UTY-CDPXZC / UTY-CDPXZD
Zone Control Interface – Error Codes and LED Indications
The Zone Control Interface monitors communication between the indoor unit, wired remote controller and optional sensors. When a fault occurs, the interface Main PCB and the wired remote controller provide corresponding error indications.
1. Display locations
| Location | Indicator | Function |
|---|---|---|
| Zone Control Interface Main PCB | Green LED D40 | Power / operation indication |
| Zone Control Interface Main PCB | Red LED D41 | Error indication. Flash count identifies the fault type. |
| Wired Remote Controller | Display | Displays the corresponding J5 error code, for example Er J5,3. |
2. Normal operating display
| Condition | Green LED D40 | Red LED D41 | Meaning |
|---|---|---|---|
| Normal operation | Lit | Unlit | Zone Control Interface is operating correctly. |
3. Error display and codes
| Error contents | Main PCB LED indication | Wired remote display | Reference |
|---|---|---|---|
| EEPROM Access Error | Green lit / Red flashes 1 time | Er J5,1 | 1 |
| Indoor Unit Data Acquisition Error | Green lit / Red flashes 2 times | Er J5,2 | 2 |
| Communication Error – Indoor Unit ↔ Zone Control Interface | Green lit / Red flashes 3 times | Er J5,3 | 3 |
| Communication Error – Zone Control Interface ↔ Wired Remote Controller | Green lit / Red flashes 4 times | Er J5,4 | 4 |
| Optional Remote Sensor 1 Error | Green lit / Red flashes 5 times | Er J5,5 | 5 |
| Optional Remote Sensor 2 Error | Green lit / Red flashes 6 times | Er J5,6 | 6 |
| Controller Type Error | Green lit / Red flashes 7 times | Er J5,7 | 7 |
LED identification: Count the flashes of the red D41 LED between pauses. The green D40 LED remains lit during the listed J5 fault indications.
4. Troubleshooting checks
- Error reset: After rectifying the issue, cycle power to clear the error display.
- Communication cable: Verify wiring between the indoor unit, interface board and wired remote controller. Confirm connections and polarity are correct.
- Sensor errors: Check optional sensor connections and confirm unused sensor terminals are treated in accordance with the installation instructions.
- Controller type error: Confirm the correct Zone Control Interface model and compatible controller configuration are being used.
Service safety: Isolate power before opening the Zone Control Interface or checking wiring. Electrical testing and internal service work should only be carried out by appropriately qualified personnel.
5. Reference images
The following existing Freshdesk-hosted images are retained as technical references.

Models: UTY-CDPXZC / UTY-CDPXZD