Overview

This chart details the external input specifications for Fujitsu General VRF outdoor units, controllers, and interface modules, outlining available functions, connection points, and wiring parameters.
These inputs allow integration with Building Management Systems (BMS), energy monitoring devices, or external control systems for improved operational flexibility.


Available Input Functions

Depending on the unit type, the following input control functions are supported:

  • Emergency Stop — Immediately halts all operation.

  • Low Noise Mode — Reduces fan and compressor speed for quieter operation (selectable levels).

  • Cooling/Heating Priority — Determines mode priority when operating in mixed environments.

  • Outdoor Unit Operation Peak Control — Enables staged energy-saving levels (30–00 to 30–03).

  • Batch Stop — Allows system-wide stop control via external input.

  • Power Usage Information Input — Receives pulse data from electricity meters for monitoring.

  • All ON / All OFF Control — Centralised start/stop input from external switch or BMS.


Signal and Electrical Characteristics

Signal TypeTerminal VoltageExternal Power SupplyAllowable CurrentCable TypeMax Cable Length
Edge / Pulse (+3)DC12–24VDC12V / DC24V5–10 mA or lessAWG22 (Twisted)25–150 m

Note: When using “Apply Voltage” type signals, the polarity for PIN 1 is positive (+).
For “Pulse” signal type, set DIP SW2–2 = ON.


Connection Terminals

Terminal IDFunction ExampleTypical Application
CN131–135 (PIN1–2)Operation control / Batch stopVRF Outdoor Units
CN6–CN12Remote / Touch Panel InputsCentral Remote Controller (UTY-DGGY / UTY-DTGY)
CN401 / CN402Input from power meter / RB UnitEnergy Monitoring Interface
CNA01 / CNA02External Control InputsBMS or third-party interfaces

Applicable Components

  • Outdoor Units: VR-II, V-II, J-II, and J series

  • Controllers: UTY-DGGY (Central Remote), UTY-DTGY (Touch Panel)

  • RB Units: UTP-RX01A(H/B), UTP-RX04A(H/B)


Additional Notes

  • Emergency stop and batch stop are dry-contact type signals.

  • When using outdoor unit operation peak control, select energy-saving level via Function No. 30–00 to 30–03:

    • 30–00: Stop

    • 30–01: 40%

    • 30–02: 60%

    • 30–03: 80–100% operation

  • Low noise levels can be selected using 42–00 to 42–02 (Level 0–2).