J Series Protective Function List

Compressor, pressure, temperature and inverter protection controls
Technical reference for J Series protective functions, detection conditions and resulting control actions.
The J Series continuously monitors refrigerant temperatures, heat exchanger temperatures, system pressure, current and inverter conditions. When a protection threshold is reached, the system may reduce compressor speed, operate a solenoid valve or stop the compressor to protect the equipment.
Service note: A protective function operating does not by itself identify the underlying fault. Confirm the relevant sensor, pressure switch, refrigerant circuit, electrical condition and associated service data before replacing components.

1. Temperature protection overview

ProtectionPrimary detectionControl response
Discharge temperatureDischarge temp thermistorProgressive compressor speed reduction, SV2 operation, or compressor stop depending on protection level.
Cooling overloadHeat exchanger mid thermistorCompressor speed reduction or SV1 operation.
Heating overloadHeat exchanger mid thermistor (indoor unit), maximum valueCompressor speed reduction or SV1 operation.

2. Pressure protection overview

ProtectionDetect partResult
High pressure protectionPressure switch 1Compressor stops. High pressure error is generated after repeated operation as listed below.
Low pressure protection 1 / 2Pressure switch 2Compressor stops. Error criteria vary according to the protection stage and timing condition.

3. Electrical and inverter protection overview

  • Active filter detected protection: Stops the compressor when an open condition is detected in the active filter element.
  • Active filter over voltage protection: Stops the compressor when excessive voltage is detected.
  • Current release protection: Reduces compressor speed by 1 Hz every 2 seconds until the current returns to the release value.
  • IPM over current: Stops the compressor when the detected current reaches the specified range.

4. Protective function list

No.Protective FunctionDetect PartsCondition of Protection DetectiveFunction
1Discharge temp protection 1Discharge temp thermistorStart: 108°C more.
Release: 100°C less (120sec)
Compressor speed is decreased by 10Hz/120 sec until it becomes lower than 108°C.
2Discharge temp protection 2Discharge temp thermistorStart: 103°C more.
Release: 88°C less (120sec)
SV2 is opened.
3Discharge temp protection 3Discharge temp thermistorStart: 118°C more.
Release: 93°C less (10min)
Compressor stops.
Discharge temperature error by 3 times within 40 min.
4Cooling overload protection 1Heat exchanger mid thermistorStart: 59°C more.
Release: 52°C less (120sec)
Compressor speed is decreased by 10Hz/120 sec until it becomes lower than 59°C.
5Cooling overload protection 2Heat exchanger mid thermistorStart: 61°C more.
Release: 52°C less (120sec)
SV1 is opened.
6Heating overload protection 1Heat exchanger mid thermistor (Indoor unit) Maximum valueStart: 56°C more.
Release: 47°C less (120sec)
Compressor speed is decreased by 10Hz/120 sec until it becomes lower than 47°C.
7Heating overload protection 2Heat exchanger mid thermistor (Indoor unit) Maximum valueStart: 57°C more.
Release: 47°C less (120sec)
SV1 is opened.
8High pressure protectionPressure switch 1Start: Pressure SW OFF
[609psi (4.2MPa) more]
Release: Pressure SW ON
[464psi (3.2MPa)]
Compressor stops.
High pressure error by 2 times within 20 min.
9Low pressure protection 1Pressure switch 2Start: Pressure SW OFF 10 minutes.
20 min after compressor started up
Release: Pressure SW ON 3 minutes
comp stop
Compressor stops.
Low pressure error by 2 times within 40 min.
10Low pressure protection 2Pressure switch 2Start: Pressure SW OFF
A compressor starts for the first time and it is less than 1 minute.
Release: Pressure SW ON 3 minutes
comp stop
Compressor stops.
Low pressure error by 5 times within 30 min.
11Active filter detected protectionElement in active filterStart: Detected open
Release: Release open detection
Compressor stops.
12Active filter over voltage protectionElement in active filterStart: Detected excessive voltage
Release: Release excessive voltage detection
Compressor stops.
13Current release protectionDetect circuit in PCBStart: Setting current limit value ※1
Release: Setting current limit value-1A
Compressor speed is decreased by 1Hz / 2 sec until it becomes to the release current value.
14IPM over currentElement in IPMStart: Detected current 61.4∼83.8A
Release: Release by compressor stop
Compressor stops.
Abnormal stop by detecting 5 times within 40 sec after start-up.
※1: Depends on DIP-SW setting.

5. Practical diagnostic use

  • Identify which protective function is active or which error history is being recorded.
  • Use the Detect Parts column to identify the sensor, switch, PCB circuit or IPM element involved in the protection logic.
  • Compare the actual operating condition with the listed start and release thresholds.
  • Where the function reduces compressor speed or opens SV1/SV2, confirm whether the system recovers before the higher-level protection is reached.
  • Where repeated compressor stops generate an error, check the repetition count and time window shown in the table.