Low Noise and Peak Cut Functions
1. Purpose
The Low Noise and Peak Cut functions enable service technicians and installers to adjust outdoor unit operation based on site requirements:
- Low Noise Mode: Reduces compressor and fan speed to lower operating sound levels.
- Peak Cut Mode: Limits compressor current draw to reduce power consumption during high-demand periods.
These functions are controlled either externally (via a switch or timer input) or locally (through the control PCB settings).
2. External Input & Output Overview
| Connector | Input | Output | Function | Remarks |
|---|---|---|---|---|
| CN10 | Low Noise Mode | — | Enables Low Noise operation via contact input | Requires external switch / timer |
| CN11 | Peak Cut Mode | — | Limits compressor current via contact input | Requires external switch / timer |
| CN12 | — | Error Status | Outputs fault signal | DC 24 V max, 500 mA |
| CN13 | — | Compressor Status | Outputs compressor run status | DC 24 V max, 500 mA |
Optional Part:
External Connect Kit – UTY-XWZXZ3
3. External Input Wiring
Purpose:
Allows control of Low Noise and Peak Cut via external signal or timer.
Connector Location: Outdoor unit control PCB (CN10/CN11)
Signal Type: Dry contact (ON/OFF)
Contact Capacity: DC 24 V or more, 10 mA minimum
Maximum Cable Length: 10 meters
Circuit Example (Low Noise or Peak Cut):
- Connect a commercial timer or switch between the signal and ground terminal.
- When the contact closes → the respective mode activates.
- When the contact opens → unit returns to normal operation.
| Input Signal | Operating Mode |
|---|---|
| ON | Function active |
| OFF | Normal operation |
4. External Output Wiring
Purpose:
Provides external monitoring signals for Error Status and Compressor Operation.
Circuit Specification:
- Voltage: DC 24 V or less
- Load Current: DC 500 mA or less
- Max Cable Distance: 10 meters
Use the same UTY-XWZXZ3 harness kit for connection.
5. Local Function Setting Procedure
The Low Noise and Peak Cut levels can be set directly on the outdoor control PCB.
Switch and LED Layout
| Switch | Function |
|---|---|
| SW1 | MODE – Access Local Setting / Error Display |
| SW2 | SELECT – Navigate setting items |
| SW3 | ENTER – Confirm setting |
| SW4 | EXIT – Return to normal operation |
| SW5 | PUMP DOWN – Starts pump down operation |
LED Indicators:
- L1: Pump Down
- L2/L3: Low Noise Mode
- L4/L5/L6: Peak Cut Mode
6. Low Noise Mode Setting Procedure
- Press SW1 (MODE) for 3 seconds → “Local Setting Mode” activates.
- Confirm POWER/MODE LED blinks 9 times.
- Press SW3 (ENTER) once.
- Use SW2 (SELECT)to adjust Low Noise level:
- MODE 1 (L2 blink) → Standard reduction
- MODE 2 (L3 blink) → Enhanced reduction
- Press SW3 (ENTER) to save.
- Press SW4 (EXIT) to return to normal operation.
| Mode | Effect |
|---|---|
| 1 | Fan and compressor speed reduction (approx. -3 dB) |
| 2 | Further reduction, increased sound attenuation |
7. Peak Cut Mode Setting Procedure
- Press SW1 (MODE) for 3 seconds to enter Local Setting.
- Confirm POWER/MODE LED blinks 9 times.
- Press SW3 (ENTER).
- Use SW2 (SELECT)to adjust power limit:
- L4/L5/L6 Pattern defines limit level.
- Press SW3 (ENTER) to store setting.
- Press SW4 (EXIT) to return to Normal Operation.
| LED Pattern (L4-L6) | Power Input Limit |
|---|---|
| ● ○ ○ | 0 % (Stop) |
| ○ ● ○ | 50 % |
| ○ ○ ● | 75 % |
| ● ● ● | 100 % (Normal) |
8. Verification
After configuration:
- Low Noise LED (L2/L3) indicates active noise reduction.
- Peak Cut LED (L4–L6) pattern shows the active limitation level.
- Verify the change in compressor current and sound level during operation.
9. Service Notes
- Always stop the air conditioner before entering local setting mode.
- Discharge static electricity before touching the control PCB.
- Do not adjust while the unit is running.
- Ensure wiring insulation and correct polarity when using external contacts.
- For combined control (BMS or timer integration), use isolated dry contacts.
10. Summary
| Function | Control Type | Adjustment Range | Connector | Accessory |
|---|---|---|---|---|
| Low Noise Mode | External or Local | Mode 1 / Mode 2 | CN10 | UTY-XWZXZ3 |
| Peak Cut Mode | External or Local | 0–100 % Power Limit | CN11 | UTY-XWZXZ3 |
| Error Output | Output | ON = Fault | CN12 | UTY-XWZXZ3 |
| Compressor Output | Output | ON = Running | CN13 | UTY-XWZXZ3 |