Technical Configuration Guide
Wired Remote Controller PCB Configuration
2-wire and 3-wire controller settings using the DIP switch and JM9 jumper
Purpose: To ensure correct communication between the indoor unit and the connected wired remote controller, configure the indoor unit main PCB to match the controller type being used.
Electrical safety: Isolate power to the indoor unit before opening the electrical cover or changing the DIP switch or JM9 jumper position.
1. Function setting table
| Connected remote controller | DIP switch position | JM9 jumper | Factory setting |
|---|---|---|---|
| 2-wire type wired remote controller | 2WIRE | Disconnected Leave JM9 open | No |
| 3-wire type wired remote controller | 3WIRE | Connected JM9 shorted | Factory default |
Important: The DIP switch and JM9 jumper must both match the connected controller type. Changing only one setting may prevent communication.
2. Setting procedure
- Isolate power.
Ensure the indoor unit is completely powered off before making any changes. - Access the main PCB.
Open the electrical cover and locate the indoor unit main PCB. - Locate the settings.
- DIP switch: Marked 2WIRE / 3WIRE.
- Jumper: Marked JM9.
- Configure the PCB for the connected controller.
| Controller type | Required actions |
|---|---|
| 2-wire controller |
|
| 3-wire controller |
|
- Confirm both settings.
Verify that the DIP switch and JM9 positions match the connected controller type. - Restore power and test.
Reconnect power and confirm normal communication with the wired remote controller.
3. Component location
The 2WIRE / 3WIRE DIP switch and JM9 jumper are located on the indoor unit main PCB.
If communication is not established: Isolate power again and recheck the controller wiring, DIP switch position and JM9 jumper setting before further diagnosis.