As problem of title, I have received the problem report from quality assurance department.

I would like to inform about problem report detail.

  • Problem detail
    Product : ASTG12LVCC (serial number ; unknown)
    Problem contents : when cooling operation, refrigerant noise was occurred.
  • Analysis result
    they could not analysis, because sample unit could not get.
    But, same problem(please refer to attached e-mail) had been occurred.
    heat exchanger of attached e-mail’s product(ASTG09LVCC) is same as ASTG12LVCC’s one.
  • Speculation of this result’s cause.
    <Same as GS14-031>
    Welding had been carried out in the state of insufficient pipe parts insertion.
    Therefore, solder had flowed into the pipe.
  • Measure
    As to piping insertion method, factory prescribed like attached pdf file.
  • Measure to product
    Already installed product; ; measures by each location if problem is occur.
    Stock product; no measures.
    Manufacture product ; already measured