General Assist Technical Reference
UTY-RNNYN Temperature Limitation
Setting the heating upper limit and cooling/dry lower limit
Applicable controller: UTY-RNNYN backlit wired remote controller
The UTY-RNNYN wired controller allows the available temperature range to be restricted using DIP Switch Bank 2. Switches 2-1 to 2-3 set the minimum cooling and dry temperature, while switches 2-4 to 2-6 set the maximum heating temperature.
Safety notice: Isolate power to the air-conditioning system before removing the controller cover or changing DIP switch settings. Controller access and configuration should be completed by suitably qualified personnel.
1. Switch functions
| DIP switches | Function |
|---|---|
| 2-1, 2-2 and 2-3 | Sets the minimum selectable temperature in Cooling and Dry modes. |
| 2-4, 2-5 and 2-6 | Sets the maximum selectable temperature in Heating mode. |
2. Heating upper temperature limit
Use DIP switches 2-4, 2-5 and 2-6 to set the highest temperature that can be selected in Heating mode.
| 2-4 | 2-5 | 2-6 | Heating maximum |
|---|---|---|---|
| OFF | OFF | OFF | 30°C |
| ON | OFF | OFF | 26°C |
| OFF | ON | OFF | 25°C |
| ON | ON | OFF | 24°C |
| OFF | OFF | ON | 23°C |
| ON | OFF | ON | 22°C |
| OFF | ON | ON | 21°C |
| ON | ON | ON | 20°C |
3. Cooling and Dry lower temperature limit
Use DIP switches 2-1, 2-2 and 2-3 to set the lowest temperature that can be selected in Cooling or Dry mode.
| 2-1 | 2-2 | 2-3 | Cooling/Dry minimum |
|---|---|---|---|
| OFF | OFF | OFF | 18°C |
| ON | OFF | OFF | 22°C |
| OFF | ON | OFF | 23°C |
| ON | ON | OFF | 24°C |
| OFF | OFF | ON | 25°C |
| ON | OFF | ON | 26°C |
| OFF | ON | ON | 27°C |
| ON | ON | ON | 28°C |
4. Configuration procedure
- Turn the air-conditioning system off and isolate the power supply.
- Remove the front cover of the UTY-RNNYN controller.
- Locate DIP Switch Bank 2 on the rear of the controller.
- Set switches 2-1 to 2-3 for the required Cooling/Dry minimum.
- Set switches 2-4 to 2-6 for the required Heating maximum.
- Reassemble the controller and restore power.
- Confirm that the selectable set temperature range matches the required limits.
Important: The cooling minimum must remain lower than the heating maximum. Select settings that provide a practical operating range for the site.
5. Example
To restrict the controller to a range of 22°C to 24°C:
- Cooling/Dry minimum 22°C: 2-1 ON, 2-2 OFF, 2-3 OFF.
- Heating maximum 24°C: 2-4 ON, 2-5 ON, 2-6 OFF.
This guide applies specifically to the UTY-RNNYN wired remote controller. Confirm the controller model before changing any switch settings.