General Assist Technical Reference

AIRSTAGE VR-II Series VRF

System introduction and compatible indoor-unit lineup
Legacy R410A heat-recovery VRF platform
The AIRSTAGE VR-II Series is a large-capacity R410A VRF platform designed for commercial buildings requiring simultaneous heating and cooling, extensive zoning, centralised control and flexible refrigerant piping.
Generation warning: VR-II is not the same as V-II, V-III, VR-III or later VR-IV systems. Always confirm the complete outdoor and indoor model number before selecting parts, controllers, PCBs, branch units or commissioning procedures.

1. Key technical highlights

FeatureTypical VR-II Series reference
RefrigerantR410A
System typeHeat-recovery VRF with simultaneous cooling and heating, model dependent
Compressor technologyDC inverter compressor control with staged and rotational operation on applicable combinations
Outdoor capacityApproximately 22 kW upward, with modular combinations exceeding 150 kW on applicable systems
Indoor-unit connectionsUp to approximately 48 indoor units, depending on outdoor combination
Piping flexibilityLong total pipe lengths and substantial vertical separation, subject to system design limits
ControlsWired controllers, central controllers, touch panels and BMS interfaces
Product statusLegacy / retired platform in many markets; parts availability must be confirmed
Maximum system capacity, indoor-unit count, piping length and height difference vary by exact outdoor combination. Do not apply headline maximums without checking the relevant design and installation manual.

2. Indoor-unit lineup

The supplied two-page lineup shows indoor units from approximately 2.2 kW to 28.0 kW cooling capacity, covering cassette, ducted, floor, ceiling and wall-mounted configurations.

Cassette indoor units

TypeModels shownCooling rangeAccessory
Compact cassetteAUXB07GALH, AUXB09GALH, AUXB12GALH, AUXB14GALH, AUXB18GALH, AUXB24GALH2.2–7.1 kWUTG-UFYC-W grille
CassetteAUXD18GALH, AUXD24GALH, AUXA18GALH, AUXA24GALH, AUXA30GALH, AUXA34GALH, AUXA36GALH, AUXA45GALH, AUXA54GALH5.6–14.0 kWUTG-UGYA-W grille
Circular-flow cassetteAUXM18GLAH, AUXM24GLAH, AUXM30GLAH, AUXK18GLAH, AUXK24GLAH, AUXK30GLAH, AUXK34GLAH, AUXK36GLAH, AUXK45GLAH, AUXK54GLAH5.6–14.0 kWUTG-UKYC-W grille

Ducted and concealed indoor units

TypeModels shownCooling range
Low-static / concealed floorARXB07GALH, ARXB09GALH, ARXB12GALH, ARXB14GALH, ARXB18GALH2.2–5.6 kW
Mini duct with drain pumpARXK07GCLH, ARXK09GCLH, ARXK12GCLH, ARXK14GCLH, ARXK18GCLH, ARXK24GCLH2.2–7.1 kW
Mini duct without drain pumpARXK07GALH, ARXK09GALH, ARXK12GALH, ARXK14GALH, ARXK18GALH, ARXK24GALH2.2–7.1 kW
Slim duct / slim concealed floorARXD07GALH, ARXD09GALH, ARXD12GALH, ARXD14GALH, ARXD18GALH, ARXD24GALH2.2–7.1 kW
Low-static pressure ductARXB24GALH, ARXB30GALH, ARXB36GALH, ARXB45GALH7.1–12.5 kW
Medium-static pressure ductARXA24GALH, ARXA30GALH, ARXA36GALH, ARXA45GALH, ARXA24GBLH, ARXA30GBLH, ARXA36GBLH, ARXA45GBLH7.1–12.5 kW
High-static pressure ductARXC36GBTH, ARXC36GATH, ARXC45GATH, ARXC60GATH, ARXC72GATH, ARXC90GATH, ARXC96GATH11.2–28.0 kW

Floor, ceiling and wall-mounted indoor units

TypeModels shownCooling rangeNotes
Floor / ceilingABYA12GATH, ABYA14GATH, ABYA18GATH, ABYA24GATH3.6–7.1 kWConvertible installation
CeilingABYA30GATH, ABYA36GATH, ABYA45GATH, ABYA54GATH9.0–14.0 kWCeiling-suspended type
Compact floorAGYA07GCAH, AGYA09GCAH, AGYA12GCAH, AGYA14GCAH2.2–4.0 kWInternal EEV
Compact floor with external EEVAGYE07GCAH, AGYE09GCAH, AGYE12GCAH, AGYE14GCAH2.2–4.0 kWUTR-EV09XB or UTR-EV14XB required
Wall mountedASYA07GACH, ASYA09GACH, ASYA12GACH, ASYA14GACH, ASYA18GACH, ASYA24GACH, ASYA30GACH, ASYA07GTAH, ASYA09GTAH, ASYA12GCAH, ASYA14GCAH, ASYA18GBCH, ASYA24GBCH, ASYA30GTAH, ASYA34GTAH2.2–10.0 kWMultiple chassis and suffix variants
Wall mounted with external EEVASYE07GACH, ASYE09GACH, ASYE12GACH, ASYE14GACH, ASYE07GTAH, ASYE09GTAH, ASYE12GCAH, ASYE14GCAH2.2–4.5 kWExternal EEV kit required

Accessory references

ApplicationAccessory
Compact cassette AUXBUTG-UFYC-W cassette grille
Cassette AUXD / AUXAUTG-UGYA-W cassette grille
Circular-flow cassette AUXM / AUXKUTG-UKYC-W cassette grille
07 / 09 external EEV indoor unitsUTR-EV09XB
12 / 14 external EEV indoor unitsUTR-EV14XB

3. Service and replacement guidance

1Confirm the exact VR generation.
VR-II branch units, outdoor PCBs, indoor PCBs, controllers and addressing procedures must not be assumed interchangeable with V-II, V-III, VR-III or later products.
2Match the full model suffix.
Suffixes such as GALH, GBLH, GATH, GBTH, GACH, GTAH and GBCH identify different assemblies and must be matched exactly.
3Readdress replacement PCBs.
Transfer DIP-switch settings exactly and complete the required address setting, refrigerant-system setup and capacity check after replacing a control PCB.
4Confirm parts availability.
The platform is retired in many markets. Verify stock, supersession and compatibility before committing to repair.
5Assess replacement carefully.
Existing R410A piping, branch units and controls require engineering assessment before reuse with a newer VRF platform.
Escalation information: Provide all outdoor, branch and indoor model numbers; serial numbers; refrigerant-system address; indoor addresses; controller type; fault codes; LED status; PCB part numbers; and details of any recent component replacement.
Do not mix generations: Similar plugs, address switches or controller terminals do not establish compatibility. Use the VR-II design, installation and service documentation for every repair or replacement decision.
This article is a practical overview based on the supplied VR-II Series indoor-unit lineup. It does not replace the applicable design, installation, service or commissioning manuals. Maximum system values vary by outdoor model, branch-unit arrangement and design conditions.