General Assist Technical Reference

VR-II Outdoor Unit Field Settings & Monitor Mode

Outdoor PCB test run, F1 monitor values, F2 field settings, F3 functions and F9 error history
For VR-II systems using the outdoor unit PCB 7-segment display and SW107 / SW108 / SW109 push buttons
This article provides a field reference for accessing and using the outdoor unit PCB monitor and setting modes. The source document covers test operation from the outdoor PCB, live operating data, field configuration, maintenance functions and stored error history.
Qualified service personnel only: These settings can alter system operation. Record existing settings before making changes. Do not change a field setting unless the application and intended effect are understood.

1. Outdoor PCB controls

ControlFunction
SW107 - MODE / EXITMoves from monitoring to mode selection, or exits back toward the normal monitoring display.
SW108 - SELECTScrolls through modes, item codes and selectable values.
SW109 - ENTEREnters the selected mode or confirms an item. Some functions require ENTER to be held for at least 3 seconds.
LED105 / LED1047-segment display used for mode, item and value indication.
LED101 / LED102Power mode / error status indicators shown on the outdoor PCB.

2. Test run from the outdoor PCB

Important: All indoor units connected to the outdoor unit can be test-operated by the push-button setting. The source specifies this function is for the master outdoor unit only.
  1. From the normal monitoring display, press MODE / EXIT (SW107) once.
  2. Press SELECT (SW108) until F3 Function Mode is displayed.
  3. Press ENTER (SW109).
  4. Use SELECT to choose the required function:
    00 Cooling test run  |  01 Heating test run  |  02 Test run stop  |  91 Central control forced release.
  5. Hold ENTER (SW109) for at least 3 seconds.
  6. After pursuit completion is shown, press ENTER or allow the display to time out after approximately 5 seconds.
  7. Press MODE / EXIT to return to the normal monitoring display.

3. F1 - Monitor mode

F1 provides live operating information without changing the system configuration.

ItemMonitor itemDisplayed information
00Connected number of outdoor unitsNumber of communicating outdoor units.
01Outdoor unit software versionOutdoor control software version.
02INV PCB software versionInverter PCB software version.
03Communication PCB software versionCommunication PCB software version.
10Outdoor fan motor speedRotational speed in rpm.
11INV compressor speedRotational speed in rps.
12INV compressor currentCurrent in A.
13Constant-speed compressor currentCurrent in A.
14EEV1 pulseEEV1 pulse position.
15EEV2 pulseEEV2 pulse position.
20Accumulated current timeAccumulated time, x10 hours.
21INV compressor accumulated time - CoolingCooling accumulated time, x10 hours.
22INV compressor accumulated time - HeatingHeating accumulated time, x10 hours.
23Constant-speed compressor accumulated timeAccumulated time, x10 hours.

Refrigerant cycle temperatures

ItemMeasurement
30Thermistor 1 - INV compressor discharge temperature
31Thermistor 2 - Constant-speed compressor discharge temperature
32Thermistor 3 - Outdoor temperature
33Thermistor 4 - Suction temperature
34Thermistor 5 - Heat-exchanger temperature
35Thermistor 6 - Liquid temperature 1
36Thermistor 7 - Liquid temperature 2
37Thermistor 8 - Sub-cool heat-exchanger inlet temperature
38Thermistor 9 - Sub-cool heat-exchanger outlet temperature
39Thermistor 10 - INV compressor temperature
40Thermistor 11 - Constant-speed compressor temperature
50Pressure sensor 1 - High pressure
51Pressure sensor 2 - Low pressure

Temperature values are displayed in °C or °F according to the configured unit. Pressure values are displayed in MPa or psi according to the configured pressure unit.

4. F2 - Field setting mode

ItemFunctionSetting values
00Pipe length00 = 40-65 m (default); 01 = 0-40 m; 02 = 65-90 m; 03 = 90-120 m; 04 = 120-150 m.
10Sequential start shift00 = Normal; 01 = 21 sec delay; 02 = 42 sec delay; 03 = 63 sec delay.
11Cooling capacity shift00 = Normal; 01 = Save energy +2°C; 02 = High power 1 -2°C; 03 = High power 2 -4°C.
12Heating capacity shift00 = Normal; 01 = Save energy -2°C; 02 = High power 1 +2°C; 03 = High power 2 +4°C.
13Defrost setting shift00 = End temperature normal; 01 = End temperature higher.
20Forced stop / emergency stop00 = Forced stop (default); 01 = Emergency stop.
21Operation mode selecting method00 = First command priority; 01 = Outdoor external input priority; 02 = Master indoor unit priority.
22Snow falling protection fan mode00 = Normal; 01 = Snow falling protection fan mode.
23Snow protection interval00 = Standard 30 min; 01 = 5 min; 02 = 10 min; 03 = 20 min.
24High static pressure mode00 = Standard; 01 = High static pressure 1 (approx. 30 Pa); 02 = High static pressure 2 (approx. 80 Pa).
28Temperature unit00 = Celsius; 01 = Fahrenheit.
29Pressure unit00 = MPa; 01 = psi.
30Energy saving level00 = Level 1 stop; 01 = 40%; 02 = 60%; 03 = 80%; 04 = 100% capacity.
40Capacity priority in low noise mode00 = Off / quiet priority; 01 = On / capacity priority.
41Low noise mode00 = Off / normal; 01 = On / low noise mode always active.
42Low noise operating level00 = Level 1 (55 dB); 01 = Level 2 (50 dB).
60Backup operation00 = On; 01 = Off. With backup enabled, remaining compressors can operate if one compressor fails.
70-73Electricity meter settings70/71 set electricity meter number; 72/73 set electricity meter pulse value for the meter connected to CN135.
Electricity meter limits: Meter number 000 and 201-299 make CN135 pulse input ineffective. Valid meter numbers are 001-200. Pulse setting 0000 is ineffective; valid pulse settings are 0001-9999.

5. F3 - Function mode

ItemFunctionAction
00Cooling test runForces thermostat ON in cooling.
01Heating test runForces thermostat ON in heating.
02Test run stopStops test run.
10Signal amplifier automatic addressRuns automatic address setting for signal amplifier.
11Indoor unit automatic addressRuns automatic address setting for indoor units on the same refrigerant circuit.
21Vacuuming modeEnables vacuuming mode.
30Error history clearClears all stored abnormal code histories.
32Current time clearSets accumulated current time to 0.
33INV compressor accumulated time clearSets INV compressor accumulated time to 0.
34Constant-speed compressor accumulated time clearSets constant-speed compressor accumulated time to 0.
35Field setting all clearReturns all field setting items to default.
40Abnormal resetClears an abnormal display after repair is complete. Operate after power OFF or power ON of the repaired outdoor unit as specified by the source procedure.
41Maximum memorized indoor unit number resetResets the maximum memorized indoor unit count. The source notes this function is added from Revision Code A.
91Central control forced releaseFor centralized controller communication failure. Releases centralized-control limitations.
Use caution with F3-35: Field setting all clear restores settings to defaults. Record all field settings before using this function.

6. F9 - Error history mode

The outdoor main PCB can store up to 10 abnormal code histories. F9 allows the technician to review them in sequence.

ItemHistory position
001 time ago - newest
012 times ago
023 times ago
034 times ago
045 times ago
056 times ago
067 times ago
078 times ago
089 times ago
0910 times ago - oldest
When more than 10 errors are memorized, the oldest stored error is erased. Use the VR-II troubleshooting/error-code reference to interpret the code displayed for each history position.

7. Technician quick reference

Need to...ModeUse
Check live pressures or temperaturesF1Items 30-40 for thermistors; 50/51 for high and low pressure.
Check compressor/fan operationF1Items 10-15.
Change system configurationF2Select the required field-setting item and confirm its intended effect before changing.
Run cooling/heating testF300 cooling / 01 heating / 02 stop.
Automatic address settingF310 signal amplifier / 11 indoor units.
Clear an error after repairF340 abnormal reset.
Review previous faultsF900 newest through 09 oldest.
Technical reference compiled from the supplied VR-II field setting and monitor documentation. Always follow the applicable model-specific Design & Technical Manual where a setting requires additional detail.