General Assist Technical Reference
AOT30LMAW4 Pressure Switch Values
Pressure Switch A and Pressure Switch B operating thresholds
Use the following pressure switch values when diagnosing the AOT30LMAW4 outdoor unit. The switch opens at the stated high-pressure threshold and returns to normal operation once the pressure falls to the reset threshold.
Pressure switch specifications
| Pressure Switch | Part Number | Circuit Turns OFF | Returns to Normal Operation |
|---|---|---|---|
| Pressure Switch A Assy | 9367726028 | 4.2 MP or more | 3.2 MP or less |
| Pressure Switch B Assy | 9367727025 | 3.7 MP or more | 2.9 MP or less |
How the switches operate
Important: The pressure unit is shown as MP in the supplied technical reference. The values above have been reproduced as provided.
Technical reference for AOT30LMAW4 pressure switch operating values.