As problem of title, I have received the problem report from quality assurance department.

I would like to inform about problem report detail.

  • Problem detail
    Product ; ARTG45LHTA
    Quantity ; 1(Serial isT001890)
    Problem contents ;
    Error A1 was occurred. And technician found the trace of leak oil at heat exchanger.
    FG AUST carried out the pressurization test by 3.5 MPa. Then, leak checker has found leak at below 3 place.

    Fig.1 leak test at FG AUST
  • Analysis result.
    < Investigation by factory’s testing process>
    Charge Helium gas by 1.2 MPa. Then, Inspect by leak detector.
    ⇒Leak could find by factory testing process.
  • <Sink test by using sample unit>
    FGL carried out the sink test after charge helium gas of 1.2MPa.
    As the result, they found 5 leaks at straight piping section of hairpin.


    Fig 2. Sink test

    At exterior of hairpin of leak place, FGL found the black discoloration of hairpin.

    Fig 3. Exterior of hairpin of leak place Fig.4 Cross section of hairpin of leak place.
  • Speculation of this result’s cause.
    FGL guess that metal corrosion had proceeded from external by effect from usage environment(installation place).
    Then, metal corrosion became the cause of leak.
    however, at this site, there is not special point at usage environment(installation place).
    Therefore, They could not specify this problem’s cause.
    So, if similar problem will occur, please let us know(with usage environment(installation place)’s information).