As problem of title, I have received the problem report from quality assurance department.

I would like to inform about problem report detail.

  • Problem detail
    Product : AOTG30LFTC(T014795)
    Problem contents :
    Could not do turned on the product, technician found that the fuse holder and fuse are nothing on the outdoor unit.
  • Analysis result
    )1 Check the actual sample unit.

    Photo 1 ; Fuse holder and fuse(TLC 25A and FSV 10V) was not attached.
    Photo 2 ; There was scar which may get when screw have been connected.
    Therefore, fuse holder was attached before.
    Photo 3 ; There was scare which may get when fuse wire are connected.
    (as to correct wiring diagram, please refer to attached “GS14-020 Appendix 1”)
    Photo 4 ; The ruins of a file on the PCB
    Photo 5 ; There was not fuse(FSV 10A)
    Photo 6 ; Fuse cover and fuse(FSV10A) are fallen.

    )2 Operating confirmation in factory line
    after fuse holder , fuse(TLC 25A) and fuse(FSV10A) are attached, sample unit operated correctly.

    )3 Checked the manufactured record
    Based on manufactured record, any problem was nothing when this product was manifested. (GS14-020 Appendix 2)
  • Speculation of this result’s cause.
    FGL guess;
    “Fuse(TLC 25A) was nothing”, and, “Fuse wire are connected to terminal directly”, and “indoor unit turned on.”
    As the result, fuse(FSV 10A) became short.
    it reproduced by replication test.(GS14-020 Appendix 3)

    FGL’s opinion is that it is not occurred at factory.