General Assist Technical Reference

J Series Outdoor Fan Control

Cooling fan-speed control, intermittent operation and heating behaviour
Technical overview of J Series outdoor-unit fan control logic
During cooling operation, the outdoor fan speed is controlled primarily from the outdoor heat-exchanger middle temperature thermistor value THHMO. During heating operation, the outdoor fan operates at Hi continuously.

1. Cooling operation

Outdoor fan-speed selection during cooling operation is performed using the detected value of the outdoor heat-exchanger middle temperature thermistor, THHMO.

  • When cooling starts from a stopped condition, the outdoor fan operates at the initial fan speed or at the fan speed stored in memory.
  • When cooling restarts after thermostat OFF, the fan speed that was operating immediately before cooling stopped is memorised and operation restarts at that fan speed.

2. Cooling fan-speed table

StepFan speed — normalFan speed — silent operation modeIntermittent output
Step 1HiLo
Step 2LoLo
Step 3Intermittent 16.0 sec ON / 3.0 sec OFF
Step 4Intermittent 26.0 sec ON / 6.0 sec OFF
Step 5Intermittent 36.0 sec ON / 8.7 sec OFF
Step 6Intermittent 43.5 sec ON / 7.4 sec OFF
Step 7Intermittent 54.7 sec ON / 15.4 sec OFF
Step 8OFF
Important: Intermittent fan operation is a normal control state. Depending on THHMO, the outdoor fan may cycle ON and OFF rather than run continuously.

3. Change of cooling-mode fan speed

The outdoor fan motor is controlled so that the heat-exchanger middle temperature thermistor THHMO remains within a target control range.

  • If THHMO falls below THHMO-min, fan speed is reduced by one step from the current fan speed.
  • If THHMO rises above THHMO-max, fan speed is increased by one step from the current fan speed.
  • THHMO-max is fixed at 55°C.
  • THHMO-min changes according to outdoor temperature THo.
Outdoor temperature thermistor THoTHHMO-minTHHMO-max
THo < 20°C38°C55°C
20°C ≤ THo < 40°C0.35 × THo + 3155°C
40°C ≤ THo45°C55°C
How THHMO-min changes:
Below 20°C outdoor temperature, THHMO-min is fixed at 38°C. Between 20°C and 40°C, it rises linearly using 0.35 × THo + 31. At 40°C outdoor temperature and above, THHMO-min is fixed at 45°C. THHMO-max remains 55°C throughout.

Example target values

Outdoor temperatureTHHMO-minTHHMO-max
10°C38°C55°C
20°C38°C55°C
30°C41.5°C55°C
40°C45°C55°C

4. Heating operation

During heating operation, the outdoor fan operates at Hi all the time.

5. Diagnostic interpretation

Observed behaviourControl interpretation
Fan slows during coolingThis may be normal if THHMO has dropped below THHMO-min.
Fan speeds up during coolingThis may be normal if THHMO has risen above THHMO-max.
Fan repeatedly cycles ON and OFFThe controller may be operating in one of the five intermittent fan-speed steps.
Fan runs continuously at Hi in heatingNormal operation according to the supplied J Series fan-control information.
Technical note: This article summarises the J Series outdoor fan-control information supplied. Exact control behaviour can vary by model and operating condition. Always refer to the applicable service manual when diagnosing a specific outdoor unit.