AIRSTAGE Technical Reference

Low Noise Mode and Peak Cut Mode

External input wiring, function settings and verification
Outdoor unit PCB configuration using CN131 and the UTY-XWZXZ2 external connector kit
Overview: Low Noise Mode reduces outdoor unit operating sound by limiting compressor and fan speed. Peak Cut Mode limits power draw and compressor capacity. Depending on the application, these functions can be controlled by an external input through CN131 or configured directly from the outdoor unit PCB.
Qualified personnel only: Isolate power before accessing the outdoor unit PCB. Confirm connector location, wiring polarity, insulation and applicable model documentation before energising the system.

1. Functions and required component

External Connector Kit: UTY-XWZXZ2
Includes red, white and black lead wires for connection to CN131.
FunctionPurposeExternal input operation
Low Noise ModeReduces compressor and fan speed to minimise operating noise.ON: Low noise operation
OFF: Normal operation
Peak Cut ModeLimits power draw and compressor capacity.ON: Output limited to the configured level
OFF: Normal compressor operation
Low Noise Mode performance depends on outdoor temperature and fan control logic. Activating Low Noise and Peak Cut together may significantly reduce available capacity.

2. External input connection - CN131

ConnectorCN131 on the outdoor unit PCB
Input voltageDC 5-24 V, 100 mA maximum load
Maximum wiring distance10 m from the outdoor unit PCB
Switch or relay contactToggle switch, rocker switch or relay contact suitable for 10 mA DC

Lead wire identification

LeadConnection
Red+V, 5-24 V DC
WhiteSignal / switch input
BlackGND

Typical resistor selection

Supply voltageTypical resistor for approximately 10 mA
5 V DC470 ohm
12 V DC1 kohm
24 V DC2.2 kohm

3. External output options

Additional outdoor unit signals may be available for monitoring:

OutputConnectorOperation
Error statusCN136ON during a fault condition
Compressor statusCN136ON while the compressor is operating
Base heaterCN115Active when outdoor temperature is 2 degrees C or below
External outputs are open-collector DC signals rated at 24 V maximum and 20 mA.

4. Outdoor unit function settings

Access procedure

  1. Power the outdoor unit and leave the system in standby.
  2. Press MODE/EXIT once.
  3. Press SELECT until F2 appears on LED104.
  4. Press ENTER to enter Function Setting Mode.
  5. Use SELECT to choose the required setting item.
  6. Press ENTER to confirm and store the setting.
ItemCodeFactory defaultOptions
Peak Cut Mode - energy-saving level3002 - Level 3 / 75%00: Stop
01: 50%
02: 75%
03: 100%
Low Noise Mode - operation setting4100 - Normal00: Normal
01: Low Noise Mode
Low Noise Mode - operation level4200 - Level 100: Level 1
01: Level 2

Setting examples

Enable Low Noise Mode
Function item 41 - Setting 01
The outdoor unit reduces fan and compressor speed to minimise noise.
Limit compressor output to approximately 50%
Function item 30 - Setting 01

5. Installation and functional verification

Typical installation sequence

  1. Install the UTY-XWZXZ2 harness onto CN131.
  2. Connect the external switch or BMS control relay.
  3. Confirm wiring polarity, resistor selection and insulation.
  4. Toggle the input and confirm the expected fan speed, sound or power response.
  5. Store the final PCB configuration using the ENTER button.

Verification

  • Low Noise Mode: The outdoor unit sound level should reduce after approximately 1-2 minutes, subject to operating conditions.
  • Peak Cut Mode: Compressor current should reduce in line with the configured output level.
  • Confirm operation using service LED indications or current measurement where applicable.

Field guidance

  • Avoid enabling Low Noise and Peak Cut simultaneously unless the site requirement justifies the combined capacity limitation.
  • After testing, restore the required final setting. Do not leave an unintended capacity restriction active.
  • For longer signal cable runs, use appropriately screened cable and route it away from sources of electrical interference.

6. Reference diagrams

The following diagrams are retained from the source article and use Freshdesk-hosted attachment URLs.

Low Noise and Peak Cut reference diagram 1
Low Noise and Peak Cut reference diagram 2
Low Noise and Peak Cut reference diagram 3
Low Noise and Peak Cut reference diagram 4
Low Noise and Peak Cut reference diagram 5
Low Noise and Peak Cut reference diagram 6
Low Noise and Peak Cut reference diagram 7
Low Noise and Peak Cut reference diagram 8
Low Noise and Peak Cut reference diagram 9
Low Noise and Peak Cut reference diagram 10