper cable25 mm outer preparation
M3.5 terminal screw1.0-1.6 N.m
M4 terminal screw1.2-1.8 N.m

5. Commissioning and test run

1Confirm installation of the wired remote controller and indoor unit.
2Turn on the indoor unit first, then the zone-control interface. For UTY-CDPXZC, also energise the damper transformer.
3Complete remote-controller Initial Setting, including number of outlets and damper type.
4Set date and time, then complete all required indoor-unit Function Settings.
5Power-cycle the zone interface and indoor unit after function settings are complete.
6Complete Zone Initial Setting when remote sensors are fitted or other zone adjustments are required.
7Power-cycle again after Zone Initial Setting.
8Run the indoor unit and confirm each zone number matches the physical location.
9Verify each damper opens and closes correctly and airflow reaches the intended zone.

Commissioning checklist

Check itemDone
Number of outlets configured for every zone[ ]
Damper type correctly selected[ ]
Room-temperature sensor function setting completed where applicable[ ]
Indoor unit test run completed[ ]
Zone numbers match physical room locations[ ]
Every damper proven open and closed[ ]
Airflow confirmed in every selected zone[ ]
Customer shown correct operation[ ]

6. LED diagnosis

Normal operation: Green LED D40 continuously lit and Red LED D41 off.
Green D40Red D41DescriptionCode
Lit1 flashEEPROM access errorEr J5.1
Lit2 flashesIndoor unit data acquisition errorEr J5.2
Lit3 flashesCommunication error between indoor unit and zone interfaceEr J5.3
Lit4 flashesCommunication error between zone interface and remote controllerEr J5.4
Lit5 flashesOptional remote sensor 1 errorEr J5.5
Lit6 flashesOptional remote sensor 2 errorEr J5.6
Lit7 flashesController type errorEr J5.7

7. Common installation mistakes

MistakeLikely result
240 V connected to UTY-CDPXZC damper circuitDamper damage and potential fire risk
OPEN / COM / CLOSE incorrectly wiredIncorrect damper operation or PCB damage
Number of outlets not programmedZone not displayed and incorrect automatic fan control
Damper type not selectedDamper operation may not start correctly
Power and communication cables bundled togetherElectrical interference and control malfunction
Unused cable holes left openInsect entry and possible PCB failure
System not power-cycled after settingsNew settings may not initialise correctly
Final verification: Record the number of outlets, damper type, zone locations and remote-sensor locations. Leave the operating and installation documentation with the customer.
Source manual: Fujitsu General Zone Control Interface Installation Manual, Part No. 9380222064, UTY-CDPXZC / UTY-CDPXZD. This article is a simplified field reference and does not replace the complete installation manual or local electrical requirements.